TemperZone OPA 250RLTFP-DZ Скачать руководство пользователя страница 6

- 6 -

Setting the indoor fan speed too high can bring a risk of any 

condensation being sucked off the fins of the indoor coil 

and into the supply air duct. Water could then start leaking 
from the supply air vents and diffusers and corrosion of 
ducting may occur.

Setting the indoor fan speed too high can also bring a risk 
of ‘over-condensing’ (when the unit is heating) which in turn 
could cause the unit to perform more outdoor coil de-ice 
cycles than necessary.

Refer Appendix II Air Handling graphs for min./max. 

airflows.

6.   OPERATION

6.1  User Operation (RS-SSD)

The tempe/– buttons adjust the room set 

temperature. (You can limit the range of user adjustment by 

setting the heating and cooling control limits in the Installer 
menu of the Viking Controller.) 

The Select button toggles the LCD display between current 

‘room’ temperature, ‘set’ temperature, inside relative 

humidity (RH), outside temperature and outside RH. 

The After Hours button starts (or cancels) the after hours 
run timer.

The LCD will also provide other information such as whether 

there are any faults, and if outside air is being used for 
economy cooling, etc. 

6.2 Scheduling

The Viking HVAC Controller, in the unit, can be programmed 

to operate at different time intervals:

• Always On

• Manual (default)

• 7 Day, 1 Event
• 7 Day, 2 Events
• 365 Day, 1 Event
• 365 Day, 2 Events

• After Hours (2 hours default)

• Daylight Saving Time (DST)

• Holidays

Refer to the Viking User & Installer Manual for more 

information and Schedule set-up instructions.

Note: RS-SSD can not be used as an interface to program 

the Schedule.

6.3  Safety Timers

The UC8 receives control signals and transfers the signals 
to the outputs after enforcing safety timers and other 
protection functions. If the compressor is held off, or held 
on, by a safety timer then the display shows 

message ‘H-O-L-d’.
Normal durations of safety timers are:

• Minimum off time 

3 minutes

• Minimum run time  1.5 minutes

• Min. cycle time 

6 minutes (up to 10 compressor 

 

 

 

starts per hour)

• Min. mode change-over time  
 

 

 

10 minutes (cooling to heating or 

 

   

vice-versa)

6.4  Variable Capacity

The OPA unit is equipped with a single variable capacity 
compressor – inverter scroll type. Compressor operating 

capacities are 16%–100% using 1.6V–10V control voltages.

At any time, when operating conditions dictate, system 
protection functions can restrict unit operating capacity.

When a capacity signal is presented that is lower than the 

minimum capacity (for example 0V on input ‘VC’) then the 

compressor operates on minimum duty.

If a unit operates on low capacity for extended periods 

then the unit may periodically perform oil flush cycles. 

Under such operating conditions compressor lubricating oil 
may slowly settle in parts of the refrigeration system other 

than the compressor. Oil flush cycles help to return the 

lubricating oil to the compressor. During an oil flush cycle 

compressor speed is increased for a duration of 1 minute.

Variable capacity indoor air fan – Refer Section 5.3

6.5  Economiser / Economy Cycle

The Economy Cycle function has been pre-set. No on-site 
Installer setting is required.

The Economiser package fitted consists of two opposed 

blade dampers – one for fresh air intake and one for indoor 
return air. A 0–10V dc control signal drives the dampers 
open and closed. This signal comes from the Viking HVAC 
temperature/humidity controller. The return air damper 
will close proportionally as the fresh air damper opens 
proportionally and vice versa. 

The control strategy is by Enthalpy (ie a combination of 
dry and wet bulb temperatures) so that free cooling is 
used without adding any heat load to the building. This is a 
requirement of Australian NCC and NZ Building Code. 

The Viking will shut the F/A damper automatically when it 
outdoor humidity is too high (ie raining) to prevent moisture 
being drawn into the unit 

When Economy Cycle is not operating, the maximum 

amount of fresh air should not exceed 25% of the unit’s 

nominal airflow. 
The fresh air damper’s adjustable stop can be set such 

that it does not close 100%. Many installations require 

a minimum fresh air introduction of 10 – 15% and the 

stop may be set on site to facilitate this. Set the Fresh 

Air damper motor ‘stop’ to the equivalent negative static 

pressure as with F/A damper closed. This is to ensure the 

air flow volume remains constant and does not dramatically 

increase when introducing fresh air. 

Demand Control Ventilation:  

Air Quality (CO

2

) sensors can 

be used to proportionally control the fresh and return air 
dampers (via the Viking control system).

In all situations the UC8 Unit Controller will allow the 
compressors to operate with the fresh air damper open 
providing the refrigeration system is not compromised. 

The compressor(s) could be stopped from operating by 
normal protection devices such as low suction temperature/
pressure or indoor coil frost protection and too many trips 
of either fault could lead to a lock out of the compressor(s) 
operation. Should this occur then a review of the control 
settings may be necessary.

Содержание OPA 250RLTFP-DZ

Страница 1: ...frigerant Class A2L which is mildly flammable The system shall be installed operated and stored in a well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur Be aware that R32 does not contain an odour If indoors the appliance shall be stored in a room away from continuously operating sources known to cause ignition of R32 refrigerant for example an opera...

Страница 2: ...00 mm The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe refer fig 2 Figure 2 Condensate Drains OPEN DRAIN MINIMUM SLOPE 20 mm PER m 1 IN 50 100 mm MINIMUM 200 mm APPROX U TRAP 100 mm APPROX VENT PIPE FOR LONG CONDENSATE DRAIN RUNS 3 REFRIGERATION SYSTEM 3 1 General These OPA models each have a single inverter compressor to provide the flex...

Страница 3: ...ard signal return is terminal 0V Control by a building management system via Modbus RTU or BACnet IP serial communications 4 5 Unit Controller UC8 The unit s UC8 controller receives requests such as Unit On Off Start compressors Activate HEAT Reverse Cycle and transfer the requests to the outputs after enforcing safety timers Figure 4 UC8 Controller The Unit Controller provides several system prot...

Страница 4: ...d pair The cable shield should connect to terminal 0V on the UC8 controller The Master Slave communications cable connected between the UC8 controllers must be removed DIP switch 11 must be set to OFF on both UC8 controllers To avoid collisions of messages on the RS485 serial communications cable it is necessary to ensure each connected UC8 controller has a unique Modbus device address Refer to se...

Страница 5: ...ps 2 to 5 for each compressor 7 Test operation of the compressors when operating in heating mode 8 Check for desired supply air flow rate at each outlet 9 Touch up any outdoor unit paintwork damage to prevent corrosion 10 Sign the check label 5 3 Commissioning of variable speed EC indoor plug fan A unit equipped with variable speed EC indoor plug fan allows adjustment of the fan speed to obtain th...

Страница 6: ...e minimum capacity for example 0V on input VC then the compressor operates on minimum duty If a unit operates on low capacity for extended periods then the unit may periodically perform oil flush cycles Under such operating conditions compressor lubricating oil may slowly settle in parts of the refrigeration system other than the compressor Oil flush cycles help to return the lubricating oil to th...

Страница 7: ...m to deliver the heating when most needed Heating capacity at design conditions may be incorrect As the outside temperature falls heat losses through the walls floor and ceiling increase Check the unit s brochure for information on the minimum maximum operating temperatures 8 3 When heating units have de icing cycles built in to remove ice on the outdoor coil This usually means reversing the cycle...

Страница 8: ...city CAP Capacity 100 Expansion valve 1 opening EE1 Expansion valve 1 75 open Expansion valve 2 opening EE2 Expansion valve 2 75 open 10 UC8 CONTROLLER DISPLAY 11 VIKING CONTROLLER FACTORY SETTINGS Installer to check settings for site suitability and adjust as necessary SMT920 Controller RS SSD Wall Control Function Factory Settings changes from defaults Function Factory Setting PIN number 21 don ...

Страница 9: ...s an indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for example a stuck accurator or loose wiring to an EEV The protection is activated when discharge superheat exceeds 60K for longer than 30 minutes The display shows the message Hi dSH when protection i...

Страница 10: ...cked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician The display shows the code of the fault that caused the lock out condition A unit that is locked out can be unlocked using any one of the following methods Remove mains power from the unit for at leas...

Страница 11: ... 3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5 3 5 4 0 8V 7V 5V 6V 9V 8V 7V 6V 5V 2 9 2 0 1 5 1 0 4 7 2 4 3 4 4 3 1000 1500 2000 2500 3000 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 500 NOMINAL 9V 8V ...

Страница 12: ...o scroll through list IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Evap temperature Et C Indoor Return air temperature C Suction Line temperature SLt C Indoor Supply air temperature C Suction Superheat SSH K Indoor fan amps A Discharge Line Pressure dLP kPa Fresh Air ...

Отзывы: