Testing the programmed numbers

Once the unit is programmed, the  

TESTCELL

  command will test all the programmed

numbers.   Simply send the word  

TESTCELL

  (one word, in capital letters) to the cell

number of the unit.  The CM705E will send a text message to all programmed numbers.
The phone sending TESTCELL will receive the message  

“Please verify that a Status

text msg is received at all programmed phone numbers.”  

Sensors

At boot up, the unit will search for attached sensors.   The unit will never alarm on a
sensor it does not detect at boot up.  If you need to add a sensor, turn off the CM705E,
wire in the sensor, then turn the unit back on.  If you need to remove a sensor, remove
the wires from the unit, and reboot the unit.  If you do not, the CM705E will alarm on the
open sensor.  It will also alarm if it detects a wiring short.  

Checking Status

You can send a text message to the phone number of the CM705E to get the current
status of all inputs.  Send 

Status? 

to the unit’s phone number.

 

Daily Status

The CM705E can be programmed to send a daily status text message.  If all sensors
are within limits, the daily stats will say all sensors are within limits.   If one or more
sensors   are   out   of   limits,   it   will   report   the   out   of   limits   sensors   and   the   condition
(temperature, humidity, open, closed, etc.).  

What is an alarm condition?

An alarm condition is anytime a sensor exceeds the upper or lower limit for longer than 
the programmed time delay.  Once an alarm occurs, the buzzer will start beeping (three 
loud beeps every 30 seconds); alarm text messages will be sent from the CM705E 
immediately.  Data Capture software will also send text and emails.  

When the sensor is back in limits for 5 minutes, the CM705E will also send a “back
within limits” text message.  (The 5 minutes is not user adjustable)  **

Power outages alarms are treated in the same manner as temperature sensors.  If the
power out delay time is set to 10 minutes, the CM705E will send the alarm text after 10
minutes of continuous power loss.  When power is restored for 5 minutes, the CM705E
will send a “power is back on” text.   The “power back on” text time delay is not user
adjustable.  

**  If the unit is in alarm, text messages have been sent, and then the unit goes back in
range it must be back in range for five continuous minutes.  If it keeps going in and out
of range, the buzzer will sound, depending on your “out of limits” time delay.  

Page 

4

 of 

8

Содержание CM705E

Страница 1: ...ex Page Number General Description and part numbers 2 Installation 3 Wiring Diagram 3 Testing the programmed numbers 4 Sensors 4 Checking Status 4 Daily Status 4 What is an alarm condition 4 LCD Screen and Cancel Alarm Push button 5 6 Helpful Hints 7 DHCP wired version 7 DHCP wireless version 7 Part Numbers 8 ...

Страница 2: ...uter The unit also stores up to 6 months worth of data in its internal memory which can be retrieved using the free program TG Status or Data Capture Programming the CM705E is accomplished via Data Capture 5 or later software http www temperatureguard com software html Once the unit has been wired to all appropriate sensors connected to the Ethernet network and is registered on the cellular networ...

Страница 3: ...chased with the network adapter Use only the provided 5VDC power adapter Wire all inputs to be used Wiring diagram below Page 3 of 8 CM705E 1v Sensor 1 1 Sensor 8 Dry Contact Inputs v 2 Wiring Diagram side view of enclosure Alarm Relay Output T22 NO T23 NC T24 Common 1 24 DC 5V ON OFF 3 4 ...

Страница 4: ...s the daily stats will say all sensors are within limits If one or more sensors are out of limits it will report the out of limits sensors and the condition temperature humidity open closed etc What is an alarm condition An alarm condition is anytime a sensor exceeds the upper or lower limit for longer than the programmed time delay Once an alarm occurs the buzzer will start beeping three loud bee...

Страница 5: ...rical order To silence the buzzer press and hold the cancel alarm button while the in alarm sensor screen is showing Under normal operation the main LCD screen will be shown Main Screen Second Screen This screen displays the internal sensor current temperature and humidity cellular module status signal strength and battery voltage after pressing the cancel alarm button once You can also scroll thr...

Страница 6: ...losed an open square is an open input Top square is Input 1 second is Input 2 etc If the input is set to water sensor the open square is no water detected the closed square is a wet condition The inputs are not displayed in the scroll through menu unless they are in alarm Sensor 2 is below the lower limit Page 6 of 8 ...

Страница 7: ... down The screen will display Reset to DHCP No Pressing and releasing the button again will toggle the No to Yes Let it boot up while the Yes is dis played and it will be in DHCP mode How do I set the Guard to DHCP wireless version The CM705E cover must be removed Power the unit on When it has completely booted up press the Reset_Defaults button for 6 seconds or until the led goes out Please note ...

Страница 8: ... Ethernet model shipped without a sim card Unit will work on the Verizon network only Add NIST to the part number for calibration certificate New feature added to Rev 17 and higher 04 15 2021 The phone numbers can now be programmed by text message and checked by text message There are 4 available numbers that can be programmed Example To program the 1st number send a text to the unit with the mess...

Отзывы: