AFA1000/1 MK2 Airflow Monitor
Installation & Operating Manual
To Setup the Temperature input using the pushbutton menus:-
1.
Press Enter from the “Requires set up” screen or if the monitor is in the Run screen Press and
Hold the Enter button for 5 seconds until the Main Menu is displayed.
2.
Using the + / - buttons select SET UP, and then select CONFIGURE, then enter the password
(the factory default password is 0-0-0-0), press Enter to continue.
3.
Using the + / - buttons select INPUT 3, and then press Enter, then using the +/- buttons select
ANALOGUE and press Enter, then using the +/- buttons select TEMPERATURE and press
Enter to continue.
4.
Using the + / - buttons select the TEMPERATURE menu and press Enter, this will introduce a
sub menu for the TEMPERATURE settings:-
Note -
the temperature sensor is accurate to °0.5 °C, the offset parameter can be used if the
displayed value needs to be changed to match a 3rd party instrument or other equipment etc.
5.
Using the + / - buttons select the TEMP UNITS parameter and press Enter, then using the +/-
buttons set to °C or °F and press Enter to continue.
6.
Using the + / - buttons select the LOW TEMP ALARM parameter and press Enter, then using
the +/- buttons adjust the value to the required alarm point and press Enter to continue.
7.
Using the + / - buttons select the HIGH TEMP ALARM parameter and press Enter, then using
the +/- buttons adjust the value to the required alarm point and press Enter to continue.
8.
Using the + / - buttons select the SHOW TEMP parameter and press Enter, then using the +/-
buttons set to ON or OFF and press Enter to continue.
9.
Using the + / - buttons select the OFFSET parameter and press Enter, then using the +/-
buttons adjust the value to the required display offset and press Enter to continue, then
select DONE and press Enter to continue.
10.
In the CONFIGURE MENU Using the + / - buttons select the LOW TEMP RELAY parameter and
press Enter, then using the +/- buttons select the required RELAY OUTPUT and press Enter to
continue.
11.
In the CONFIGURE MENU Using the + / - buttons select the HIGH TEMP RELAY parameter and
press Enter, then using the +/- buttons select the required RELAY OUTPUT and press Enter to
continue, then select DONE and RUN.
Testing.
Once the Temperature sensor function has been set up the measured Temperature can be
displayed in the diagnostics menu I/O Status - Sensor data screen described in section 2.8
Parameter
Description
Range
A Temp Units
Display units
°C or °F
B Low Temp Alarm
Sets the Low temperature alarm point
0.0 to High Alarm value
C High Temp Alarm Sets the High temperature alarm point
100.0 to Low Alarm value
D Show Temp
Turns the Temperature display On/Off
Yes/No
E Offset
Allows the measured value to be offset
-5.0 °C to +5.0 °C
Содержание AFA1000/1 MK2
Страница 4: ...1 SAFETY...
Страница 9: ...2 OVERVIEW OF THE AIRFLOW MONITOR...
Страница 19: ...3 FUNCTIONS OPERATION...
Страница 24: ...4 COMPONENTS...
Страница 27: ...5 INSTALLATION...
Страница 32: ...6 CONFIGURATION CALIBRATION...
Страница 36: ...7 AUXILIARY FEATURES CONNECTIONS...
Страница 41: ...8 RS485 COMS OUTPUT...
Страница 48: ...9 WARRANTY...