Demarcation Fuse/Circuit Breaker Alarm Panel
Power :: Model 125DM08
1.4.2 Installation Procedure
NOTE: Panel brackets are available for flush mounting in a 19-in. rack. A pair of 23-in. rack brackets are also
included. Either pair of brackets can be moved or installed to extend front of panel beyond the face of the rack in
1-in. (2.54 cm) increments.
WARNING
!
WARNING
!
WARNING! Failure to properly ground this equipment can create hazardous conditions to installation
personnel and to the equipment.
NOTE: Input and output wire size for this panel must be rated for the corresponding breaker/fuse size at the
power distribution unit (PDU). The input wiring to this panel may be a greater size to accommodate a voltage drop
from the primary power source.
WARNING! Before connecting input power cables, make sure input power to panel is turned off.
NOTE: Always follow operating company guidelines when connecting input wiring to the primary power source.
CAUTION
!
CAUTION!
Make sure the alarm connector on the fuse holder is straight before
inserting into the panel.
A bent alarm bayonet on a fuse holder can either cause internal damage to the
panel or fail to make electrical contact with the alarm wiring within the panel.
LINE & LO AD designations are on
bottom of TPC fuse holders on
THIS side of the panel.
Bezel
LINE & LO AD designations are on
top of TFD fuse holders on THIS
side of the panel.
Bezels
LINE
LOAD
LINE
LOAD
TFD Fuse Holder
TPC Fuse Holder
M AKE SURE ALARM
CO NNECTO R O N FUSE HO LDER
IS STRAIT BEFO RE INSERTING
INTO THE PANEL
A bent alarm bayonet on a fuse
holder can either cause internal
dam age to the panel or fail to m ake
electrical contact with alarm wiring
within the panel.
CAUTION !