Dual 40/50/100A Configurable Breaker Panel

Power

 :: T009-5XXXXXXXXXXX

© Telect, Inc.,  All Rights Reserved, 118267-3 A0

1.509.926.6000  ::  telect.com

5

Installation Guide

 

8. 

For input wiring

 

— wiring used as inputs to this distribution panel — proceed as follows:

For Compression Lug Inputs

 

For Screw-Tight Inputs

a. 

Crimp dual-hole compression lugs onto suitable copper 

wires (#6 to #1 AWG) for 

BATT

 and 

RTN

 terminals, 

Feeds A and B.

b.  Remove the black plastic terminal covers, if installed.

c. 

Use a coarse, nonmetallic cleaning pad to clean 

 

terminals and studs.

d. 

Lightly coat antioxidant on lugs, input 

BATTERY

 and 

RETURN

 terminals, and then connect lugs to Feed A 

and B input terminals on back of panel using M5 KEPs 

nuts and washers provided, as shown in “Compression 

Lug Inputs”. Tighten lugs to 20 in.-lb (2.25 N•m).

e.  Reinstall terminal covers.

a. 

Strip ¼ in. (0.635 cm.) of insulation from of

 

input cables.

b. 

For 

BATT

 and 

RTN

 of each feed, insert input cables 

all of the way into connectors and then tighten to 14 

in.-lb (~1.5 N•m).

Compression Lug Inputs

Screw-Tight Vertical & Horizontal Inputs

Alarm Indicators

9. 

Make sure power is off [open breaker, dummy fuse or open fuse holder at power distribution unit, or PDU] before 

connecting this panel’s cables to PDU.

10. 

Make sure breakers on this panel are all off.

11. 

Enable fuse or breaker at PDU (60A or 125A max., depending on 

configuration) to turn on Feed A to Side A of panel; check voltage and 

polarity at input connectors of panel. Also, check: 

• 

POWER ON A

 LED on front of panel turns on (green).

• 

INPUT BREAKER A 

LED (for a panel with optional input 

breakers) turns on (green).

If not, check that input breakers on rear of panel are pressed in.

• 

BREAKER ALARM

 LED turns on (red).

• 

POWER ON B

 must be off.

12. With 

POWER ON A

 lit (normal operation) — but with 

POWER ON B

 LED 

off (failure operation) —test power-fail relay and contacts at 

POWER 

FAIL 

terminals on rear of panel:

• 

Expect an open circuit (∞Ω) between Terminals 

C

 and 

NC

.

• 

Expect continuity (0Ω) between Terminals 

C

 and 

NO

.

Alarm Terminals

 

RTN

BATT

RTN

BATT

Heat shrink

tubing

BREAKER

ALARM

ALARM

RESET

INPUT

BREAKER

POWER

ON

A

B

B

A

®

SPOKANE, WA 800-551-4567

NO C NC NC C

FUSE ALARM

NO

POWER FAIL

Содержание T009-5 Series

Страница 1: ...ompression inputs only White or black panels can be configured with any combination of 1A to 20A Carling M Series breakers oriented with the on symbol at either the bottom or top 50A thermal input bre...

Страница 2: ...r dual hole lug Conductor size depends on input interruption device 20 in lb 2 25 N m max Input terminals Compressions Quantity Stud Lugs Cable Torque 4 2 BATT 2 RTN M5 with KEPS nut Use 8 mm 5 16 in...

Страница 3: ...omer Service Department at 1 800 551 4567 domestic only or 1 509 926 6000 for further recourse NOTE Panel brackets provide either flush or extended EIA or WECO mounting in a 19 or 23 rack Panel is con...

Страница 4: ...insi que pour l quipement ALERT ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories UL TUV et...

Страница 5: ...tighten to 14 in lb 1 5 N m Compression Lug Inputs Screw Tight Vertical Horizontal Inputs Alarm Indicators 9 Make sure power is off open breaker dummy fuse or open fuse holder at power distribution u...

Страница 6: ...l breaker out puts on each side must not exceed 40A for a panel with an optional thermal input breaker 50A for a panel having screw tight inputs connectors but without an optional thermal input breake...

Страница 7: ...aced Then turn off input power to that side of panel 4 Place breaker to be replaced in the off position 5 Using a very small flat tipped screwdriver carefully pry out on bottom of breaker while applyi...

Страница 8: ...nting Brackets Black 090 0041 0030 White 090 0041 0031 Front Cover Clear 090 0001 0001 Designation Label 1 7 A B 115353 ALERT The LINE side connection of the breaker has live VDC Do not allow contact...

Страница 9: ...is closed and C to NO is open Input Power Failure POWER ON A or POWER ON B LED s will go off POWER FAIL relay de energizes so that C to NC opens and C to NO closes Input Breaker Opens input breakers...

Страница 10: ...e Inputs Wire Binding A Side Inputs Compression Inputs With 50A Input Breakers Screw Tight Horizontal Inputs Without 50A Input Breakers Compression Inputs Without 50A Input Breakers 100A max side Scre...

Страница 11: ...akers Installed with On at Top 3 White Enclosure Breakers installed with On at Top Panel Color Breaker Orientation 0 Screw Tight Horizontal Inputs with 50A Thermal Input Breakers Inputs Type of Connec...

Страница 12: ...r its patent rights or the patent rights of others This document and the products described herein are subject to change without notice INPUT BREAKER B BATT 24V 48V 100A MAX 24V RTN BATT RTN GND CHS C...

Отзывы: