PaLm Programmator
-
Operation Manual
29
In the
Tx On Time
check-box enter the warming-up time for setting a stable carrier
frequency prior to transmission. The value entered must be within the interval of 0.1 to
5.0 sec. over a spacing of 0.1 sec.
In the
reset Time
check-box select the warming-up time for setting the transmitter
after power up following which the transmitter begins to transmit. This time is within the
interval of 1 to 255 sec.
In the
rna Time
check-box set the time for automatic transmission of a “
trouble
“
message along with an alarm which has not been restored. The time interval introduced
is within 5 to 60 min.
When introducing any parameters, follow whether they observe the permissible
intervals. Otherwise the programme will display a trouble message when
attempting to load the file.
6. “inputs” screen
Set the transmitter input values in this screen. Specify the transmitter input parameters
from
in1
to
in8
.
The events which can be activated, i.e. for
which a signal will be received, are:
•
aL
- the transmitter sends an
alarm
status signal when a signal is perceived at
the respective input.
•
re
- the transmitter sends a
restore
signal when a signal is perceived at the
respective input.
•
Tr
- the transmitter sends a signal in case
of
trouble
the respective input.
•
inV
- the transmitter
inverts
the alarm
and restore signals.
The statuses of the events can be changed
by pressing on the respective check-box.
Use the
mode
column to change over
between the different modes for using the
respective input:
U - PullUp
,
D - PullDown
,
r - Balance resistor
.
Use the
address
and
Channel
check-
boxes to establish a connection between
the physical channel and the logical
channels to send signals about them.
Figure 23. inputs screen of
PaLm Programmator.
address
field sets the site to which the respective input is connected.
Enter the logical information in the
Channel
check-box.