background image

Tek-DP 1610D

Technology Solutions

*Note:

 

• The installation of thermometer pockets or wells will not alter the required minimum upstream straight  

      

   lengths for the other fittings.

• All straight lengths are expressed in multiples of diameter D.

• Values without parentheses are “Zero additional Uncertainty” values.

• Values in parentheses are “0.5% additional Uncertainty” values.

Table 1: Required Straight Lengths for Orifice Plate, Nozzle

Beta 

Ratio

Upstream Side

of Primary Devices (U1)

Downstream Primary

Devices (D1)

Single 90

bend or

tee (Flow

from one

branch only)

Two or

0 more 90

bends in

the same

plane(*)

Two or

0 more 90

bends in

different

planes

Reducer

2D to D

over a

Length of

1.5D to 3D

Expander

0.5D to D

over a

Length of

D to 2D

Globe valve

fully poen

Full bore

ball valve

or gate valve

fully poen

Abrupt

symmetrical

reduction

having a

diameter

ratio >=0.5

Thermo-

meter

(pocket

or well*) of

diameter

<=0.03D

Thermo-

meter 

(pocket

or well*) of

diameter

between

<=0.03D and

0.13D

Fitting

(All

mentioned

in Upstream

Side of

Primary

Devices)

0.20

10

(6)

14

(7)

34

(17)

5

16

(8)

18

(9)

12

(6)

30

(15)

5

(3)

20

(10)

4

(2)

0.25

10

(6)

14

(7)

34

(17)

5

16

(8)

18

(9)

12

(6)

30

(15)

5

(3)

20

(10)

4

(2)

0.30

10

(6)

16

(8)

34

(17)

5

16

(8)

18

(9)

12

(6)

30

(15)

5

(3)

20

(10)

5

(2.5)

0.35

12

(6

16

(8)

36

(18)

5

16

(8)

18

(9)

12

(6)

30

(15)

5

(3)

20

(10)

5

(2.5)

0.40

14

(7)

18

(9)

36

(18)

5

16

(8)

20

(10)

12

(6)

30

(15)

5

(3)

20

(10)

6

(3)

0.45

14

(7)

18

(9)

38

(19)

5

17

(9)

20

(10)

12

(6)

30

(15)

5

(3)

20

(10)

6

(3)

0.50

14

(7)

20

(10)

40

(20)

6

(5)

18

(9)

22

(11)

12

(6)

30

(15)

5

(3)

20

(10)

6

(3)

0.55

16

(8)

22

(11)

44

(22)

8

(5)

20

(10)

24

(12)

14

(7)

30

(15)

5

(3)

20

(10)

6

(3)

0.60

18

(9)

26

(13)

48

(24)

9

(5)

22

(11)

26

(13)

14

(7)

30

(15)

5

(3)

20

(10)

7

(3.5)

0.65

22

(11)

32

(16)

54

(27)

11

(6)

25

(13)

28

(14)

16

(8)

30

(15)

5

(3)

20

(10)

7

(3.5)

0.70

28

(14)

36

(18)

62

(31)

14

(7)

30

(15)

32

(16)

20

(10)

30

(15)

5

(3)

20

(10)

7

(3.5)

0.75

36

(18)

42

(21)

70

(35)

22

(11)

38

(19)

36

(18)

24

(12)

30

(15)

5

(3)

20

(10)

8

(4)

U2

14

18

31

7

15

16

10

15

3

10

Содержание TEK-DP 1610D

Страница 1: ...Quick Start Guide TEK DP 1610D 796 Tek Drive Crystal Lake IL 60014 USA 1 847 857 6076 1 847 655 6147 www tek trol com Integral Orifice Assembly...

Страница 2: ...ational and international standards codes and practices Review the approvals section of the 3800E Multivariable Pressure Transmitter reference manual for any restrictions associated with a safe instal...

Страница 3: ...Technology Solutions Fig 5 Two or More 90 Bends in Same Planes 4 Installations Straight Length Requirements Fig 3 Reducer U D Fig 4 Single 90 Bend Flow from One Branch U D 2d to d over a length of 1...

Страница 4: ...L 60014 USA 1 847 857 6076 1 847 655 6147 www tek trol com Quick Start Guide Fig 6 Two or More 90 Bends in Different Planes Fig 7 Expander Fig 8 Ball Valve or Gate Valve Fully Open U D 0 5d to d over...

Страница 5: ...ymmetrical reduction having a diameter ratio 0 5 Thermo meter pocket or well of diameter 0 03D Thermo meter pocket or well of diameter between 0 03D and 0 13D Fitting All mentioned in Upstream Side of...

Страница 6: ...5 4 0 50 1 5 0 5 2 5 1 5 8 5 5 5 0 5 2 5 1 5 3 5 1 5 4 0 55 2 5 0 5 2 5 1 5 12 5 6 5 0 5 3 5 1 5 4 5 2 5 4 0 60 3 1 3 5 2 5 17 5 8 5 0 5 3 5 1 5 4 5 2 5 4 0 65 4 1 5 4 5 2 5 23 5 9 5 1 5 4 5 2 5 4 5...

Страница 7: ...pipe to ensure that condensate does not collect on the transmitter sensing diaphragms If the fluid is flowing up a direct mount Tek DP 1610D should not be used in vertical gas applications because of...

Страница 8: ...ect on the transmitter sensing diaphragms If the fluid is flowing down a direct mount Tek DP 1610D should not be used in vertical liquid or steam applications Vertical installation for steam should be...

Страница 9: ...Vent B is High Valve C is Equalizer D is Equalizer Valve Where A is Low Valve B is Vent C is High Valve D is Equalizer Valve E is Block Valves Fig 13 Direct Mount Gas Measurement Fig 14 Remote Mount G...

Страница 10: ...Guide Liquid Measurement Fig 15 Direct Mount Liquid Measurement Fig 16 Remote Mount Liquid Measurement Where A is Vent B is Low Valve C is Equalizer Valve D is High Valve Where A is Vent B is High Val...

Страница 11: ...ect Mount Steam Measurement Fig 18 Remote Mount Steam Measurement Where A is Vent B is Low Valve C is Equalizer Valve D is High Valve Where A is Vent B is High Valve C is Equalizer Valve D is Vent Val...

Страница 12: ...transmitter o Remove the temperature terminal housing cover o Disconnect the RTD lead wires from the terminal block o Separate the wires so that the un insulated ends are not affecting o Check that th...

Страница 13: ...parameters for accuracy Cross check pipe inside diameter for proper sizing Raising flow signal Two phase flow The flow meter is a head measurement device and will not measure a two phase flow accurate...

Страница 14: ...utions BV Tek Trol Middle East FZE PO Box 121 Windsor Colorado 80550 USA Sales 1 847 857 6076 796 Tek Drive Crystal Lake IL 60014 USA Sales 1 847 857 6076 Florijnstraat 18 4879 AH Etten Leur Netherlan...

Отзывы: