TemperZone OPA 250RLTFP-DZ Скачать руководство пользователя страница 3

- 3 -

Figure 3. Pressurisation bung locations

4.   CONTROLS

4.1  Electrical Requirements

Electrical work must be done by a qualified electrician.

 DANGER! LIVE ELECTRICAL CONNECTIONS. DISCONNECT MAINS 

POWER BEFORE WORKING ON UNIT. ONLY QUALIFIED PERSONS 

WHO ARE COMPETENTLY TRAINED SHOULD PERFORM SERVICE AND 

MAINTENANCE TASKS.

The outdoor unit must be wired directly from a distribution 
board by means of a circuit breaker and a mains isolator 
provided – preferably close to the unit.

Note:

 DO NOT USE REWIRABLE FUSES.

A 24 hour power supply to the compressor crank case 
heaters is required, otherwise the warranty is void.

4.2  Control options

These OPA Econex (-DZ) units are controlled using the 

Smart Temp RS-SSD wall control (indoor Smart Sensor). 
Other options include the following:

• 24V AC and 0-10V signals from an external controller or 

thermostat

• Remote on/off switch and/or time clock
• Modbus RTU serial communications over RS485 

connection

• BACnet-IP serial communications over Ethernet 

connection (with optional gateway module)

Standard reverse cycle units are suitable for use with 
thermostats and controls with manual heating/cooling 
selection or automatic change-over.

A unit wiring diagram is supplied alongside the electrical 

board and in the Specifications document

.

4.3  Remote on/off

The UC8 has an input for a remote on/off function on 

terminal ‘On’, signal return is terminal ‘0V’. When used the 

remote on/off terminals should connect to a voltage-free 
relay contact. When not used the remote on/off terminals 

should be shorted (‘looped’) – refer wiring diagram.

4.4  Capacity control

OPA Econex units offer the following capacity control 

options:

• Automatic control when the unit connects to the 

RS-SSD

 

wall control.

• 0-10V compressor control signal via terminal ‘VC’ on the 

UC8 circuit board, signal return is terminal ‘0V’.

• 0-10V indoor fan control signal via terminal ‘VF’ on the 

UC8 circuit board, signal return is terminal ‘0V’.

• Control by a building management system via Modbus 

RTU or BACnet-IP serial communications.

4.5  Unit Controller (UC8)

The unit’s UC8 controller receives requests such as ‘Unit 

On/Off’, ‘Start compressors’, ‘Activate HEAT (Reverse 

Cycle)’ and transfer the requests to the outputs after 

enforcing safety timers.

Figure 4. UC8 Controller

The Unit Controller provides several system protection 
functions. These are covered in Appendix I (p.9).

For additional information, refer to the UC8 Controller label 
on the unit or www.temperzone.biz for operation & fault 

diagnostics information; model search ‘UC8’.

References available:

UC8 Operation Manual : Air-to-Air Units

UC8 Fault & Display Messages (as per unit label)

UC8 Quick Reference and Operation Fault Diagnosis

UC8 Troubleshooting Guide
UC8 Modbus Communications
UC8 BACnet Communications
UC8 Master-Slave Connection

4.6  Viking Controller for Economiser/Economy Cycle

OPA Econex (-DZ) units utilise: (i) Viking SMT-920 HVAC 

Controller, (ii) RS-SS outdoor air temp. & humidity sensor, 

and (iii) RS-SSD wall control (aka indoor Smart Sensor). 
Air Quality (CO

2

) sensors, 0–10V, are available to work with 

this Controller.

The controlller is factory set for ‘Enthalpy control’

 to comply 

with Australian NCC and NZ Building Code.

Refer Section 6.3 Operation for more information.

4.7  Viking/Smart Temp RS-SSD wall control

Connect the RS-SSD to the unit using a shielded twisted 

pair type cable, suitable for RS485 communications. Signal 

wires 1 and 4 should form one twisted pair. 

Note

: The cable shield must be connected to a suitable 

Earth. Do not connect at both ends. 
RS-SSD has its own DIP switches that are factory preset, 

as per OPA unit wiring diagram.

Connect the thermostat as follows:

RS-SSD Connection:

S1 S2 S3 S4

Smart Sensor

Viking HVAC Controller

RS-SSD

1

2

3

4

Shielded twisted 
pair 4 core

Shared with 
RS-SS outdoor 
air sensor

Note: The RS-SSD can not be used simultaneously with a 

2-wire remote sensor. 

Refer RS-SSD Manual for installer options and use.

LCD Display

Push button

©temperzone Ltd 2021

Standard hand unit

Opposite hand unit

Содержание OPA 250RLTFP-DZ

Страница 1: ...frigerant Class A2L which is mildly flammable The system shall be installed operated and stored in a well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur Be aware that R32 does not contain an odour If indoors the appliance shall be stored in a room away from continuously operating sources known to cause ignition of R32 refrigerant for example an opera...

Страница 2: ...00 mm The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe refer fig 2 Figure 2 Condensate Drains OPEN DRAIN MINIMUM SLOPE 20 mm PER m 1 IN 50 100 mm MINIMUM 200 mm APPROX U TRAP 100 mm APPROX VENT PIPE FOR LONG CONDENSATE DRAIN RUNS 3 REFRIGERATION SYSTEM 3 1 General These OPA models each have a single inverter compressor to provide the flex...

Страница 3: ...ard signal return is terminal 0V Control by a building management system via Modbus RTU or BACnet IP serial communications 4 5 Unit Controller UC8 The unit s UC8 controller receives requests such as Unit On Off Start compressors Activate HEAT Reverse Cycle and transfer the requests to the outputs after enforcing safety timers Figure 4 UC8 Controller The Unit Controller provides several system prot...

Страница 4: ...d pair The cable shield should connect to terminal 0V on the UC8 controller The Master Slave communications cable connected between the UC8 controllers must be removed DIP switch 11 must be set to OFF on both UC8 controllers To avoid collisions of messages on the RS485 serial communications cable it is necessary to ensure each connected UC8 controller has a unique Modbus device address Refer to se...

Страница 5: ...ps 2 to 5 for each compressor 7 Test operation of the compressors when operating in heating mode 8 Check for desired supply air flow rate at each outlet 9 Touch up any outdoor unit paintwork damage to prevent corrosion 10 Sign the check label 5 3 Commissioning of variable speed EC indoor plug fan A unit equipped with variable speed EC indoor plug fan allows adjustment of the fan speed to obtain th...

Страница 6: ...e minimum capacity for example 0V on input VC then the compressor operates on minimum duty If a unit operates on low capacity for extended periods then the unit may periodically perform oil flush cycles Under such operating conditions compressor lubricating oil may slowly settle in parts of the refrigeration system other than the compressor Oil flush cycles help to return the lubricating oil to th...

Страница 7: ...m to deliver the heating when most needed Heating capacity at design conditions may be incorrect As the outside temperature falls heat losses through the walls floor and ceiling increase Check the unit s brochure for information on the minimum maximum operating temperatures 8 3 When heating units have de icing cycles built in to remove ice on the outdoor coil This usually means reversing the cycle...

Страница 8: ...city CAP Capacity 100 Expansion valve 1 opening EE1 Expansion valve 1 75 open Expansion valve 2 opening EE2 Expansion valve 2 75 open 10 UC8 CONTROLLER DISPLAY 11 VIKING CONTROLLER FACTORY SETTINGS Installer to check settings for site suitability and adjust as necessary SMT920 Controller RS SSD Wall Control Function Factory Settings changes from defaults Function Factory Setting PIN number 21 don ...

Страница 9: ...s an indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for example a stuck accurator or loose wiring to an EEV The protection is activated when discharge superheat exceeds 60K for longer than 30 minutes The display shows the message Hi dSH when protection i...

Страница 10: ...cked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician The display shows the code of the fault that caused the lock out condition A unit that is locked out can be unlocked using any one of the following methods Remove mains power from the unit for at leas...

Страница 11: ... 3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5 3 5 4 0 8V 7V 5V 6V 9V 8V 7V 6V 5V 2 9 2 0 1 5 1 0 4 7 2 4 3 4 4 3 1000 1500 2000 2500 3000 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 500 NOMINAL 9V 8V ...

Страница 12: ...o scroll through list IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Evap temperature Et C Indoor Return air temperature C Suction Line temperature SLt C Indoor Supply air temperature C Suction Superheat SSH K Indoor fan amps A Discharge Line Pressure dLP kPa Fresh Air ...

Отзывы: