MODELS: TVA, TVE & TVS IOM Manual 

 

 

 

Design and Take-off Precautions 

 

Attention  should  be  paid  to  the  height  of  drywall  which  encapsulates    ductwork    in  a  bulkhead.  Note  the  
height  of  the  side  supply  air  opening  shown  in  the  submittal  and  ensure  that  the  drywall  does  not  interfere 
with  the  side  wall  grille.  Make  allowance  for  the  1”  flange  around  the  grille.  Call  Temspec  at  the  time  of 
submittal  review  if  side  supply  air  openings  need  to  be  lowered  or  rotated  to  a  vertical  position  to  avoid 
interference with walls or doors. 

Temspec  does  not  include    wall  sleeves    which  might  be  needed  to  bridge    a  gap  between  the  grille  collar    
on  the  unit  and  the  drywall  surface,  howsoever  caused.  Also  floor    sleeves,    extension    sleeves    through 
shear walls and extension of thermostat speed switch wiring through shear walls are not included. 

It is  important to  accurately  locate the floor sleeve relative to the fan coil and  the drywall. If subsequently  a 
wall sleeve is used because the unit is incorrectly located back from the face of the drywall, a problem with 
access for  servicing can arise  if  the sleeve depth is  too long (over 4”).  Also note that the return air panel  
of the type which attaches with quarter-turn fasteners cannot be used with a sleeve and ½” drywall must be 
attached directly to the front of the unit. 

 

Inspection Upon Receipt of Equipment 

 

The  entire  shipment  should  be  inspected  for  damage,  either  readily  visible  or  concealed.  Any 
damage  must  be  noted  on  the  freight  bill  by  the  carrier’s  agent  and  Temspec  notified  within  24 
hours. 

 

Remove  the  inlet  service  panel  and  check  the  fan  wheel  for  free  rotation  by  spinning  it  manually. 
Slight  misalignment  can  be  corrected  by  repositioning  the  motor  or  by  loosening  the  fan  hub  set 
screw and repositioning the fan on the motor shaft. 

 

Check  riser  projections  at  each  end  of  the  cabinet  for  damage  that  would  prevent  making  an 
acceptable piping connection. 

  Check  internal  piping,  coil  and  valve  packages  for  possible    transit    damage.    If  contractor  /  

installer  deem  it  necessary  to  tighten  mechanical  fittings  Temspec  does  not  assume  any 
responsibility  for  this  procedure.  It  is  stressed  that  the  component  manufacturer's  recommended 
procedures be strictly followed. 

 

Thermostats, speed switches and other accessories which have been shipped separately should 
be inspected for quantity and transit damage. 

 

 

Two-way Control Valves. 

• 

When  two    way  valves    are  used,  pump  and  chiller  bypass    or  pump  speed  control  must   
be included in the system. This is necessary to ensure that the close-off pressure rating of 
the valve is not exceeded. This also helps to minimize noises during the shoulder season. 
The maximum close-off pressure rating is given in the submittals. 

 

 

Electrical Connection 

• 

It  is  assumed  that  the  fan  coil  unit  will  be  in  a  dedicated  electrical  circuit.  If    the  unit  is          
to  be  in  a  circuit  which  includes  electrical  outlets    or  other  electrical  devices,    Temspec  
must be informed prior to releasing the units for production. 

 

Handling 

 

The fan coil units must be handled with the due care required for an HVAC unit. Avoid dropping or jarring 

the unit during offloading and moving the unit into position. Do not lift the unit using the riser pipes. 

Содержание TVA

Страница 1: ...720 Columbus Road Mississauga Ontario Canada L5T 2G1 Tel 905 6703595 Fax 905 6703592 www temspec com Vertical Stack Fan Coil Units Models TVA TVE TVS INSTALLATION OPERATION AND MAINTENANCE MANUAL 141111 ...

Страница 2: ... agent and Temspec notified within 24 hours Remove the inlet service panel and check the fan wheel for free rotation by spinning it manually Slight misalignment can be corrected by repositioning the motor or by loosening the fan hub set screw and repositioning the fan on the motorshaft Check riser projections at each end of the cabinet for damage that would prevent making an acceptable piping conn...

Страница 3: ...ot necessary to use a pad under the unit Fire stopping the floor opening and making good the riser insulation at the floor opening is the responsibility of the contractor Check that the drain hose is not kinked before soldering the condensate riser If the risers incorporate expansion compensation loops remove the support brackets after anchoring the risers The fan coil unit has unions at the shut ...

Страница 4: ...ng the run out to contact the edge of the slot in the sheet metal potentially causing failures or leaks Also ensure that the condensate riser stub out is at 90 to the cabinet so that the drain hose is not kinked 4 Riser anchoring is required for two purposes The risers are anchored to the floor slab at one or more points in the height of the building so that they do not slip down under gravity The...

Страница 5: ...he page in the submittals which shows where the screws can be located to avoid damaging internal components When using the panel which has quarter turn fasteners the drywall must be attached to the front The sides and back can be framed 2 Framing Frame the unit using metal studs The flange around the return air access opening is 2 deep The type of return air panel which has a hinged filter door in...

Страница 6: ...lar of the fan coil unit rotate the panel upright so that it is against the wall and turn the head of the fastener clockwise to the locked position Type with a hinged filter door in the upper half of the grille panel 1 If the drywall has not been installed flush with the outer edge of the collar on the unit and if a gap exceeding exists between the inner surface of the drywall and the outer edge o...

Страница 7: ...dge of the door and sharply pull the door forwards Lift the door to the horizontal position The filter is now accessible and is removed by sliding it upwards out of the channels behind the grille Annually before the start of the cooling season Remove the return air access panel from the wall Remove the two sheet metal screws which secure the panel that shields the fan assembly Pull the shield pane...

Отзывы: