© Telect, Inc., All Rights Reserved, 139695-3 A0
1.509.926.6000 :: telect.com
2
Demarcation Fuse/Circuit Breaker Alarm Panel
Power :: Model 125DM08
1.2 Specifications
Inputs/Outputs:
Specification:
Max. Rating Single-Pole, Circuit Breaker (each)
100A
Max. Rating TFD Holder, Schematic C
125A (TLS Fuse); 70A (TPS Fuse)
Max. Continuous Output Load (each)
80% of rated
Max. Total Load Rating of Panel
800A continuous
Voltage Range
±20 to ±28 Vdc
-40 to -60 Vdc
BATT & RTN Wire Size
#8 to #1 AWG
Ground Wire Size
#10 to #2 AWG (depends on input fuse)
Terminal Stud Sizes
(Input, Output, and Earth Ground)
¼-20 dual studs on 5/8” centers
¼-20 dual PEMs on 5/8” centers (side ground)
Power Dissipation
17W per I/O
Short-Circuit Withstand Rating
5000A
Alarms:
Specification:
Alarm Relay Contacts
0.6A @ 60 Vdc
Alarm Card Power Rating
1W
Alarm Wire Size
Solid: #26 to #22 AWG
Weight:
Specification:
Weight, Shipping
~20 lb (~9 kg) - 125DM08
~22 lb (~10 kg) - 125DM08-TFD
Dimensions:
Specification:
Nominal, without brackets:
Width
Height
Depth
17.25 in (43.8 cm)
3.5 in (8.9 cm)
10.84 in. (27.6 cm)
Environment:
Specification:
Operating Temperature
-5°C (23°F) to 50°C (131°F)
1.3 Inspection
Please read these instructions carefully before beginning installation. If you need assistance, call Technical
Support at 1.888.821.4856 (domestic calls), or 509.921.6161 (Option 2), or email us at [email protected].
Inspect equipment after unpacking and compare it to the packing list. Immediately report any shipping damage,
defects, or missing parts to Telect at 1.800.551.4567. Keep all documentation that comes with your shipment.