If station housing uints have not already been installed and pre wired, complete this phase now. Follow the station
housing installation manual (UP-HIM) that comes with the housing units. Then ensure the following steps have been
completed before installing Station Head Units.
Run power conduit from panel to each station housing in accordance with local electrical codes and regulations. For
futur
e upgradability, ensure that conduit is sized for a total of five (5) wires! including four (4) current carrying conduc-
tors (connected to 2 double pole 40amp breakers) and one (1) Earth conductor.
Use this diagram for a general overview of a typical site. Power conduit is always required. Data conduit between
stations is always required between multiple stations. Data conduit to the building is only needed if the onsite Verizon
2G data signal is poor. Alwasy test the Verizon signal before planning the site. (see page 11 for more detials)
If more than one station is to be installed in the same area, affix a data conduit T-box below each station housing, then
run data conduit between each. Size data conduit to carry up to 2 Cat5e cables each.
Pull Cat5 data cable in accordance with the number of station at the site. Leave 6ft of cable extending from top edge of
conduit wire protector in each station. Terminate all Cat5 Ethernet cables using identical wire (color) pattern on each
end (see page 11 for more detials)
First refer to page 5 for service based wiring options.
For UP80J head uints, size 3 electrical conductors according to NEC code using the following continuous load amperage
limits: Line (30 Amps continuous), Line (30 Amps continuous), and an earth ground sized to match the largest current
carrying conductor. Pull these 3 electrical conductors from panel to each station leaving 40 inches of conductor extend-
ing from inside edge of conduit wire protector on the station side.
Building
Internet
Router
(DHCP)
Service
Panel
STN-1
STN-2
STN-3
STN-4
Data conduit
Required
Cat 5 cables
Building
data conduit
only required
if Verizon data
signal poor
Power conduit large enough for 5 wires each.
Electrical Conduit
Planning:
Pull Electrical Conductors
Data Conduit
Pull Data Cables
Page 6
Station Housing Installation (Wiring):
6B
6A
6C
6D
6E