Data dependencies for the 20 mA settings of outputs 1 and 2
Output function
Minimum value
Maximum value
Default
Level
>4 mA Setting for Level
Tank TBO + RO
1
Tank
TBO - BD
2
Volume
>4 mA Setting for Volume
Max. value in the volume table
Max. value in the
volume table
Mass
>4 mA Setting for Mass
Max. value in the mass table
Max. value in the
mass table
Distance
>4 mA Setting for Distance
Tank TBO + RO
1
Tank RO
3
Interface Level
>4 mA Setting for Interface Level
Tank TBO + RO
1
Tank
TBO - BD
2
Interface Distance
>4 mA Setting for Interface
Distance
Tank TBO + RO
1
Tank RO
3
Interface Volume
>4 mA Setting for Interface
Volume
Max. value in the volume table
Max. value in the
volume table
Interface Mass
>4 mA Setting for Interface Mass
Max. value in the mass table
Max. value in the
mass table
Ullage Volume
>4 mA Setting for Ullage Volume
Max. value in the volume table
Max. value in the
volume table
Ullage Mass
>4 mA Setting for Ullage Mass
Max. value in the mass table
Max. value in the
mass table
Layer
>4 mA Setting for Layer
Tank TBO + RO
1
Tank height - BD
4
Layer Volume
>4 mA Setting for Layer Volume
Max. value in the volume table
Max. value in the
volume table
Layer Mass
>4 mA Setting for Layer Mass
Max. value in the mass table
Max. value in the
mass table
1
RO = Reference Offset (C1.10). TBO = Tank Bottom Offset (C.1.11).
2
BD = Blocking Distance (C.1.9). TBO = Tank Bottom Offset (C.1.11).
3
RO = Reference Offset (C1.10)
4
BD = Blocking Distance (C.1.9)
8
2
www.tek-trol.com
Technology Solutions
Instruction Manual
Tek-Flex
4100A