Dual 40/50/100A Configurable Breaker Panel

Power

 :: T009-5XXXXXXXXXXX

© Telect, Inc.,  All Rights Reserved, 118267-3 A0

1.509.926.6000  ::  telect.com

9

Installation Guide

 

LED & Alarm Summary

Normal Operation

 

• 

POWER ON A

 & 

POWER ON B

 LEDs will be on (green)

• 

INPUT BREAKER A

 & 

INPUT BREAKER B

 LEDs will be on (green) for panel with optional input breakers

• 

BREAKER ALARM

 LED will be off

• 

FUSE ALARM

 relay is de-energized so that —

◊  C to NC is closed and

◊  C to NO is open

• 

POWER FAIL

 relay is energized so that —

◊  C to NC is closed and

◊  C to NO is open

Input Power Failure

• 

POWER ON A

 or 

POWER ON B

 LED(s) will go off

• 

POWER FAIL

 relay de-energizes so that —

◊  C to NC opens and

◊  C to NO closes

Input Breaker Opens

 

(input breakers are optional)

• 

INPUT BREAKER A

 or 

INPUT BREAKER B

 LED(s) will go off

• 

BREAKER ALARM

 LED will go on (red)

• 

POWER FAIL

 relay de-energizes so that —

◊  C to NC opens and

◊  C to NO closes

• 

FUSE ALARM

 relay energizes so that —

◊  C to NC opens and

◊  C to NO closes

Output Breaker Opens

 (either being tripped or manually turned off) 

• 

BREAKER ALARM

 will go on (red)

• 

FUSE ALARM

 relay energizes so that —

◊  C to NC opens and

◊  C to NO closes

Pressing ALARM RESET turns off 

BREAKER ALARM

 LED and de-energizes 

FUSE ALARM

 relay.

Содержание T009-5 Series

Страница 1: ...ompression inputs only White or black panels can be configured with any combination of 1A to 20A Carling M Series breakers oriented with the on symbol at either the bottom or top 50A thermal input bre...

Страница 2: ...r dual hole lug Conductor size depends on input interruption device 20 in lb 2 25 N m max Input terminals Compressions Quantity Stud Lugs Cable Torque 4 2 BATT 2 RTN M5 with KEPS nut Use 8 mm 5 16 in...

Страница 3: ...omer Service Department at 1 800 551 4567 domestic only or 1 509 926 6000 for further recourse NOTE Panel brackets provide either flush or extended EIA or WECO mounting in a 19 or 23 rack Panel is con...

Страница 4: ...insi que pour l quipement ALERT ALERT Only use components and crimping tools approved by agencies or certifying bodies recognized in your country or region such as Underwriter s Laboratories UL TUV et...

Страница 5: ...tighten to 14 in lb 1 5 N m Compression Lug Inputs Screw Tight Vertical Horizontal Inputs Alarm Indicators 9 Make sure power is off open breaker dummy fuse or open fuse holder at power distribution u...

Страница 6: ...l breaker out puts on each side must not exceed 40A for a panel with an optional thermal input breaker 50A for a panel having screw tight inputs connectors but without an optional thermal input breake...

Страница 7: ...aced Then turn off input power to that side of panel 4 Place breaker to be replaced in the off position 5 Using a very small flat tipped screwdriver carefully pry out on bottom of breaker while applyi...

Страница 8: ...nting Brackets Black 090 0041 0030 White 090 0041 0031 Front Cover Clear 090 0001 0001 Designation Label 1 7 A B 115353 ALERT The LINE side connection of the breaker has live VDC Do not allow contact...

Страница 9: ...is closed and C to NO is open Input Power Failure POWER ON A or POWER ON B LED s will go off POWER FAIL relay de energizes so that C to NC opens and C to NO closes Input Breaker Opens input breakers...

Страница 10: ...e Inputs Wire Binding A Side Inputs Compression Inputs With 50A Input Breakers Screw Tight Horizontal Inputs Without 50A Input Breakers Compression Inputs Without 50A Input Breakers 100A max side Scre...

Страница 11: ...akers Installed with On at Top 3 White Enclosure Breakers installed with On at Top Panel Color Breaker Orientation 0 Screw Tight Horizontal Inputs with 50A Thermal Input Breakers Inputs Type of Connec...

Страница 12: ...r its patent rights or the patent rights of others This document and the products described herein are subject to change without notice INPUT BREAKER B BATT 24V 48V 100A MAX 24V RTN BATT RTN GND CHS C...

Отзывы: