background image

STEP 6.  FRAMING CEILING AND ROOF OPENING 

SEE FIGURE 18 FOR INSTRUCTIONS IF THE FLUE-PIPE 
WILL BE OFFSET BELOW THE FIRST CEILING LEVEL. 

If you are not using elbows in this installation frame, the 
ceiling and roof openings are directly above one another in 
the locations you chose in the Planning Ahead section of 
this manual. The flue should go straight up to the chimney 
termination. Firestops must be used at each ceiling level. A 
firestop is not required at the roof line. The roof framing 
must be 2 x 6's or 2 x 4's and must be securely nailed 
because the chimney termination and flashing are anchored 
to this construction and must withstand heavy loads. The 
opening in the ceiling should be square. Use the nail you 
previously put in the ceiling as the center of the square. See 
below for framing alternative detail. Repeat this procedure 
to cut and frame an opening in each ceiling level. 

STEP 7. INSTALLING FIRESTOP SPACER 

Install a firestop at each ceiling level. The angles on the 
firestop are to maintain clearances. Nail the firestop to the 
joist and headers around the ceiling opening. No firestop is 
to be used at the roof level. The firestop should be installed 
from the underside of the ceiling, (see figure 12), except at 
the attic level where it should be installed on top at the 
framing members, (see figure 13).  A MINIMUM OF 1" AIR 
SPACE CLEARANCE MUST BE MAINTAINED FROM THE 
CHIMNEY PIPE TO ALL COMBUSTIBLES. 

When the chimney penetrates the ceiling at a 90° angle, 
use firestop spacer 8204F-1, 14 1/2" x 14 1/2" framed 
opening. When the chimney penetrates the ceiling at a 30° 
angle, use firestop spacer 8230F-1, 14 1/2" x 22" framed 

opening. 

INSTALLING THE CHIMNEY

 

Double Wall Chimney pipe has two sections: the inner and 
the outer sections.  It is very important that both sections be 
installed for each length of chimney used in the system. 

CAUTION:  THE OUTER PIPE SECTION HAS A WIRE 
SPACER USED TO CENTER THE INNER PIPE.  THIS IS 
REQUIRED TO MAINTAIN CLEARANCES TO 
COMBUSTIBLE CONSTRUCTION.  DO NOT REMOVE!

 

STEP 8. 

Insert the inner (8") pipe with the male end pointing DOWN 
into the inner collar. The inner flue section fits inside the 
inner collar. Push the pipe until it bottoms and the snap 
locks engage. Check each joint to ensure that the sections 
are securely locked together. 

STEP 9. 

Slip the outer (12") pipe with the male end UP over the 
other pipe and over the outer collar. The outer flue section 
fits on the outside of the outer flue collar. Push the pipe until 
it bottoms and the snap l ocks engage. Screws may be used 
only in the outer pipe for additional support if desired. 

STEP 10.

 

Continue this process of adding chimney pipe sections on 
top of each other until the pipe penetrates the roof opening 
enough to allow you to install the flashing and storm collar.  
Chimney sections must  be supported by either guy wires or 
3/4” conduit flattened on the ends when the chimney 
extends 6” or more above the roof.  The chimney may be 
extended to a maximum of 12’ above the roof.  A flue 
support mus t be used when the system is 35’ or higher. 

Figure 9  

Figure 10 

Figure 12 

Figure 13 

Pitch 

2 x 4 

2 x 6 

2 x 8 

2 x 10 

2 x 12 

0/12 

14 x 14 

14 x 14 

14 x 14 

14 x 14 

14 x 14 

1/12 

12 x 14 1/2  14 x 14 5/8  14 x 14 3/4  14 x 14 7/8  14 x 15 1/8 

2/12 

14 x 15 

14 x 15 1/4  14 x 15 1/2  14 x 15 3/4  14 x 16 1/4 

3/12 

14 x 15 1/2 

14 x 16 

14 x 16 1/4  14 x 16 3/4  14 x 17 1/2 

4/12 

14 x 16 1/4  14 x 16 7/8  14 x 17 1/4  14 x 17 7/8  14 x 18 3/4 

5/12 

14 x 17 

14 x 17 1/4  14 x 17 5/8  14 x 18 1/8  14 x 19 1/4 

6/12 

14 x 17 7/8  14 x 18 7/8  14 x 19 3/8  14 x 20 3/8  14 x 21 3/4 

7/12 

14 x 18 3/4  14 x 19 5/8  14 x 20 1/2  14 x 21 5/8  14 x 23 1/4 

8/12 

14 x 19 3/4 

14 x 21 

14 x 21 3/4 

14 x 23 

14 x 24 7/8 

9/12 

14 x 20 3/4  14 x 22 1/4 

14 x 23 

14 x 24 1/2  14 x 26 1/2 

10/12 

14 x 21 3/4  14 x 23 1/2  14 x 24 3/8 

14 x 26 

14 x 28 1/4 

11/12 

14 x 23 

14 x 24 3/4  14 x 25 3/4  14 x 27 1/2 

14 x 30 

12/12 

14 x 24 1/8  14 x 26 1/8  14 x 27 1/8  14 x 28 1/8  14 x 31 7/8 

ROOF CUT TO NEAREST 1/8" ABOVE 

Roof Framing Lumber  

Figure 11 

Содержание TFC39-22

Страница 1: ...ulating fireplace Optional Combustion Air Kits AIR 5 AIR 5A AIR 5B AIR 7 AIR 3B Optional Glass Doors CLS 4 CLS 3 CX31 CX41 Optional Blower Kit BL3922 Requires junction box JB 2 TLC39 22I With insulated outer wrap 39 louvered heat circulating fireplace with fully insulated outer wrap Optional Combustion Air Kits AIR 5 AIR 5A AIR 5B AIR 7 AIR 3B Optional Glass Doors CLS 4 CLS 3 CX31 CX41 Optional Bl...

Страница 2: ...es 5 Determining the R Values 6 Fireplace Installation 7 Installing the firebox 7 Installing the chimney 8 Chimney termination height 10 Foot Rule of Thumb 9 Offset installations 9 10 11 Flashing and storm collar 12 Installing the termination 12 Chase installations 12 Installing a gas line 13 Cold climate installations 13 Mobile home installation 14 Finishing Your Fireplace 15 16 Using Your Firepl...

Страница 3: ... combustible wall is 17 See Figure 4 for alternative wall shields and required R factors 7 If the floor in front of the fireplace is combustible a protective hearth extension must be used Raised or floor level extensions may be constructed On TFC39 only a raised hearth extension may be flush with the fireplace hearth It must be a minimum of 16 x 52 For a raised hearth on louvered models the firepl...

Страница 4: ...ace is limited Your fireplace weighs no more than some of your fine furniture If the fireplace is located near a load bearing wall additional supports to the foundation will not be necessary HEAVY FACINGS SUCH AS BRICK STONE ETC MAY REQUIRE ADDITIONAL FOUN DATION SUPPORT ALTHOUGH THIS UNIT MAY BE INSTALLED ON COMBUSTIBLE SURFACES IT MUST NOT BE INSTALLED ON CARPET OR VINYL Figure 1 Locations Figur...

Страница 5: ... wish to drive a nail through the ceiling at this spot Then go into the attic and find the nail Using the plumb bob with the ceiling nail as the center point of the flue mark the center of the area on the roof through which the flue will pass This is to see if it is possible to cut your opening for the flue in both the ceiling and roof without cutting either roof rafters or ceiling joists A locati...

Страница 6: ... wall shield as well D The framing header may rest on top of the standoffs E The minimum distance from the fireplace opening to an adjacent combustible wall is 17 The minimum distance to an adjacent combustible wall may be reduced to 12 when an approved wall shield is used on the wall The wall shield must be 40 x 40 and be constructed of a noncombustible inorganic material having a thermal resista...

Страница 7: ...atety strip is not required below the front face of the fireplace and mating edge of the hearth extension if the following steps are taken 1 The pre fabricated hearth extension or site built must be secured to the floor of the home to prevent shifting Various methods of attachment may be used including screws nails or common construction adhesives 2 After the fireplace and hearth extension have be...

Страница 8: ...ACER USED TO CENTER THE INNER PIPE THIS IS REQUIRED TO MAINTAIN CLEARANCES TO COMBUSTIBLE CONSTRUCTION DO NOT REMOVE STEP 8 Insert the inner 8 pipe with the male end pointing DOWN into the inner collar The inner flue section fits inside the inner c ollar Push the pipe until it bottoms and the snap locks engage Check each joint to ensure that the sections are securely locked together STEP 9 Slip th...

Страница 9: ... the amount of the offset dimension away from the ceiling nail See figure 18 The X dimen sion in the drawing is the amount of the offset Be sure to consider the direction that your offset will incline To achieve the minimum offset see table attach the return elbow to the first elbow To achieve further offset you may install various lengths of pipe between the elbows to a maximum length of 72 inche...

Страница 10: ... 3 10 0 0 0 1 50 4 2 0 1 1 0 56 4 8 1 0 0 1 62 5 2 0 1 0 1 66 5 6 2 0 0 1 72 6 0 1 1 0 1 80 6 8 0 0 1 1 92 7 8 0 0 0 2 96 8 0 0 1 1 1 102 8 6 1 0 0 2 108 9 0 0 1 0 2 112 9 4 2 0 0 2 118 9 10 1 1 0 2 126 10 6 0 0 1 2 136 11 4 1 0 1 2 138 11 6 0 0 0 3 142 11 10 0 1 1 2 148 12 4 1 0 0 3 154 12 10 0 1 0 3 158 13 2 2 0 0 3 164 13 8 1 1 0 3 172 14 4 0 0 1 3 182 15 2 1 0 1 3 184 15 4 0 0 0 4 188 15 8 0 1...

Страница 11: ... 74 7 8 140 7 8 1 0 1 1 2 1 77 7 8 149 3 8 1 1 0 0 3 2 80 7 8 154 5 8 1 0 1 0 3 2 82 7 8 158 1 2 0 0 3 2 85 7 8 163 1 4 1 1 1 0 3 2 89 7 8 170 1 8 1 0 0 1 3 2 94 7 8 178 3 4 1 1 0 1 3 2 95 7 8 180 5 8 1 0 0 0 4 2 97 7 8 184 1 0 1 1 3 2 100 7 8 189 1 4 1 1 0 0 4 2 103 7 8 194 1 2 1 0 1 0 4 2 105 7 8 197 7 8 1 2 0 0 4 2 108 7 8 203 1 8 1 1 1 0 4 2 112 7 8 213 1 4 1 0 0 1 4 3 117 7 8 221 7 8 1 1 0 1 ...

Страница 12: ... local sheet metal shop is required to complete a chase installation This cover becomes a flashing that prevents water from entering the chase The chase cover should be sealed at the corners A minimum 1 high collar is required at the point where the chimney pipe or slip section will penetrate the chase cover It requires 12 5 8 diameter collar The seam at the base of the collar must be watertight I...

Страница 13: ...The insulation and sealing of the enclosure around the fireplace is very important in cold climates If the enclosure is insulated and sealed properly you can avoid future cold air problems The time taken to install the firebox correctly is well worthwhile INSULATION OF THE FIREPLACE ENCLOSURE When in a chase or on an outside wall the fireplace enclosure can be insulated like any other outside wall...

Страница 14: ...air kit may go through the floor or the side wall of the mobile home 4 11 6 is the minimum system height for mobile home installations The height of the system is measured from the base of the fireplace and includes 6 of the chimney cap 5 A firestop thimble is required in all mobile home installations The TEMCO Model UFT8 1 universal firestop thimble may be used for flat and vaulted mobile home ce...

Страница 15: ... min adhesive or mortar when anchoring brick stone or tile to the face of the fireplace Check to see whether man made brick and stone are made of non combustible materials before using them on the face of the fireplace Some of these products contain combustible materials Combustible wall coverings such as paneling or wallboard may not overlap the black face of the fireplace The space between the w...

Страница 16: ...mmon construction adhesives 2 After the fireplace and hearth extension have been secured the gap between the fireplace and hearth extension must be filled or sealed with a non combustible grout caulk or sealant OR If a protective metal strip is used under the space between the fireplace and hearth extension sealing of the gap between the fireplace and hearth extension is optional See Note Below Se...

Страница 17: ...ES NOT WARRANT THE GLASS AND IS NOT RESPONSIBLE FOR CONSEQUENTIAL PROPERTY DAMAGE AS STATED IN THESEPARATEGLASSDOORWARRANTY 13 Creosote Formation and Need for Removal When wood is burned slowly it produces tar and other organic vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote re...

Страница 18: ...efractory retainer left side 1 68339 7 Screws for refractory retainers 2 68188 8 Right side refractory 1 67902 9 Left side refractory 1 67901 10 Back refractory 1 67130 11 Bottom refractory 1 67900 12 Integral grate 1 68373 13 Grate retaining bracket 2 66130 14 Refractory retainer 1 66130 REPLACEMENT PARTS FOR 39 FIREPLACES The following replacement parts are available from your TEMCO dealer 18 ...

Страница 19: ...ce Products and specifically does not cover the following Anyone other than the original owner Shipping costs after the first year of coverage Labor after the first year of coverage Damage caused by improper installation misuse abuse or alteration of the fireplace or chimney system Cracks in refractories that do not affect safe operation Any work done or cost incurred without written consent from ...

Страница 20: ...k in Order of Importance 1 6 ___Appearance ___Location Flexibility ___Builder Decided Purchaser Address Phone Retailer Address Phone Date of Purchase CUT ALONG LINE To register your warranty please provide the information indicated on this form and mail it to TEMCO Fireplace Products 301 Perimeter Park Dr Suite 227 Nashville TN 37211 WARRANTY REGISTRATION Please Answer the Following Questions Chec...

Отзывы: