Tornado G4 User Manual
26
Other Operating Modes
Monitor Mode
As Basic mode, plus:
• RDM status reporting over RS485
• RDM configuration – settings may be changed remotely or at
the enclosure control panel
Control Mode
As Basic mode, plus:
Enclosure functions as a 1-channel DMX device, with
remote control of the lamp relay
o
DMX level > 75% enables normal relay operation
(normally ON)
o
DMX level < 25% disables normal relay operation
(relay turns OFF)
o
This allows you to force a hard reset of the lamp relay
in the event of a luminaire malfunction
Control mode is recommended for show control
applications, but can be risky in live show operation, since
the DMX slot used for the enclosure MUST be kept high to
prevent the lamp relay from opening.
Service Mode
For trained service personnel only
Normal operation is suspended and the enclosure
functions as a 3-channel DMX device:
o
Lamp Relay (Slot 1)
o
Fans
(Slot 2)
o
Heater (Slot 3)
Service mode is ONLY for troubleshooting – DO NOT use
Service mode for normal operation.