13
Connecting Extinguishing Equipment
13.1
Extinguishing Adapters
In order to connect the ECD extinguishing output to different actuators, it is necessary to
connect adapters between the ECD output and the extinguishing equipment input,
Telefire offers several adapters.
Shown below are the type of equipment and the relevant adapter:
Fike FIRERASER cylinders-use TLA-130 adapter
Fike GCA cylinder-use TLA-22 adapter
Greenex Aerosol Containers-use TLA-33 adapter
FirePro Aerosol Containers-use TLA-44 adapter
SAFE Solenoid Activated gas containers-use TLA- 110 adapter
i
Note
When extinguishing adapters are installed, addition of EOL resistors is not
required!
i
Note
Please consult the manufacturer for solutions regarding activation of
additional extinguishing devices.
13.2
Number of Extinguishing Adapters
Extinguishing Device
Maximal number of extinguishing adapters
SAFE solenoid gas
cylinders
A single TLA-110 adaptor connected to the extinguishing
output
FIKE solenoid gas
cylinders (FIRERASER)
A single TLA-130 adaptor connected to the extinguishing
output
FIKE GCA gas cylinders
A single TLA-22 adaptor connected to the extinguishing
output
FirePro aerosol generators A single TLA-44/1 or TLA-44/4 adaptor connected to the
extinguishing output
GreenEX aerosol
generators
A single TLA-33 adaptor connected to the extinguishing
output
i
Note
Connect a single extinguishing adaptor to the extinguishing activation output.
This adaptor will activate a single extinguishing device, except for the TLA-
44/4 that can activate up to 4 FirePro aerosol extinguishers.
Please consult the manufacturer for solutions regarding activations of
additional extinguishing devices