Astra-Z-4245

 

 

Wireless

 

Optic-Electronic Fire Smoke Detector

 

 

Operation Manual

 

 

 

 

 

 

 

 

 

This  operation  manual  is  intended  for  studying  the  operating 
principles,  proper  use,  storage,  and  maintenance  of  the 
Wireless  Optic-Electronic  Fire  Smoke  Detector  Astra-Z-4245 
(hereinafter referred to as detector) (Figure 1). 
The  manufacturer  reserves  the  right  to  make  changes  to 
improve the  detector without prior notification. All changes will 
be included in the new revision of the operation manual. 

 

List of Abbreviations

Astra-Zitadel System

: Astra-Zitadel on-site wireless intrusion / 

fire detection and alarm system; 

Astra-Zitadel System Control Panel

: Astra-Z-812M, Astra-Z-

8945  ver.A,  Astra-8945  Pro  or  Astra-812  Pro  Control  Panel 
(with connected Astra-Z Wireless Extender); 

LT

: Laser Tester Astra-942; 

MSS Astra-Z

: Astra-Z Monitoring Software Suite; 

MSS Astra Pro

: Astra Pro Monitoring Software Suite. 

 

Function 

 

1.1 

The  detector  is  intended  for  detecting 

fire  accompanied  by  smoke,  forming  and 
transmitting 

«Fire» notification to the Astra-

Zitadel system control panel via radio. 

1.2 

Power is supplied to the detector from 

one  or  two  lithium-thionyl-chloride  batteries 
(primary  and  secondary),  size  AA,  voltage 
3,6 V. 

 

Operating Principle 

 

The  detector

’s  operating  principle  is  based  on  registering

 

infrared  radiation  (hereinafter  IR)  that  is  reflected  from  smoke 
particles  in  a  smoke  chamber  by  a  photodetector.  Further  the 
electric  signal  formed  by  the  photodetector  is  amplified  and 
sent  to  microcontroller  in  order  to  analyze  the  smoke  density 
value.  The  microprocessor  forms  smoke  density  value  and 
«Fire»  notification  in  accordance  with  specified  operating 
algorithm. 

 

Specification 

 

Detector sensitivity, dB/m ........................................ 0.05 to 0.2 
Response time, s, max ......................................................... 10 
Detection area, m

2

, max ..................................................... 110 

Installation height, m, max .................................................... 10 

Technical Parameters of Radio Channel

 

Operating frequency range, MHz .................. 2 400 to 2 483. 5 
Number of operating channels at 5 MHz intervals ................ 16 
Channel width, MHz ............................................................... 2 
Wireless coverage range, line-of-sight, m, min ................... 300 

General Technical Parameters

 

Current consumption, mA, max: 
- with radio module OFF .................................................... 0.05 
- with radio module ON ....................................................... 105 
Battery replacement  
indication threshold, V ......................................................... 2.6 
Power supply voltage lower threshold (programmed 
deactivation threshold retaining  
battery discharge indication), V ........................................... 2.1 
Technical readiness time, s, max ......................................... 40 
Standby mode recovery time, s, max ....................................... 60 
Overall dimensions, mm, max: 
- diameter ........................................................................... 106 
- height ................................................................................. 60 
Weight (without battery), kg, max ...................................... 0.13 
Primary battery average life time, year, min ........................... 3 
Secondary batteries average life time, year, min ..... 5 

Operating Conditions

 

Temperature range, 

°

C ..................................... from -30 to +55 

Relative air humidity, % ............................... up to 93 at +

40 °C 

without moisture condensation  

Delivery Set 

 

Astra-Z-4245 Wireless 
Optic-Electronic Fire Smoke Detector ................................ 1 pcs. 
Battery ............................................................................... 2 pcs. 
Screw 3.

9×32 ..................................................................... 2 pcs. 

Dowel 6×30 ........................................................................ 2 pcs. 
Operation Manual ............................................................. 1 copy 

 

Structure 

 

Batteries from delivery package are inserted. 
 

 

 

Figure 2 

 

5.1

 The detector consists of a removable electronic unit and a 

base (Figure 2).

 

5.2

  Inside  the  electronic  unit  is  a  smoke  chamber,  printed 

circuit  board  (PCB)  with  radio  elements,  radio  module  and 
batteries. 

5.3

  Mounted  on  PCB  is  a  tamper  switch  (S1  button),  which 

results  in  the 

«Tampering»  notification  when  the  cover  is 

removed. 

5.4

  Mounted  on  PCB  are  red  and  white  LEDs  for  detector 

operability / wireless network status supervision respectively. 

 

Note

  -  It  is  not  recommended  to  disassemble  the  detector

’s  electronic 

unit, as this could damage the detector tuning.

 

 

Notification Types 

 

Table  1:  Notifications  processed  by  LEDs  and  Control  Panel 
(or MSS interface) 

 

Notification 

 

Type

 

Red 

 

LED 

 

White

 

LED

 

Control 

Panel

 

Standby 
mode start 

Lights up for 

1

 

to 40 
seconds

 

Not lit 

 

Normal 

Lights up for 

0.2 seconds 
one time

 per 

(60±5) 
seconds

 

Not lit 

Figure 1 