Rev. 4245-v3_2_en 

Step-6 

Initiating 

Detector 

Registration 

Using  the  Reg  Plug  and  Tamper 
Switch:

 

1) 

Shortly (for 

1-2 seconds

) close

 

 the 

Reg

 plug with a screwdriver.

 

 
 
 
The  detector  switches  to  registration  in  wireless  network 
mode for 

60 seconds

2) 

Within 60 seconds, shortly (for 

0,2-2 

seconds

) press the 

tamper switch

  

on  the  detector.  The  detector  switches 
to  wireless  network  search  mode  and 
the  detector`s 

white 

LED  blinks  at  a 

frequency of 

5 Hz

Step-7

 

 

Verify registration procedure:  

  Once registration procedure completed 

successfully

, the 

abbreviated  name  of  detector 

«SD»

  appears  on  the  screen 

or   

«SDxxx registered»

  notification  appears  on  the control 

panel`s screen. 
Assemble the detector: 
-  Place  the  detector

’s  electronic  unit  on  the  base,  aligning 

the 

projections

 on the detector base with the 

button

 on the 

electronic unit circuit board.  

 

 

 

-  Press  the housing  of  the  detector

’s electronic unit against 

the base and turn it clockwise firmly. 

 

In  case  registration  procedure 

failed 

repeat  the 

registration procedure, i.e. perform steps 

3

 and 5 

or

 3 and 

6

.

 

 

Step-8

 

 

After  successful  registration  of  the  detector,  for  long  term 
storage  before  its  installation,  it  is  allowed  to  switch  the 
detector 

OFF

  by  removing  the  battery  or  installing  a  soft 

isolator. 
When  power  is  supplied,  there  is  no  need  to  re-register  the 
detector in the same wireless network if it was not intentionally 
removed  from  the  network  through  software  or  control  panel`s 
menu. 

 

 

8.4 Deleting Detector from Wireless Network 

 

Deletion the detector from wireless network is performed 

using 

Software **

 or through Control Panel`s menu.

 

When deleting detector from wireless network, Control Panel 
transmits  notification  about  deletion  to  detector  within 

two 

periods  of  RF  supervision  time. 

After  receiving  the 

notification detector issues "No network" notification. 

  To speed up the deletion procedure: 

- remove detector`s cover 
- shortly close 

Reg

 plug 

- press and hold down tamper switch for 

8-10

 sec. 

The  detector  issues  "No  network"  notification  to  LED  and  is 
available for registration.

 

 
 
 
 

 

Installation 

 

9.1  Location 

 

9.1.1  Install the detector on the ceiling. 

 

9.1.2 The area covered by one detector, as well as the maximum 
distance  between  detectors  and  between  the  detector  and  the 
wall, must be determined according to Table 2. 
Table 2 

Secured room 

height, 

Average area 

covered 

by one detector, m

2

 

Maximum distance, m 

between  

detectors 

from detector 

to wall 

up to 3.5 

up to 85 

9.0 

4.5 

> 3.5 to 6.0 

up to 70 

8.5 

4.0 

> 6.0 to 10.0 

up to 65 

8.0 

4.0 

 
9.1.3 When installing the detector on a sloped ceiling, it should 
be installed at the highest point. 

 

9.1.4  Do  not  cover  the  detector;  smoke  particles  must  freely 
penetrate the grating into the smoke chamber. 

 

9.2  Installation Procedure 

 

Step-1  

Turn the detector

’s electronic 

unit counter-clockwise. 

 

 

 

Remove  the  electronic  unit 
from the detector base. 

Step-2  

Mark  a  place  on  the  ceiling, 
using  the  detector  base  as  a 
template. 

 

 

 

Fasten  the  base  to  the 

ceiling.

 

Step-3  

Install the

 

detector

’s electronic unit onto the fastened base:

 

- Align the 

projections

 on the detector base with the 

button

 

on the electronic unit circuit board. 
 

 

 

-  Press  the  housing  of  the  detector

’s  electronic  unit  against 

the base and turn it clockwise firmly. 
-  Make  sure  the  detector  LED  issues 

«Standby  mode» 

notification. 

 

 