IL603 Tek-SELECT

®

II Manual  • Page 1

Section 1.0 — SYSTEM INSTALLATION

1.1 Installation Procedure

1. Read instructions to determine equipment location and

installation method.

2. Install housings and wiring.

3. Check and connect wiring.

4. Program masters and install stations.

5. Check operation.

1.2 Planning and Equipment Location

NOTE: Do not locate any intercom components or wiring within
3 feet (1 meter) of motors, transformers, fluorescent lights, dim-
mer switches, electrical wiring or other sources of electrical
interference.

NOTE: It is recommended that special consideration be given
to the system cabling if electromagnetic interference (EMI) or
radio frequency interference (RFI) presents a potential interfer-
ence problem at a jobsite. The system cabling should be
shielded—or in extreme cases installed in metallic conduit—to
provide protection from extraneous signals or noise. If EMI
(AC hum, ESD, computer or telephone data noise, etc.) and RFI
interference sources are in physical contact (for example, inter-
com cable is placed on top of AC wiring), then standard
shielded cable protection may be negated.

NOTE: TekTone

®

 is not responsible for interference resulting

from improper installation.

Masters and Remotes:

1. Do not locate masters near any source of direct heat,

extreme cold, or in areas exposed to dust, oil, chemicals
or excess humidity. Locate stations where they will be
convenient to use. If wall mounted, locate at convenient
operating height.

2. Do not locate stations close to each other (separate

rooms are preferred).

3. Do not locate flush mounted stations back to back on a

common wall.

Power Supply and Relays:

Locate the power supply and other central equipment near
the center of the master-to-master cable run and where
convenient for service.

Do not locate units near any source of direct heat or extreme
cold.

Transformer:

The transformer must be provided with 115 VAC electrical
power. Locate the transformer within 50 feet (15 meters) of
the power supply, and at least 3 feet (1 meter) from master
stations, remote stations and intercom wiring.

Do not locate transformers near any source of heat.

Do not connect transformer to power source until wiring is
complete. Observe all local and national electrical codes.

Music System:

Locate music system according to the instructions supplied
with the system. If any area requires music without intercom,
the music system may be located in that area.

1.3 System Housings

IH102

Flush mounting ring for indoor remotes

IH110R

Flush mounting ring for SM406 and SM411 masters

IH400A

Desk cabinet for SM401 and indoor remotes

IH401

Desk cabinet for SM404, SM406 and SM411

1.4 Wiring Installation

Master Stations:

Master stations may be loop wired.

Note: Due to common impedance coupling, tone signals
may be amplified and heard by master stations monitoring
other stations. With long wires, this interference may be
quite loud. This effect may be reduced by using two
conductors for the terminal C wire, by using the next larger
size conductor (#20 instead of #22), or by wiring the system
in a star pattern, so that all stations home run to the central
equipment (power supply) location.

If all call relay is not used, limit length of cable as follows:

Wire Size

Maximum Total Cable Length

#22

500 feet (150 meters)

#20

800 feet (240 meters)

#18

1200 feet (360 meters)

If the all call relay is used, limit length of cable as follows:

Wire Size

Maximum Total Cable Length

#22

250 feet (75 meters)

#20

400 feet (120 meters)

#18

600 feet (180 meters)

Number of wires:

7 1 per station*
SM401 Master Station = 8 wires
SM406 Master Station = up to 13 wires
SM411 Master Station = up to 18 wires

* If no door release operation is required, eliminate one
common. A second common can be eliminated if no remotes
with lighted push buttons are used.

Run cable from master-to-master and to central equipment
location.

Note: Better performance may be obtained by running all
wires to the central equipment (power supply) location.

All Call:

Add 2 wires to master-to-master cable.

Содержание Tek-SELECT II SM401

Страница 1: ...unication is needed Multicolored signal lights hands free reply privacy and monitoring are all standard features Optional equipment is available to call all stations distribute music and control remot...

Страница 2: ...raciesthatmayappearinthis documentation TekTone the TekTone logo Tek Call Tek Care Tek Check In Tek Com Tek Digicare Tek Door Tek Entry III Tek Guard Tek Micro Tek MMARS II Tek NIOS Tek Paging Tek Pho...

Страница 3: ...ume Adjustment 3 1 9 Terminal Reference for Master 3 2 0 OPERATING INSTRUCTIONS 2 1 Master Station 5 Call another station 5 Answer a call from a master at a remote 5 Answer a call from a master at a m...

Страница 4: ...strike RY400 Remote control relay 3 outputs RY401 All call relay for 12 stations RY402 In use adapter SB205A Paging horn requires EC105 capacitor and transformer SF400 Call button for use with paging...

Страница 5: ...cal power Locate the transformer within 50 feet 15 meters of the power supply and at least 3 feet 1 meter from master stations remote stations and intercom wiring Do not locate transformers near any s...

Страница 6: ...any part of the system to AC power lines Do not connect transformer to power source until wiring is complete 1 6 Equipment Installation Surface Mounting SM404 SM406 and SM411 Masters 1 Install IH401...

Страница 7: ...400 remote control relay is installed Violet F When this line is shorted to the N connection through a dry contact the master switches from listen to talk A selector button must be pushed in for this...

Страница 8: ...Page 4 IL603 Tek SELECT II Manual...

Страница 9: ...lights Answer a call from a master at a master 1 Calls from masters are not indicated by a light but may be preceded by a short tone signal Master calls are announced by voice 2 To answer a If the PR...

Страница 10: ...Page 6 IL603 Tek SELECT II Manual...

Страница 11: ...IME DIP SWITCH DETAIL 6 OFF ON 1 3 CONNECTOR 2 5 4 1 2 9 11 7 6 8 O R A N G E BLUE G R E E N B R O W N R E D 3 B L A C K B R O W N W H I T E RED WHITE VIOLET WHITE GREY 10 CONNECTOR 1 D N B A P M L X...

Страница 12: ...9 8 11 7 M X 5 6 10 1 3 2 4 MASTER SM411 T1 D2 T2 R2 D1 L N P M E1 E2 R1 D C POWER SUPPLY PK400 F R N C L P D B A X 9 11 7 M 8 5 6 10 1 3 2 4 MASTER SM411 F R N C L P D B A 10 9 11 7 M 8 5 6 X 1 3 2 4...

Страница 13: ...6 C R L SM406 MASTER C X OUTDOOR REMOTE OR642 OR642W TRANSFORMER SS106 24 V A C FOOT SWITCH 7 If the paging horn is not connected to the all call relay the 25V audio transformer is not needed NOTES 2...

Страница 14: ...EMOTE D2 D1 R2 T2 T1 M L E1 C P D R1 N E2 POWER SUPPLY PK400 A P B C R L N D F K2 3 K6 M X 1 K1 K3 K4 K5 4 6 2 5 MASTER SM406 TRANSFORMER SS106 TRANSFORMER SS106 24 V A C X3 K2 K3 K1 S3 S2 X2 X1 ADAPT...

Страница 15: ...ease is not used delete connections to terminals D and D1 5 RY402 should always have a direct connection to the PK400 s N terminal 2 Connect power transformers to 115 V A C in accord with local electr...

Страница 16: ......

Отзывы: