Dual 40/50/100A Configurable Breaker Panel
Power
:: T009-5XXXXXXXXXXX
© Telect, Inc., All Rights Reserved, 118267-3 A0
1.509.926.6000 :: telect.com
3
Installation Guide
Specifications Cont.
Electrical
Specifications
Operating voltages
–20 to –60 VDC, +20 to +30 VDC
Maximum input interruption device rating
125A for a 100A panel
60A for all other panels
Maximum continuous input load rating (total)
100A per feed (with compression inputs but without 50A
thermal input breaker)
50A per feed (with screw-tight inputs but without 50A
thermal input breaker)
40A per feed (with 50A thermal input breaker)
Maximum output interruption device rating
20A per circuit breaker
Maximum continuous output load rating
16A per circuit breaker
Alarm contact ratings, continuous
2A at 30 VDC 0.6A at 60 VDC
Alarm board power ratings
@20V: 80mA (1.60W)
@27V: 120mA (3.24W)
@40V: 127mA (5.08W)
@54V: 133mA (7.18W)
@24V: 112mA (2.69W)
@30V: 122mA (3.66W)
@48V: 130mA (6.24W)
@60V: 136mA (8.16W)
Max. operating temperature at max. load ratings
55°C (131°F)
Min. operating temperature at max. load ratings
–10°C (14°F)
Ambient operating temp. at half-load
55°C (131°F)
Max. surface temperature of breakers at 26°C
(79°F) ambient
35°C (95°F)
Max. panel heat dissipation at full load
18W per side at 1920W (40A x 48V) per side
20W per side at 2400W (50A x 48V) per side
42W per side at 4800W (100A x 48V) per side
Percentage of full load heat dissipation at
nominal voltage
Less than 1% of total load wattage
118267-2 A0
Page 2
ALERT
!
ALERT! This product must be installed and maintained only by qualified personnel. Verify all connec-
tions meet requirements specified in local electric codes or operating company guidelines before
supplying power. Protect this equipment with a fuse or breaker sufficient to interrupt power levels
specified under “Electrical Specifications”.
Please read these instructions carefully before beginning installation. If you need assistance call Technical Support at
888-821-4856 (domestic calls), or 509-921-6161 (Option 2), or eMAIL us at [email protected]
1. Inspect equipment after unpacking and compare it to the packing list.
Immediately report any shipping damage, defects, or missing parts to Telect at 1-800-551-4567. Keep all documen-
tation that comes with your shipment.
NOTE
Telect is not liable for shipping damage. If damaged, notify the carrier and call Telect’s Customer Service Department at
1-800-551-4567 (domestic only) or 1-509-926-6000 for further recourse.
NOTE
Panel brackets provide either flush or extended EIA or WECO mounting in a 19" or 23" rack. Panel is configured at the factory
for flush mounting in a 19" rack.
Electrical Specifications
Operating voltages
–20 to –60 Vdc, +20 to +30 Vdc
Maximum input interruption device rating
125A for a 100A panel
60A for all other panels.
Maximum continuous input load rating (total)
100A per feed (with compression inputs but
without
50A
thermal input breaker)
50A per feed (with screw-tight inputs but
without
50A
thermal input breaker)
40A per feed (
with
50A thermal input breaker)
Maximum output interruption device rating
20A per circuit breaker
Maximum continuous output load rating
16A per circuit breaker
Alarm contact ratings, continuous
2A at 30 Vdc
0.6A at 60 Vdc
Alarm board power ratings
@20V: 80mA (1.60W)
@24V: 112mA (2.69W)
@27V: 120mA (3.24W)
@30V: 122mA (3.66W)
@40V: 127mA (5.08W)
@48V: 130mA (6.24W)
@54V: 133mA (7.18W)
@60V: 136mA (8.16W)
Max. operating temperature at max. load ratings
55°C (131°F)
Min. operating temperature at max. load ratings
–10°C (14°F)
Ambient operating temp. at half-load
55°C (131°F)
Max. surface temperature of breakers at 26°C (79°F) am-
bient
35°C (95°F)
Max. panel heat dissipation at full load
18W per side at 1920W (40A x 48V) per side
20W per side at 2400W (50A x 48V) per side
42W per side at 4800W (100A x 48V) per side
Percentage of full load heat dissipation at nominal voltage less than 1% of total load wattage
ALERT! This product must be installed and maintained only by qualified personnel. Verify all connections
meet requirements specified in local electric codes or operating company guidelines before supplying power.
Protect this equipment with a fuse or breaker sufficient to interrupt power levels specified under
“Electrical Specifications”.
Please read these instructions carefully before beginning installation. If you need assistance call Technical Support at
509.926.6000 or email us at [email protected].
1. Inspect equipment after unpacking and compare it to the packing list. Immediately report any shipping
damage, defects or missing parts to Telect at 509.926.6000. Keep all documentation that comes with
your shipment.
NOTE: Telect is not liable for shipping damage. If damaged, notify the carrier and call Telect at 509.926.6000 for
further recourse.
NOTE: Panel brackets provide either flush or extended EIA or WECO mounting in a 19" or 23" rack. Panel is configured at
the factory for flush mounting in a 19" rack.