9 Lock-out
Each protection function has a trip counter. A trip counter
is reset to 0 whenever the compressor run request is
removed. Any trip that has occurred more than 12 hours
ago is removed from the trip count. For some protection
functions, when the trip counter reaches value 3 (i.e. three
consecutive trips occur) then the unit is “locked out”.
When a unit is locked out the compressor is not allowed to
start. Lock-out is designed to protect the compressor from
repeatedly starting when a serious fault exists that requires
the attention of a service technician.
The display shows the code of the fault that caused the
lock-out condition.
A unit that is locked out can be unlocked using any one of
the following methods:
• Remove mains power from the unit for at least 3 seconds,
then restore power.
• Issue an ‘unlock’ command via Modbus RTU serial
communications.
• Reset the controller via Modbus RTU serial
communications.