background image

Rev. 4245-v3_2_en

 

Fire 

Lights up 

one 

time

 for 

10 

seconds

 when 

the smoke 
density 
reaches the 
activation 
threshold  

 

Not lit 

Detector failure 

Triple

 blink 

every 25 
seconds 

Not lit 

Powering up 

Not lit 

Any 

 

Primary battery 
failure 

Not lit 

Any  

Secondary 
battery failure* 

Not lit

 

Any  

Power failure 

Triple

 blink 

every 25 
seconds 

Not lit 

Tampering/ 
Tamper recovery 

Lights up 

one time

 for 

0.2 seconds

 

Not lit

 

Network search 

Not lit 

Blinks with 
frequency of 

5Hz

 for 

1 to 

60 seconds

 

 

No network 

Not lit 

Double

 blink 

every 25 
seconds 

 

Radio module 
failure 

Not lit 

Triple

 blink 

every 25 
seconds 

+: notification issued; 

–: notification not issued 

*: with secondary battery installed 

 

Notes

 

1

 The 

«Power failure»

 notification is processed by the 

red

 LED 

if  both  batteries  are  discharged  or  if  one  of  the  batteries  is 
missing and the second battery is discharged.

 

If 

«Primary  battery  failure» 

notification  appears, 

replace 

the battery within 

two months

.

 

 

Operating Modes 

 

The detector provides for 

«Registration» and «Test» modes. 

 

7.1 

«Registration»

  mode  is  intended  for  registering  the 

detector  in  the  wireless  network  in  which  it  supposed  to 
operate (see 

p.8.3

). 

7.2 

«Test»

  mode  is  intended  for  testing  electronic  and 

optical circuits of the detector. 
The mode is activated upon a command from the control panel 
or  LT.  Within  5  seconds  after  the  command  receipt,  the 
detector  should  issue 

«Test  fire»  notification  (in  case  of 

detector  normal  operation)  or 

«Detector  failure»  or  «Power 

failure

» notifications (in case of corresponding failures). 

 

Pre-Starting Procedure 

 

8.1 

After  transportation  in  conditions  differing  from  those  of 

operation,  keep  the  detector  unpacked  for  4  hours  in  the 
expected operating conditions. 

 

8.2  Running Detector. Replacing Batteries

 

 

WARNING! 

Lithium-thionyl-chloride  batteries  have  an  effect  of 

«passivation» to provide the possibility of long-term storage.  To 
provide  battery  normal  operation  after  long-term  storage,  hold 
an 

«activation» procedure. 

 

Step-1

 

 

Turn the detector

’s electronic unit 

counter-clockwise. Remove the 
electronic unit from the detector 
base. 

 

Step-2 

 

When  using 

one

  battery  to  switch  the  detector  ON,

 

insert 

the 

Primary

 battery. 

Note

 

–  When  using 

two

  batteries,  it  is  recommended  to 

insert  the 

Secondary

  battery  first,  and  then  the 

Primary

 

battery.  The  Secondary  battery  can  be  inserted  up  to 

1

 

minute

 after inserting the Primary battery. 

To  replace  the  battery,  remove  the  old  one,  and  after  at 
least 30 seconds insert the new one. 
The  red  LED  lights  up  for 

1  to  40  seconds

 

–  the  battery 

activation and checking period. 
If  after 

40  seconds

  the 

red

  LED  flashes 

triply 

every  25 

seconds, re-activate the battery by removing it, and after at 
least 30 seconds reinserting it. 

Warning!  If  two  batteries  have  been  inserted,  replace 
both batteries.

 

 

 

8.3 

Registering  the  Detector  in  the  Wireless 

Network

 

 

Detector  registration  procedure  is  required  for  detector 
identification  in  the  wireless  network  in  which  it  is  supposed 
to operate. 

 

Step-1 

According  to  Astra-Zitadel  System  Control  Panel`s 

Operating Manual *

 perform the following procedure: 

1)

  Install 

Software  ** 

(MSS  Astra-Z,  Pconf-Z  or  MSS  Astra 

Pro) intended for configuring Control Panel. 

2) 

Create wireless network 

Step-2 

Perform 

par.8.2

 

Step-3 

Switch  the  control  panel  to 

Wireless  device  registration

 

mode  by  the  method  described  in  the  appropriate  Control 
Panel 

Operating manual *

  

 

Step-4 

Initiate  detector  registration  procedure  by  one  of 

methods

:  

a) using the 

LT 

(step-5)

;

 

b) using the 

Reg

 plug and the 

tamper switch 

(step-6) 

 

WARNING! 
Avoid  to  initiate  registration  procedure  on  several 
detectors simultaneous  

 

Step-5 

Initiating Detector 
Registration Using the LT:

 

-  Press  the  lower  button  on  the 
LT  and  hold  until  a  beam 
appears. 
-  Direct  the  laser  beam  at  the 
detector LED. 
- Irradiate the LED for 

1 second

The  detector 

red

  LED  lights  up  for 

2  seconds

,  and  then 

the detector switches to wireless network search mode and 
the detector 

white 

LED blinks at a frequency of 

5 Hz

 

No more than 10 m 

At least 0.1 m 

Отзывы: