background image

 

 

 

850-811250-Revision 13b  

 

GD10-P00 and GD10-PE0

 

INFRARED POINT GAS DETECTOR 

 

 
 

 
 

 
 

 
 

 

 
 

 
 

 
 

 
 

 
 

 
 

O

PERATING 

M

ANUAL

 

 
 

Содержание Everywhereyoulook GD10-P00

Страница 1: ...850 811250 Revision 13b GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL...

Страница 2: ...production of all or part of this document in any form is permitted without the written consent of TELEDYNE OLDHAM SIMTRONICS S A S All of the information that is provided in this document is accurate...

Страница 3: ...of any of its products UNLESS SUCH PRODUCTS HAVE BEEN SELECTED BY TELEDYNE OLDHAM SIMTRONICS ACCORDING TO THE APPLICATION Ownership clauses The drawings specifications and information herein contain c...

Страница 4: ...ase refer to IEC 60079 29 2 standard Warranty Under normal conditions of use and on return to the factory parts and workmanship are guaranteed for 5 years IR sources are guaranteed for 15 years Waste...

Страница 5: ...P Weather Protection 14 4 4 GD10P Duct or pipe mounting 15 4 5 GD10PE Fixing 17 4 6 GD10PE Weather protection standalone mounting 17 4 7 GD10PE Duct or pipe mounting 17 4 8 External cable 19 4 9 Elect...

Страница 6: ...13b 8 Specific instructions for use in explosive atmospheres and operational safety 35 9 Marking 37 10 Declarations of conformity 39 11 Product coding 43 11 1 GD10P Gas and range code 45 12 Accessori...

Страница 7: ...ptible to detection The intensity of this absorption line is however significantly dependent on the molecule under consideration In general the larger the molecule is the greater the absorption streng...

Страница 8: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 2 850 811250 Revision 13b Suitable for use in SIL 2 and SIL 3 systems...

Страница 9: ...nd bulkheads in places such as pump rooms but may also be used as a standalone point detector in places where the properties of the GD10PE is required such as low ppm level detection A weather protect...

Страница 10: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 4 850 811250 Revision 13b...

Страница 11: ...reading Accuracy 3 FS between 0 50 reading 5 FS between 50 100 reading Response time 2 T20 0 8 sec Optional 0 2 sec T50 2 1 sec Optional 0 4 sec T90 5 sec Optional 1 0 sec Start up time Less than 60...

Страница 12: ...ntenance HART interface ELECTRICAL Power supply 24 VDC range 18 32 VDC Power consumption Approx 3 5 W Connection 3 wires 0 5mm2 1 5mm2 Cable entry M20 Ex e cable gland ENVIRONNEMENT Storage Temperatur...

Страница 13: ...ASTM 316 Weight Approx 2 9 kg 6 4 Lbs Dimensions 264L x 104W x 106H mm 10 4 x 4 1 x 4 2 inches EMC Compliant to EN 50270 and IEC 61326 3 1 7 WARRANTY 5 years full warranty on complete instrument 15 ye...

Страница 14: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 8 850 811250 Revision 13b...

Страница 15: ...0 LEL reading 1 4 LEL 10 20 LEL reading Response time 9 T20 0 8 sec T50 2 1 sec T90 5 sec Start up time Less than 60 sec10 full specification obtained after 30 min warmup time 8 The detector is intend...

Страница 16: ...k 4 20 mA Maintenance HART interface ELECTRICAL Power supply 24 V DC range18 32 V DC Power consumption Approx 3 5 W Connection 3 wires 0 5mm2 1 5mm2 Cable entry M20 Ex e cable gland ENVIRONNEMENT Stor...

Страница 17: ...Stainless steel SIS2343 ASTM 316 Weight Approx 6 5 kg Dimensions 805L x 104W x 106H mm EMC Compliant to EN 50270 and IEC 61326 3 1 14 WARRANTY 5 years full warranty on complete instrument 15 years war...

Страница 18: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 12 850 811250 Revision 13b...

Страница 19: ...here maintenance i e cleaning of the optics is easily performed The detector may be mounted in areas where no oxygen is present The detector may be mounted in areas with strong airflow The detector ca...

Страница 20: ...l prevent accumulation of water and dust on the optics The Weather Protection must always be oriented correctly for optimal performance Figure 1 GD10P mounting 4 3 GD10P Weather Protection When the GD...

Страница 21: ...d in the core of the airflow in wide ducts or pipes Avoid direct light on lens and mirror if the GD10P is mounted without the Weather Protection In order to achieve minimum response time the Weather P...

Страница 22: ...INFRARED POINT GAS DETECTOR OPERATING MANUAL 16 850 811250 Revision 13b Figure 3 Exploded view Duct Mount Flange Kit Figure 4 Ventilation duct or pipe mounting using Duct Mounting Flange Kit Refer to...

Страница 23: ...D10PE Duct or pipe mounting By using the optional duct mounting kit GD10PE is very suitable for monitoring ventilation air in ducts and channels The flange is bolted to a vertical flat surface of suff...

Страница 24: ...on is at some distance behind the first filter or grille when used for forced flow air intakes You may also just bolt the detector as stand alone with the nose bracket support but this is not advisabl...

Страница 25: ...insulated ducts it is necessary to remove some insulation Figure 9 4 8 External cable The cable type must be chosen in accordance with applicable regulations The table below indicates maximum cable l...

Страница 26: ...nt The unused entry is blanked with an Ex e cover The detector housing must be connected to local ground via the external earth point The wire should be minimum 4 mm2 8 AWG and as short as possible Th...

Страница 27: ...Make sure that the flat support surface is clean properly greased and that it does not show any visible scratches or knocks Please refer to Chapter 4 Installation for details 5 2 Power up Ensure that...

Страница 28: ...lean the optical parts before testing the detector refer to Paragraph 7 1 Cleaning of optical lens mirror 2 Do a gas test To make sure the detector works fine you should as a minimum do a function che...

Страница 29: ...uction 1 mA No detection Early Dirty Optics Warning 55 signal reduction 2 mA Detector will still output gas concentration if it is greater than 7 of range FS 10 of range 0 6 mA Default 0 of range 4 mA...

Страница 30: ...org registered products product name GD10P The loading of the DD onto a specific communicator must be done according to the relevant user guide for that communicator The loss of HART communication is...

Страница 31: ...250 Revision 13b 25 6 2 3HART Menu Map This menu map shows a non exhaustive list of available commands in the HART interface of GD10 For more information about the complete list of HART available comm...

Страница 32: ...ated the operator is navigated to one or several data input screens where detailed data can be entered or predefined options selected Detailed navigation between the commands is not explained as this...

Страница 33: ...tection range After a reconfiguration it is recommended to restart the detector and verify the new settings by simulating different alarm warning states A current meter may be used to read the level a...

Страница 34: ...outside a specific temperature range 16 C 26 C If the Zero level is not improved after the zeroing the reason is that the zero drift is over the allowed limit for field trimming 6 2 4 11 GD10 Loop Te...

Страница 35: ...ce is clean For difficult contaminants the mirror and lens can be cleaned with an equal part mixture of isopropyl alcohol and water Do not perform any testing of the detector before this solution has...

Страница 36: ...t is required by regulations or in cases where you need to verify system performance during commissioning or similar thorough testing The GD10P PE detectors have a fixed calibration from the factory A...

Страница 37: ...hown in the drawing The test gas should be the same as the target gas Humidity of the test gas is 0 100 RH uncondensed At 40 C 50 RH means volume H2O 3 5 Gas flow should be approximately 1 liter minut...

Страница 38: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 32 850 811250 Revision 13b Do not forget to remove the Gas Test Socket when calibration test is over...

Страница 39: ...ctors should normally be returned to the factory for service An alternative is to do this re zeroing on site with a dedicated hand held terminal or HART communicator Note that on site does not mean in...

Страница 40: ...ginal value the output signal will go down to Early Dirty Optics see section 6 1 for further details If the IR transmission is further attenuated the output signal will go down to Dirty Optics fault I...

Страница 41: ...cessories plugs adaptors etc shall be flameproof certified db or eb for use in gas atmospheres and Ingress Protection will be greater or equal to IP 66 They shall be of M20x1 5 type according to ISO96...

Страница 42: ...ED POINT GAS DETECTOR OPERATING MANUAL 36 850 811250 Revision 13b 8 1 1 6 Functional safety certification For all information related to the safety function of the GD10P PE gas detectors please refer...

Страница 43: ...TING MANUAL 850 811250 Revision 13b 37 9 Marking The GD10P PE identification labels are shown in the figures below as example ATEX IECEx INMETRO MED markings combustible gases version ATEX IECEx INMET...

Страница 44: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 38 850 811250 Revision 13b CSA marking combustible gases version...

Страница 45: ...GD10P00 and GD10PE INFRARED POINT GAS DETECTOR OPERATING MANUAL 850 811250 Revision 13b 39 10 Declarations of conformity...

Страница 46: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 40 850 811250 Revision 13b...

Страница 47: ...GD10P00 and GD10PE INFRARED POINT GAS DETECTOR OPERATING MANUAL 850 811250 Revision 13b 41...

Страница 48: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 42 850 811250 Revision 13b...

Страница 49: ...Vol 17EG Methane CH4 100 LEL 2 4 4 Vol 18BG Methane Biogas CH4 CO2 100 Vol 23AN Carbon dioxide CO2 10000 ppm 23BH Carbon dioxide CO2 3 Vol 24BC Carbon dioxide Methane immune CO2 5 Vol 24BG Carbon dio...

Страница 50: ...calibration a selection of most used variants 03AM Ethylene C2H4 5000 ppm 17DE Methane CH4 20 LEL 1 B Configuration 0 Fixed default value Approval 0 None B CSA X ATEX IECEx INMETRO Interface H 4 20mA...

Страница 51: ...05DG Ethanol C2H5OH 3 3 05EG Ethanol C2H5OH 3 1 07DG Propene C3H6 2 0 08DG Acetone C3H6O 2 6 09DG Propane C3H8 2 2 09EG Propane C3H8 1 7 11DG Pentane C5H12 1 4 12DG n Hexane C6H14 1 1 13DG Benzene C6H...

Страница 52: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 46 850 811250 Revision 13b...

Страница 53: ...38 Mosquito Set Assy GD10P Insect protection in stainless steel mesh Slides on the outside of the standard weather protection 499 813397 Sun shade Assy GD10P for horizontal mounting protects from dire...

Страница 54: ...15733 GD10PE Duct Mounting Flange 499 815271 12 3 Spares Spare Parts Description Part Number Weather Protection Kit GD10P 499 810913 Cap cover for the gas test nozzle GD10P and GD10PE 599 904176 Rear...

Страница 55: ...0 2 years in clean atmosphere 499 815712 100 RH uncondensed 1013 hPa 10 2 years in clean atmosphere 599 816841 100 RH uncondensed 1013 hPa 10 2 years in clean atmosphere 499 816867 100 RH uncondensed...

Страница 56: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 50 850 811250 Revision 13b...

Страница 57: ...GD10P00 and GD10PE INFRARED POINT GAS DETECTOR OPERATING MANUAL 850 811250 Revision 13b 51...

Страница 58: ...GD10 P00 and GD10 PE0 INFRARED POINT GAS DETECTOR OPERATING MANUAL 52 850 811250 Revision 13b...

Страница 59: ...GD10P00 and GD10PE INFRARED POINT GAS DETECTOR OPERATING MANUAL 850 811250 Revision 13b 53...

Страница 60: ...served 850 811250 Revision 13b June 2021 AMERICAS 14880 Skinner Rd CYPRESS TX 77429 USA Tel 1 713 559 9200 EMEA Rue Orfila Z I Est CS 20417 62027 ARRAS Cedex FRANCE Tel 33 0 3 21 60 80 80 ASIA PACIFIC...