Tek-DP 1610D
Technology Solutions
• For Gas
Where,
A is 90° Recommended Zone
B is Vertical Plane
C is Horizontal Plane
Where,
A is 360° Recommended Zone.
Tek-DP 1610D Integral Orifice Assemblies should be mounted above the pipe to ensure that condensate
does not collect on the transmitter sensing diaphragms
If the fluid is flowing up, a direct mount Tek-DP 1610D should not be used in vertical gas applications
because of drain and vent orientation. Consider remote mounting the pressure transmitter to facilitate
condensate draining.
Fig 9: Direct Mount Gas in Horizontal Pipes
Fig 10: Direct Mount Gas in Vertical Pipes
A
FLOW
A
A
B
C
A
B
C