Dual-Feed 600A Load Center Frame
600CB10 & 600CB12 Installation Guide
7
© Telect, Inc. All rights reserved. 7.14.17 136429-2
509.926.6000 :: www.telect.com
4. Locate an unused rack position and mount the load center using at least two sets of fasteners per side, as shown in
Figure 6.
Mount the panel as high as possible on the rack, leaving at least 1RU of access space above the load center. Tighten
screws to 35-in./lb. (4.29 N
•
m).
Telect recommends using a seismic rack for best rigidity.
WARNING! Failure to properly ground this equipment can create hazardous conditions to installation personnel
and to the equipment.
Figure 6 – Rack Mounting