VOT 2; Rev 1.2; EN; 09.07.2013
TKT67C
– Installation and maintenance
21
4.10 Control Module panel test functions and alarms
LED
Description
Instruction
BATTERY TEST
As a basic setting, the battery test is done
automatically twice a year: on the 4
th
of July
and on the 4
th
of January, at 12 pm (midnight).
If the LED is continuously lit, the battery
test is in progress.
If the LED is flashing, an error has been
detected in the battery test. In this case
the
External fault
LED will also be lit.
During the battery duration test, the central
battery unit is switched to battery mode and
all output circuits are switched on.
If the LEDs
Internal fault
is lit and
Battery
test
is flashing, the battery duration test
has failed.
A change of battery always requires a new
configuration, so that the software knows a
battery has been replaced.
The battery test can be started by pressing
one button on the control unit interface, or
manually using the control unit menu.
No action needed, unless the test
fails. If the test fails check condition
of batteries
To run the battery test yourself,
either
1. Press the
BROWSE
button for
8 seconds.
or
1. Press the
MENU / OK
button.
2. Use the
BROWSE
button to
select 2,
TESTING.
3. Use the
SET
button to select 3,
battery test during 2/3 of the
operation time.
4. Accept the selection with the
MENU / OK button.
The battery test starts.
LUMINAIRE TEST
If the LED is continuously lit, the luminaire test
is in progress.
If the LED is flashing with
External fault
LED,
configuration is in progress.
Luminaire test must be carried out once in 1-7
days. Factory setting is once a day at
midnight (00.00 o’clock).
No action needed, unless the test
fails. If the test fails check condition
of luminaires.
To run the luminaire test yourself,
either
1. Press the
BROWSE
button for
3 seconds.
or
1. Press the
MENU / OK
button.
2. Use the
BROWSE
button to
select 2,
TESTING.
3. Use the
SET
button to select 1 =
Starting the luminaire test.
4. Accept the selection with the
MENU / OK button.
The luminaire test starts. If a faulty
luminaire was found in any of the
circuits, its corresponding LED will
flash when its circuit number is
Содержание TKT6716C
Страница 26: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 26 5 2 1 Parts layout...
Страница 42: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 42...
Страница 43: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 43...
Страница 44: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 44...
Страница 45: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 45...
Страница 46: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 46...
Страница 47: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 47...
Страница 48: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 48...
Страница 49: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 49...
Страница 50: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 50...
Страница 51: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 51...
Страница 52: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 52...
Страница 53: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 53...
Страница 55: ...VOT 2 Rev 1 2 EN 09 07 2013 TKT67C Installation and maintenance 55...