TSA-1000
© 2008
–
2012 Telefire Fire & Gas Detectors Ltd
Revision 1.12
האיגש
!
אצמנ אל הינפהה רוקמ
.
2
– Page 72 of 72 –
17
Commissioning
•
Verify that ALL POWER SOURCES are disconnected.
•
Verify that THE EXTINGUISHER IS DISCONNECTED (disconnect both wires to the
extinguisher), connect a DUMMY load to the extinguisher output.
•
Verify that all required interfaces are connected. Verify correct wiring.
•
Verify presence and connection of required (ONLY) and correct EOL resistors.
•
Connect mains and battery.
•
Fix all faults
•
When ALL faults are fixed and the ECD is in the quiescent state, configure and
program the ECD as required.
•
Update site specific data and date and time
•
Change the level 2 and 3 passwords (Recommended).
•
Verify that the POWER LED is ON with short OFF pulses
•
Perform a full Field Test,
•
Perform an activation test.
•
Test and verify correct operation from detectors and from manual activation
•
Verify that the ECD lock and switch keys are available and accessible to operators
•
Attach the required documentation to or near the Control Panel
•
Disconnect ALL power, Remove the dummy load, and connect the extinguisher to
the extinguishing output or output lines.
•
Connect mains and batteries.
•
Fix all problems
•
Verify that the ECD is in the quiescent state.
i
Note
Do not access, probe, or touch the area near the AC input terminals when the
CP is powered, to avoid electric shock.
17.1.1 Additional System Documentation
In different countries and according to some CP installation regulations, it is sometimes
required to place a document containing condensed system information and operating
instructions, on or near the CP.
Attach the condensed instructions document to the system’s front panel, or frame it and
place it in a prominent, highly visible position nearby.
It is recommended that the document shall at least contain the following;
•
Actions to be taken upon events of alarm or fault by the operators
•
A list of areas/zones as installed in the protected premises, and blank spaces for
their details and description
•
Text referring to The name, address and phone number of the service
representative, and blank spaces to fill in the details after installation
•
Text referring to the name, address and phone number of the Installing
representative, and blank spaces to fill in the details after installation.