INSTALLATION AND MAINTENANCE INSTRUCTIONS

HD203B

Addressable Photoelectric Smoke& Heat Detector

SPECIFICATIONS

Operating Voltage Range:

16 to 28 VDC

Standby Current:

380µA @ 28 VDC (one communication every 5 seconds with LED blink enabled)

Maximum Alarm Current (LED on: ) 5 mA @ 28 VDC

Operating Humidity Range:

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range:

14°F to 122°F (-10°C to50°C)

Smoke Sensitivity:

1.06±.26%FT.

Fixed Temperature Rating:

135°F (57°C)

Rate of Rise Detection:

Responds to greater than 15°F/min,A2R

Height:

2.2˝ (55 mm) installed in Base

Diameter:

4.0˝ (103 mm)

Weight:

5.5 oz. (155 g)

INSTALLATION

BEFORE INSTALLING

This sensor must be installed in compliance with the

control panel system installation manual. The installation

must meet the requirements of the Authority Having

Jurisdiction (AHJ). Sensors offer maximum performance

when installed in compliance with the National Fire

Protection Association (NFPA); see NFPA 72.

GENERAL DESCRIPTION

The detector is plug-in type photoelectronic smoke and

heat sensors with addressable analog communications.

The sensors transmit an analog representation of smoke

density or temperature over a communication line to a

control panel. Inside MCU’s EEPROM keep the sensor’s

address that can be set by a portable Address setting

device.

Two LEDs on the sensor are controlled by the panel to

indicate sensor status.

The

detector require

compatible

addressable

communications to function properly. Connect these

sensors to listed-compatible control panels only.

WIRING GUIDE

All wiring must be installed in compliance with the

National Electrical Code, applicable local codes, and any

special requirements of the Authority Having Jurisdiction.

Proper wire gauges should be used. The installation wires

should be color-coded to limit wiring mistakes and ease

system troubleshooting. Improper connections will

prevent a system from responding properly in the event of

a fire.

Remove power from the communication line before

installing sensors.

1. Wire the sensor base per the wiring diagram, Figure 1.

2. Set the desired address by portable address setting

device.

3. Install the sensor into the sensor base. Push the sensor

into the base while turning it clockwise to secure it in

place.

4. After all sensors have been installed, apply power to

the control unit and activate the communication line.

5. Test the sensor(s) as described in the TESTING section

of this manual.

Figure 1. Wiring diagram:

Dust covers provide limited protection against

airborne dust particles during shipping. Dust covers

must be removed before the sensors can sense smoke.

Remove sensors prior to heavy remodeling or

construction.

TAMPER-RESISTANCE

The detectors include a tamper-resistant capability that

prevents their removal from the bracket without the use

of a tool.

CAUTION

©

60mm