background image

Instruction Manual 

  

 

 

 

 

 

 

 

Tek-DP 1650A

 

 

www.tek-trol.com 

Technology Solutions

13 

10.

 

Connect instrument lines to the instrument valves 8 to the appropriate meter, recorder, 

transmitter w controller. 

11.

 

Retract the sensor by rotating the drive nuts counter-clockwise as viewed from the top. The 

nuts must be turned alternately, about two turns at a time, to prevent binding resulting from 

unequal loading. Continue this procedure until the sensor is fully retracted. 

 

NOTE 

If flow rate higher than 66 lb.ft/sec (90Nm/s) or pipe size larger than 8”(DN400), will require 

19mm diameter probe, mounted in 1” ball valve and 1” socket and 22mm hole 

 

4

 

Electrical Connection 

This section covers the all electrical connection requirement. Electrical connection of the device 

must be carried out by trained, qualified specialists authorized to perform such work by the 

installation site. 

 

 

WARNING 

 

Connect all electrical cables when the power is switched off. If the device does not 

have switch-off elements, then, overcurrent protection devices, lightning protection 

and/or energy isolating devices must be provided by the customer. 

 

The device must be grounded to a spot in accordance with regulations in order to 

protect personnel against electric shocks. 

 

 

NOTE 

 

When using the measuring device in hazardous areas, installation must comply with 

the corresponding national standards and regulations and the Safety Instructions or 

Installation or Control Drawings. 

 

 

Содержание TEK-DP1650A

Страница 1: ...Technology Solutions T 1650A EK DP Instruction Manual DProbar Multiport Self Averaging Flow Meter Document Number IM 1650A www tek trol com...

Страница 2: ...contact Customer Support 796 Tek Drive Crystal Lake IL 60014 USA Tel 1 847 857 6076 www tek trol com No part of this publication may be copied or distributed transmitted transcribed stored in a retri...

Страница 3: ...n 3 1 4 3 Storage 4 1 4 4 Nameplate 4 2 Product Description 4 2 1 Introduction 4 2 2 Measuring Principle 4 2 3 Dimensional Drawings 5 2 4 Specifications 6 2 5 Model chart 6 3 Installation 8 3 1 Select...

Страница 4: ...cation The manufacturer accepts no liability for the consequences of misuse by the operator Wrong installation or operation of the devices systems will cause the warranty to be void The respective Ter...

Страница 5: ...er may damage it or lead to system failure 1 4 Packaging Transportation and Storage 1 4 1 Packaging The original package consists of 1 Tek DP 1650A DProbar Multiport Self Averaging Flow Meter 2 Docume...

Страница 6: ...he pipe or conduit In a differential pressure flow meter as the liquid passes through the obstruction its potential energy is converted into kinetic energy The velocity of the liquid increases and is...

Страница 7: ...flow rate of the liquid using the following formulas To calculate the volumetric flow rate QA N K D2 Faa DP GF For liquids QA N K D2 Faa DP F For gases To calculate the mass flow rate QMASS N K D2 Ya...

Страница 8: ...available including Brass steel stainless steel and Hastelloy Bolt Material ASTM A193 B7 ASTM A194 2H ASTM A193 B8M ASTM A194 8MA Process Connection Flanged Weld prepared ends Threaded BSPT Threaded...

Страница 9: ...ss Connections A 1 mNPT B 1 150 Flange C 1 weldolet Temperature Measurement O No Temperature Sensor T Integral RTD X Remote thermowell and RTD Flow Transmitters Computers 01 None Customer Supplied 02...

Страница 10: ...rdous processes avoid direct contact with the fluid and the meter All installation must comply with local installation requirements and local electrical code WARNING This section offers instructions f...

Страница 11: ...stream of Fluid Bar are given in Table 1 Use of recommended straight pipe lengths of uniform diameter ensures that the flow measurement will be made with fully developed characteristics Included gate...

Страница 12: ...n Manual Tek DP 1650A www tek trol com Technology Solutions 10 3 1 2 TYPE FBR 73 FBR 75 FLUID BAR 3 1 3 TYPE FBR 76 FLUID BAR Fig 5 Type FBR 73 Fluid Bar Fig 7 Type FBR 76 Fluid Bar Fig 6 Type FBR 75...

Страница 13: ...trol com Technology Solutions 11 3 1 4 TYPE FBF 61 FLUID BAR 3 1 5 TYPE FBF 75 FBF 76 FLUID BAR 3 1 6 TYPE FBF 85 FLUID BAR Fig 8 Type FBF 61 Fluid Bar Fig 9 Type FBF 75 Fluid Bar Fig 10 Type FBF 76...

Страница 14: ...d support is aligned perpendicular to the pipe axis in line with the weld coupling 5 Install the Flow Tap unit isolating valve on the process connection Verify that the valve is in the fully open posi...

Страница 15: ...22mm hole 4 Electrical Connection This section covers the all electrical connection requirement Electrical connection of the device must be carried out by trained qualified specialists authorized to p...

Страница 16: ...To ensure meeting stated accuracy alignment must be within limits shown below Pipe size The Fluid Bar may have been designed for a different pipe size than that in which it is being used Measure pipe...

Страница 17: ...ts and solutions for process power and oil gas industries Tek Trol provides process measurement and control products for Flow Level Temperature Pressure Measurement Control Valves Analyzer systems We...

Отзывы: