background image

STEP 11.

 

INSTALLING FLASHING 

Place the flashing over the chimney pipe where it 
penetrates the roof and mark the outline of the flashing on 
the roof. Remove the nails from the shingles inside this 
outline and to the bottom edge of the roof cutout. Coat the 
roof area under the shingles with roofing cement. Slide the 
flashing under the shingles on the sides of the flashing and 
re-nail the top and side shingles. DO NOT nail through the 
lower portion of the flashing. If necessary, cover the side 
and top of the flashing with the salvaged shingles. The 
flashing should cover the lower side of the roof opening as 
pictured in figure 19. 

STEP 12.

 

INSTALLING THE STORM COLLAR 

The storm collar is assembled to the chimney system next. 
Holding the adjustable storm collar with the tab of the collar 
in your right hand, put the collar around the flue pipe. Push 
the tab on the collar through the slot provided. Pull the tab 
through and bend it just enough so that the collar may  be 
raised upward. 
Apply waterproof caulking around the flashing where the 
collar fits around the top of the flashing. Push the storm 
collar down s ecurely on the sealer and flashing. To secure 
the collar, pull the tab through the slot as far as possible 
and bend the tab over to hold it in place. 

STEP 13. INSTALLING THE TERMINATION CAP  

A chimney termination is required to finish the installation. 
The following instructions are for the 82O3D termination. 
Refer to the instructions packed with the termination for 

additional information. 

CHASE INSTALLATIONS 

1. A chase is an enclosure for the fireplace and/or chimney 

that is attached to the outside of the house. It may start 
at the basement floor line, at the first level or at some 
point on the side of the wall. A chase may also be used 
to enclose a chimney from the point where it penetrates 
the roof, to slightly below the termination cap. 

2. The floor under the fireplace must be a solid, continuous 

level surface. Many local building codes also require a 
firestop spacer in the chase at the ceiling level in the 
house. Consult your local building codes to determine 
the requirements for chase installations in your area. 
Remember that all chimney components must have an 
absolute minimum of 1" air space from combustible 
materials. Plan the dimensions of your chase 
accordingly. 

3. A chase should be constructed and insulated like any 

other exterior wall in your home. 

4. A metal cover made by a local sheet metal shop is 

required to complete a chase installation. This cover 
becomes a flashing that prevents water from entering the 
chase. The chase cover should be sealed at the corners. 
A minimum 1" high collar is required at the point where 
the chimney pipe or slip section will penetrate the chase 
cover. It requires 12 5/8" diameter collar. The seam at 
the base of the collar must be watertight. It  may be 
necessary to support the chase cover with framing 
members if the cover is large or has multiple caps. 
Required clearance to combustibles must be maintained. 
Spacers (¼" high) should be used to space the chase 
cover above the wood framing to minimize conduction of 
heat to the wood. 

5. These fireplaces may be installed in a chase using Model 

8203D termination cap. 

All sections of the

 

chimney 

must extend 6" above the chase cover when the 
8203D termination Is used. 

Install the storm collar over 

the 1" collar on the chase cover and caulk between storm 
collar and pipe. The termination is installed to the 
chimney pipe above the chase cover as described in 

figure 20. 

6. If a flush mount is desired, model STD-22 Round Chase 

Cap, ARC-52 Architectural Cap, PRC-12 or LPC-12 
Pyramid Caps, or TC~12 Conical Cap may be used. 
When used, the last chimney section must be no 

more 

than 

12" below 

the chase cover collar. 

All slip sections 

require a minimum 3" lap into the last chimney section. 
Refer to separate installation instructions for each 
termination for details. 

7. It is recommended, but not required, that you insulate 

underneath the fireplace and between the studs on the 
outside wall of the chase to reduce heat loss in cold 
climates. Be sure to use non-combustible insulation 
without paper or plastic backing. 

Never use blown-in 

type insulation in a chase.  Insulation should never 
cover the top or sides of

 

the fireplace or any part of

 

the chimney system. 

To

 

further reduce heat loss, it is 

recommended that 1/2" gypsum wallboard be installed 
over the insulation on the inside of the chase. Plan chase 
dimensions accordingly. 

8. Chases with two or more chimneys should be 

constructed wide enough to allow chimneys to be spaced 
at least 24" on center from each other. When chimneys 
are closer than this, smoke from one may be drawn 
down the flue of the adjacent chimney. When chimneys 
must be installed closer than this smoke transfer may be 
prevented by vertically offsetting adjacent terminations 
by 12" to 18" or by installing 12" to 18" high sheet metal 
shields between terminations. 

WARNING: DO  NOT PACK REQUIRED AIR SPACES 

WITH INSULATION OR OTHER MATERIALS.

 

Figure 19 

Installing 
flashing and 
storm collar 

Figure 20 

12 

Содержание TFC39-22

Страница 1: ...ulating fireplace Optional Combustion Air Kits AIR 5 AIR 5A AIR 5B AIR 7 AIR 3B Optional Glass Doors CLS 4 CLS 3 CX31 CX41 Optional Blower Kit BL3922 Requires junction box JB 2 TLC39 22I With insulated outer wrap 39 louvered heat circulating fireplace with fully insulated outer wrap Optional Combustion Air Kits AIR 5 AIR 5A AIR 5B AIR 7 AIR 3B Optional Glass Doors CLS 4 CLS 3 CX31 CX41 Optional Bl...

Страница 2: ...es 5 Determining the R Values 6 Fireplace Installation 7 Installing the firebox 7 Installing the chimney 8 Chimney termination height 10 Foot Rule of Thumb 9 Offset installations 9 10 11 Flashing and storm collar 12 Installing the termination 12 Chase installations 12 Installing a gas line 13 Cold climate installations 13 Mobile home installation 14 Finishing Your Fireplace 15 16 Using Your Firepl...

Страница 3: ... combustible wall is 17 See Figure 4 for alternative wall shields and required R factors 7 If the floor in front of the fireplace is combustible a protective hearth extension must be used Raised or floor level extensions may be constructed On TFC39 only a raised hearth extension may be flush with the fireplace hearth It must be a minimum of 16 x 52 For a raised hearth on louvered models the firepl...

Страница 4: ...ace is limited Your fireplace weighs no more than some of your fine furniture If the fireplace is located near a load bearing wall additional supports to the foundation will not be necessary HEAVY FACINGS SUCH AS BRICK STONE ETC MAY REQUIRE ADDITIONAL FOUN DATION SUPPORT ALTHOUGH THIS UNIT MAY BE INSTALLED ON COMBUSTIBLE SURFACES IT MUST NOT BE INSTALLED ON CARPET OR VINYL Figure 1 Locations Figur...

Страница 5: ... wish to drive a nail through the ceiling at this spot Then go into the attic and find the nail Using the plumb bob with the ceiling nail as the center point of the flue mark the center of the area on the roof through which the flue will pass This is to see if it is possible to cut your opening for the flue in both the ceiling and roof without cutting either roof rafters or ceiling joists A locati...

Страница 6: ... wall shield as well D The framing header may rest on top of the standoffs E The minimum distance from the fireplace opening to an adjacent combustible wall is 17 The minimum distance to an adjacent combustible wall may be reduced to 12 when an approved wall shield is used on the wall The wall shield must be 40 x 40 and be constructed of a noncombustible inorganic material having a thermal resista...

Страница 7: ...atety strip is not required below the front face of the fireplace and mating edge of the hearth extension if the following steps are taken 1 The pre fabricated hearth extension or site built must be secured to the floor of the home to prevent shifting Various methods of attachment may be used including screws nails or common construction adhesives 2 After the fireplace and hearth extension have be...

Страница 8: ...ACER USED TO CENTER THE INNER PIPE THIS IS REQUIRED TO MAINTAIN CLEARANCES TO COMBUSTIBLE CONSTRUCTION DO NOT REMOVE STEP 8 Insert the inner 8 pipe with the male end pointing DOWN into the inner collar The inner flue section fits inside the inner c ollar Push the pipe until it bottoms and the snap locks engage Check each joint to ensure that the sections are securely locked together STEP 9 Slip th...

Страница 9: ... the amount of the offset dimension away from the ceiling nail See figure 18 The X dimen sion in the drawing is the amount of the offset Be sure to consider the direction that your offset will incline To achieve the minimum offset see table attach the return elbow to the first elbow To achieve further offset you may install various lengths of pipe between the elbows to a maximum length of 72 inche...

Страница 10: ... 3 10 0 0 0 1 50 4 2 0 1 1 0 56 4 8 1 0 0 1 62 5 2 0 1 0 1 66 5 6 2 0 0 1 72 6 0 1 1 0 1 80 6 8 0 0 1 1 92 7 8 0 0 0 2 96 8 0 0 1 1 1 102 8 6 1 0 0 2 108 9 0 0 1 0 2 112 9 4 2 0 0 2 118 9 10 1 1 0 2 126 10 6 0 0 1 2 136 11 4 1 0 1 2 138 11 6 0 0 0 3 142 11 10 0 1 1 2 148 12 4 1 0 0 3 154 12 10 0 1 0 3 158 13 2 2 0 0 3 164 13 8 1 1 0 3 172 14 4 0 0 1 3 182 15 2 1 0 1 3 184 15 4 0 0 0 4 188 15 8 0 1...

Страница 11: ... 74 7 8 140 7 8 1 0 1 1 2 1 77 7 8 149 3 8 1 1 0 0 3 2 80 7 8 154 5 8 1 0 1 0 3 2 82 7 8 158 1 2 0 0 3 2 85 7 8 163 1 4 1 1 1 0 3 2 89 7 8 170 1 8 1 0 0 1 3 2 94 7 8 178 3 4 1 1 0 1 3 2 95 7 8 180 5 8 1 0 0 0 4 2 97 7 8 184 1 0 1 1 3 2 100 7 8 189 1 4 1 1 0 0 4 2 103 7 8 194 1 2 1 0 1 0 4 2 105 7 8 197 7 8 1 2 0 0 4 2 108 7 8 203 1 8 1 1 1 0 4 2 112 7 8 213 1 4 1 0 0 1 4 3 117 7 8 221 7 8 1 1 0 1 ...

Страница 12: ... local sheet metal shop is required to complete a chase installation This cover becomes a flashing that prevents water from entering the chase The chase cover should be sealed at the corners A minimum 1 high collar is required at the point where the chimney pipe or slip section will penetrate the chase cover It requires 12 5 8 diameter collar The seam at the base of the collar must be watertight I...

Страница 13: ...The insulation and sealing of the enclosure around the fireplace is very important in cold climates If the enclosure is insulated and sealed properly you can avoid future cold air problems The time taken to install the firebox correctly is well worthwhile INSULATION OF THE FIREPLACE ENCLOSURE When in a chase or on an outside wall the fireplace enclosure can be insulated like any other outside wall...

Страница 14: ...air kit may go through the floor or the side wall of the mobile home 4 11 6 is the minimum system height for mobile home installations The height of the system is measured from the base of the fireplace and includes 6 of the chimney cap 5 A firestop thimble is required in all mobile home installations The TEMCO Model UFT8 1 universal firestop thimble may be used for flat and vaulted mobile home ce...

Страница 15: ... min adhesive or mortar when anchoring brick stone or tile to the face of the fireplace Check to see whether man made brick and stone are made of non combustible materials before using them on the face of the fireplace Some of these products contain combustible materials Combustible wall coverings such as paneling or wallboard may not overlap the black face of the fireplace The space between the w...

Страница 16: ...mmon construction adhesives 2 After the fireplace and hearth extension have been secured the gap between the fireplace and hearth extension must be filled or sealed with a non combustible grout caulk or sealant OR If a protective metal strip is used under the space between the fireplace and hearth extension sealing of the gap between the fireplace and hearth extension is optional See Note Below Se...

Страница 17: ...ES NOT WARRANT THE GLASS AND IS NOT RESPONSIBLE FOR CONSEQUENTIAL PROPERTY DAMAGE AS STATED IN THESEPARATEGLASSDOORWARRANTY 13 Creosote Formation and Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote re...

Страница 18: ...efractory retainer left side 1 68339 7 Screws for refractory retainers 2 68188 8 Right side refractory 1 67902 9 Left side refractory 1 67901 10 Back refractory 1 67130 11 Bottom refractory 1 67900 12 Integral grate 1 68373 13 Grate retaining bracket 2 66130 14 Refractory retainer 1 66130 REPLACEMENT PARTS FOR 39 FIREPLACES The following replacement parts are available from your TEMCO dealer 18 ...

Страница 19: ...ce Products and specifically does not cover the following Anyone other than the original owner Shipping costs after the first year of coverage Labor after the first year of coverage Damage caused by improper installation misuse abuse or alteration of the fireplace or chimney system Cracks in refractories that do not affect safe operation Any work done or cost incurred without written consent from ...

Страница 20: ...k in Order of Importance 1 6 ___Appearance ___Location Flexibility ___Builder Decided Purchaser Address Phone Retailer Address Phone Date of Purchase CUT ALONG LINE To register your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products 301 Perimeter Park Dr Suite 227 Nashville TN 37211 WARRANTY REGISTRATION Please Answer the Following Questions Chec...

Отзывы: