Operation

Link Source Alarm (LSA)

CEV / CFOx61/x71 series video modem’s (transmitter and receiver) 
contact closure output can be used to control optical switch when the 
video modem’s LSA (Link Source Alarm) mode is enabled. When 
operating with LSA, a connection cable is required between the optical 
switch and video modem.

Note!

 Enabling LSA (LSA ON) overrides all other functions of video 

modem’s CC output. 

When LSA is enabled, video modem’s contact closure input and data 1 
connections are normally available via optical switch’s DATA 1 (loopthru) 
connector when using a connection cable between CEV / CFOx61/x71 
series video modem and optical switch. The recommended connection 
cable is Teleste 

CIC702

 (RJ-45/RJ-45).

LSA commands

CEV / CFO16x/17x series video modem includes a command line 
interface (CLI) for con

fi

 guration purposes. With help of CLI commands 

you can con

fi

 gure the LSA settings. See CEV / CFO16x/17x series 

video modem’s user manual for more details how to use the CLI. 

:  Enables/disables LSA monitoring on the device
:  Displays or sets the link source alarm switching delay (in seconds). 

Delay de

fi

 nes how long the device will wait for the optic link to get up 

before operating the switch for the 

fi

 rst time

:  Displays or set the link source alarm hold time (in seconds). Holdtime 

de

fi

 nes the waiting time to ensure the recovery of the optical link

:  Resets device source alarm to it’s initial state (see page 4 for 

switching logic 

fl

 ow chart)

Switch port positions and indicator leds

When the switch is not activated (initial state), the com port is connected 
to port A, and all front panel RJ-45 connectors leds (1-4) are dark.

When the switch is activated (alarm state), the com port is connected to 
port B and all front panel RJ-45 connectors leds (1-4) are green. 

The switching can be controlled by the following ways:

•  LSA (contact closure output at video modem)
•  System power fail (rack power supply)
•  External control open (pins open)
•  External control closed (pins closed)
•  Remote controlled via video modem link
  (normal contact closure operation, see note on the right)

Note!

 When using LSA control, the optican switch operates 

automatically with the logic descripted in page 4.

Port B

Port A

Com

LSA on / off

LSA delay

LSA holdtime

LSA reset

COM port positions

The optical switch’s initial state is 
always port position A, except when 
using system power switching mode, 
at that control mode the switch’s 
initial state is position B.

2

 

Optical switch

 user manual rev001

Содержание CFO series

Страница 1: ...Video Networks Optical switch 1 x 2 switch for singlemode bre 1290 1330 and 1470 1610 nm wavelenghts User Manual For CFO series CEV x61 x71 Optical switch user manual 59300281 rev001...

Страница 2: ...1 Frame installation 1 Stand alone installation 1 Fibre connection 1 Operation 2 Link Source Alarm LSA 2 LSA commands 2 Switch port positions and indicator leds 2 Settings 3 Wiring example 3 DIP swit...

Страница 3: ...nd alone installation The unit can be installed for stand alone use by using a CMA series module adapter The unit is to be pushed along the guide rails into the CMA module adapter and secured with the...

Страница 4: ...l wait for the optic link to get up before operating the switch for the first time Displays or set the link source alarm hold time in seconds Holdtime defines the waiting time to ensure the recovery o...

Страница 5: ...ches see settings below The default factory setting is LSA controlled 1 ON 2 3 4 5 6 DIP swithes are located on the bottom of unit Note When the optical switch is configured to LSA mode there is an al...

Страница 6: ...ed Switch position Com port B LSA control is kept de activated Switch position Com port A LSA hold time User definable time Waiting time in seconds to ensure that optical connection has been establish...

Страница 7: ...unless otherwise stated Optical Wavelenght range 1310 50 and 1460 1620 nm Insertion loss 1 0 dB max Return loss 60 dB Switching type 1x2 non latching Switching time 8 ms Cross talk 60 dB min Switching...

Страница 8: ...of the European Parliament and of the Council on waste electrical and electronic equipment WEEE obliges that producers appropriately mark electrical and electronic equipment with the symbol indicatin...

Отзывы: