![Telect DSX-3 Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/telect/dsx-3/dsx-3_user-manual_1080066017.webp)
Telect, Inc. • USA +1.509.926.6000 • 52.33.3836.37.52
www.telect.com • © 2010 Telect, Inc., All Rights Reserved, 139256 A0
Page 2-13
5. Ground the chassis lug to the rack using #6- to #14-AWG stranded wire and a single-hole
compression ring lug for a #8 stud.
Figure 9 - Grounding the Chassis
6. Connect I/O cables to the rear of the chassis, as shown in the following illustration.
In general,
•
For network I/O cables originating overhead, start with the lowest BCS 4R chassis in the
rack and work up.
•
For network I/O cables originating from below, start with the highest chassis in the rack
and work down.
•
NE I/O cables connect to the lower I/O connectors on the chassis. Use a BNC
insertion tool.
Figure 10 - BNC Insertion Tool