32
Figure 48
Insulating clearance limitations of HD
ISM with low upper terminal
Figure 49
Insulating clearance limitations of HD
ISM with high upper terminal
Short circuit current
Minimum clearance (a)
25 kA
150 mm
31.5 kA
190 mm
Table 5 - Minimum clearances due to electromagnetic influence
The recommended minimum open air clearances between phase to phase and phase to earth are stated in
Table 6. Shorter distances shall be verified by a voltage test.
Power frequency rated voltage
Impulse test voltage (BIL)
Minimum clearance (L2)
12 kV
75 kV
120 mm
17.5 kV
95 kV
140 mm
Table 6 - Minimum clearances due to rated insulation voltage
Minimum clearances due to rated insulation voltage
Figure 47
Electromagnetic clearances limitations
L2
Содержание TAVRIDA ELECTRIC VCB15 LD
Страница 1: ...VCB Vacuum Circuit Breaker 17 5kV 31 5kA 2000A 24kV 16kA 800A User Guide...
Страница 3: ...1 Product description...
Страница 7: ...2 Nameplates and seals...
Страница 11: ...3 Product handling...
Страница 23: ...4 Installation...
Страница 50: ...5 Commissioning...
Страница 57: ...6 Operation...
Страница 61: ...7 Maintenance and troubleshooting...
Страница 66: ...8 Disposal...
Страница 68: ...Appendix 1 Product range...
Страница 71: ...Appendix 2 Overall drawings...
Страница 74: ...75 ISM15_LD_3 Weight 13 kg ISM15_LD_6 PCD 133 mm Weight 55 kg...
Страница 81: ...82 ISM25_LD_2 1 PCD 150 mm Weight 35 kg ISM25_LD_2 2 PCD 150 mm Weight 37 kg...
Страница 85: ...Appendix 3 Secondary schemes...
Страница 86: ...87...
Страница 87: ...88...
Страница 88: ...89...
Страница 89: ...90...
Страница 90: ...91...
Страница 91: ...92...
Страница 92: ...93...