MODELS: TVA, TVE & TVS IOM Manual 

 

 

the  remote  disconnect  device  prior  to  removing  the  fan/motor  shield.  Do  not    use    the    motor    speed 
switch  as  a  disconnect  method.  All  wiring  must  enter  the  unit  through  designated  openings  and  not 
through the riser stub out openings. 

Supply Air Grille Installation 

 

The grille is a snap-in fit into the collar on the unit. If the unit has a ducted supply, side supply air grilles 
are provided  with a balancing damper. If  the  unit   has  two  unit   mounted  grilles and   is  not ducted,  
one  of  the  grilles  is  provided    with  a  damper.    This  grille  is  to  be  fitted  to  the  opening  which  requires       
the lesser of the two air flows (for example the bedroom). 

 

Return Air/Access Panel Installation 

 
 

Type with quarter turn fasteners: 

 

1. 

Insert  the  square  shaft  of  the  fastener  into  the  recessed  hole  in  the  panel.  Put  the  plastic 
washer onto the shaft, followed by the retainer. Push the retainer as far as possible so that it 
firmly holds the fastener in place. 

2. 

Put  the  pawl  onto  the  shaft  and  position  it  so  that  the  pawl  will  pull  the  panel  tightly  against 
the wall. Tighten the lock screw in the pawl. 

3. 

Install the filter in the panel, hook the panel over the bottom collar of the fan coil unit, rotate 
the panel upright so that it is against the wall and turn the head of the fastener clockwise to 
the locked position. 

 

Type with a hinged filter door in the upper half of the grille panel: 

 

1. 

If the drywall has not been installed flush with the outer edge of the collar on the unit and if a 
gap  exceeding  ½”  exists  between  the  inner  surface  of  the  drywall  and  the  outer  edge  of  the 
collar, the opening will have to be sleeved. 

2. 

Insert the grille panel into the 2” deep collar on the unit so that the grille frame is against the 
drywall. 

3. 

Lift the  hinged filter  door to the  horizontal position and secure the grille panel by  driving  two 
sheet  metal  screws  through  the  inside  of  the  grille  frame  and  into  the  collar  on  the  unit.  Do  
not over-tighten the screws as this can distort the frame. 

4. 

Install the filter into the channels behind the grille and close the filter access door. 

 

Thermostat Installation 

 

1. 

Unit  mounted  thermostat 

–  Connect  the  wires  from  the  thermostat  to  the  wire  harness 

usually inside the electrical box using the plug provided or wire nuts.  Fit the  thermostat onto 
the  electrical  box  using  the  machine  screws  provided.  The  electrical  box  is  located  on    the 
front of the unit, above the return air panel. 

 

2. 

Remote mounted thermostat 

– Run low voltage wires from the 24V thermostat on the wall 

back to the terminal strip inside the unit. 

Содержание TVA

Страница 1: ...720 Columbus Road Mississauga Ontario Canada L5T 2G1 Tel 905 6703595 Fax 905 6703592 www temspec com Vertical Stack Fan Coil Units Models TVA TVE TVS INSTALLATION OPERATION AND MAINTENANCE MANUAL 141111 ...

Страница 2: ... agent and Temspec notified within 24 hours Remove the inlet service panel and check the fan wheel for free rotation by spinning it manually Slight misalignment can be corrected by repositioning the motor or by loosening the fan hub set screw and repositioning the fan on the motorshaft Check riser projections at each end of the cabinet for damage that would prevent making an acceptable piping conn...

Страница 3: ...ot necessary to use a pad under the unit Fire stopping the floor opening and making good the riser insulation at the floor opening is the responsibility of the contractor Check that the drain hose is not kinked before soldering the condensate riser If the risers incorporate expansion compensation loops remove the support brackets after anchoring the risers The fan coil unit has unions at the shut ...

Страница 4: ...ng the run out to contact the edge of the slot in the sheet metal potentially causing failures or leaks Also ensure that the condensate riser stub out is at 90 to the cabinet so that the drain hose is not kinked 4 Riser anchoring is required for two purposes The risers are anchored to the floor slab at one or more points in the height of the building so that they do not slip down under gravity The...

Страница 5: ...he page in the submittals which shows where the screws can be located to avoid damaging internal components When using the panel which has quarter turn fasteners the drywall must be attached to the front The sides and back can be framed 2 Framing Frame the unit using metal studs The flange around the return air access opening is 2 deep The type of return air panel which has a hinged filter door in...

Страница 6: ...lar of the fan coil unit rotate the panel upright so that it is against the wall and turn the head of the fastener clockwise to the locked position Type with a hinged filter door in the upper half of the grille panel 1 If the drywall has not been installed flush with the outer edge of the collar on the unit and if a gap exceeding exists between the inner surface of the drywall and the outer edge o...

Страница 7: ...dge of the door and sharply pull the door forwards Lift the door to the horizontal position The filter is now accessible and is removed by sliding it upwards out of the channels behind the grille Annually before the start of the cooling season Remove the return air access panel from the wall Remove the two sheet metal screws which secure the panel that shields the fan assembly Pull the shield pane...

Отзывы: