TemperZone OPA 250RLTFP-DZ Скачать руководство пользователя страница 2

- 2 -

2.   INSTALLATION

2.1 Clearance

Refer to diagrams below and in supplied Specifications 

document for minimum clearances.

Figure 1. Clearances

Plant Room Installation

Ensure sufficient ventilation is installed. Discharge air from 

above the unit must be ducted away to prevent recirculation 

of air through the unit. Restricted airflow and/or recirculation 

reduces efficiency. Never install the unit in a totally 

enclosed room.

2.2  Economiser Weathercowl

The Economiser weathercowl (weatherhood) is supplied in 

kitset form and must be assembled, then fitted to the unit 

– usually before the unit is lifted into place (refer separate 
kitset instructions). Screws and pre-drilled holes are 
provided. Ensure all joints are sealed with silicon sealant. 
There must be at least 300mm clearance beneath the 

cowl once it is fitted in place. Ensure the fitted cowl is not 

damaged when unit is lifted into position. 

2.3 Mounting

The unit should be fastened to a firm flat horizontal base 

using the holes supplied in the mounting channels, or using 
universal beam clamps. When the unit is being installed 
on a roof it is recommended that the unit is installed on a 
substantial structure with vibration isolating mounts or pads.

Flexible duct connections are recommended between the 
supply and return ducts and the unit.

The unit is shipped with blocks installed under the 
compressors.  Ensure these blocks are removed from the 
compressor feet prior to starting the unit (not required for 
operation).

Factory filter frames are fitted. Access to the filters is via the 

return air access door.

2.4  Condensate Drains

Condensation can form on both the indoor and outdoor 
air coils. This is normal during unit operation. It is 
recommended the condensate be piped to a suitable 
drainage point to prevent ponding and/or slippery mould 
growth around the base of the unit. 

An optional outdoor coil drain tundish is available (part 060-

000-635) with 25mm OD stub. Alternatively, for a drip free 

installation a separate drain tray beneath the unit could be 
used to drain condensate to a suitable drainage point.

Condensate drains should be ‘U’ trapped outside the unit. 

The trap should have a vertical height of at least 100 mm. 
The drain should have a slope of at least 1 in 50 and must 

not be piped to a level above the unit drain pipe. (refer fig. 2)

Figure 2. Condensate Drains

OPEN
DRAIN

MINIMUM
SLOPE
20 mm PER m
(1 IN 50)

100 mm
MINIMUM

200 mm

APPROX.

'U' TRAP

100 mm

APPROX.

VENT PIPE
FOR LONG
CONDENSATE
DRAIN RUNS

3.   REFRIGERATION SYSTEM

3.1 General

These OPA models each have a single inverter compressor 

to provide the flexibility and economy of variable speed 

operation. The compressor is very efficient at part load.
Each refrigeration system has been charged with R32 

refrigerant; refer Specifications document for amount. 

3.2 Compressor

The compressor is an inverter scroll type. The compressor 
lubricant is polyolester oil (POE). Note, this oil absorbs 
moisture quickly if exposed to open air.

3.3 Economiser

When the outdoor air heat content (enthalpy) is below that 
of the return air, the fresh air damper will open and the 

return air damper close to provide the first stage of cooling. 

A spill air facility in the building may be necessary for when 
the return air damper is closed. The fresh air damper should 
return to minimum setting and the return air damper open 
before the compressors are allowed to operate to provide 

further cooling. Refer Section 6.3 for more information.

3.4  Fresh Air 

Air flow through the damper should not exceed 25% of 

the OPA unit’s nominal air flow. Excessive amounts of low 

ambient fresh air will reduce the performance of a reverse 
cycle OPA unit especially on heating cycle. Fresh air should 
be adjusted to meet CO

2

 sensing requirements.

The damper setting is dependent on the return air duct 

static pressure and the design air flow for the specific 

installation. It is recommended an air flow balance 

commissioning contractor be utilised. Too much fresh air 

introduction may void the OPA unit’s warranty.

3.5  Pressurised Compartment

The compressor/electrical compartment can be pressurised 
with indoor supply air. This assists in keeping dust out of the 
compartment. Two plastic bungs are located near the top 

of the common side-wall (refer Figure 3). Remove only the 

bungs applicable to your type of unit – standard or opposite 
hand; not both sets.

ECONOMISER

WEATHER

HOOD

500 MIN.

 CLEARANCE

500 MIN. CLEARANCE

ELECTRICAL
ACESS DOOR

2000 MIN. CLEARANCE

FILTER
ACCESS
DOOR

MINIMUM CLEARANCE

OPA 250/350 : 1000
OPA 450/560 : 1200

1000 MIN. CLEARANCE

FAN ACCESS

800 MIN. CLEARANCE

Содержание OPA 250RLTFP-DZ

Страница 1: ...frigerant Class A2L which is mildly flammable The system shall be installed operated and stored in a well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur Be aware that R32 does not contain an odour If indoors the appliance shall be stored in a room away from continuously operating sources known to cause ignition of R32 refrigerant for example an opera...

Страница 2: ...00 mm The drain should have a slope of at least 1 in 50 and must not be piped to a level above the unit drain pipe refer fig 2 Figure 2 Condensate Drains OPEN DRAIN MINIMUM SLOPE 20 mm PER m 1 IN 50 100 mm MINIMUM 200 mm APPROX U TRAP 100 mm APPROX VENT PIPE FOR LONG CONDENSATE DRAIN RUNS 3 REFRIGERATION SYSTEM 3 1 General These OPA models each have a single inverter compressor to provide the flex...

Страница 3: ...ard signal return is terminal 0V Control by a building management system via Modbus RTU or BACnet IP serial communications 4 5 Unit Controller UC8 The unit s UC8 controller receives requests such as Unit On Off Start compressors Activate HEAT Reverse Cycle and transfer the requests to the outputs after enforcing safety timers Figure 4 UC8 Controller The Unit Controller provides several system prot...

Страница 4: ...d pair The cable shield should connect to terminal 0V on the UC8 controller The Master Slave communications cable connected between the UC8 controllers must be removed DIP switch 11 must be set to OFF on both UC8 controllers To avoid collisions of messages on the RS485 serial communications cable it is necessary to ensure each connected UC8 controller has a unique Modbus device address Refer to se...

Страница 5: ...ps 2 to 5 for each compressor 7 Test operation of the compressors when operating in heating mode 8 Check for desired supply air flow rate at each outlet 9 Touch up any outdoor unit paintwork damage to prevent corrosion 10 Sign the check label 5 3 Commissioning of variable speed EC indoor plug fan A unit equipped with variable speed EC indoor plug fan allows adjustment of the fan speed to obtain th...

Страница 6: ...e minimum capacity for example 0V on input VC then the compressor operates on minimum duty If a unit operates on low capacity for extended periods then the unit may periodically perform oil flush cycles Under such operating conditions compressor lubricating oil may slowly settle in parts of the refrigeration system other than the compressor Oil flush cycles help to return the lubricating oil to th...

Страница 7: ...m to deliver the heating when most needed Heating capacity at design conditions may be incorrect As the outside temperature falls heat losses through the walls floor and ceiling increase Check the unit s brochure for information on the minimum maximum operating temperatures 8 3 When heating units have de icing cycles built in to remove ice on the outdoor coil This usually means reversing the cycle...

Страница 8: ...city CAP Capacity 100 Expansion valve 1 opening EE1 Expansion valve 1 75 open Expansion valve 2 opening EE2 Expansion valve 2 75 open 10 UC8 CONTROLLER DISPLAY 11 VIKING CONTROLLER FACTORY SETTINGS Installer to check settings for site suitability and adjust as necessary SMT920 Controller RS SSD Wall Control Function Factory Settings changes from defaults Function Factory Setting PIN number 21 don ...

Страница 9: ...s an indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for example a stuck accurator or loose wiring to an EEV The protection is activated when discharge superheat exceeds 60K for longer than 30 minutes The display shows the message Hi dSH when protection i...

Страница 10: ...cked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician The display shows the code of the fault that caused the lock out condition A unit that is locked out can be unlocked using any one of the following methods Remove mains power from the unit for at leas...

Страница 11: ... 3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5 3 5 4 0 8V 7V 5V 6V 9V 8V 7V 6V 5V 2 9 2 0 1 5 1 0 4 7 2 4 3 4 4 3 1000 1500 2000 2500 3000 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 500 NOMINAL 9V 8V ...

Страница 12: ...o scroll through list IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Evap temperature Et C Indoor Return air temperature C Suction Line temperature SLt C Indoor Supply air temperature C Suction Superheat SSH K Indoor fan amps A Discharge Line Pressure dLP kPa Fresh Air ...

Отзывы: