VOT 34; Rev 1.81; EN; 11.12.2019
TKT65C
– Installation and maintenance
33
Figure 9. Error log
Error code:
Error description:
1
Internal error
2
External error
3
Central battery system has not been configured
4
Internal and external error
5
Fuse fault or other malfunction in output circuit
6
Deep discharge
7
Error with changeover board
8
Overload
To move back to the higher-level menu from the test log, press the SETUP button.
Setup
You can change the settings and start tests by first selecting the desired function using the +/- buttons
and then confirming your selection by pressing the SETUP button. By using the Setup display, you can
start a battery or luminaire test, as well as set the date and time. Once you have started a battery test,
you can cancel it by pressing the SETUP button and then selecting
Stop battery test
.
You can start a luminaire test by selecting
Start luminaire test
. The first luminaire test will configure the
central battery system.
You can set the date and time by selecting
Set date and time
. In the clock settings, a blinking cursor
identifies a value that you can change with the +/- button. You can change the parameter whose value
you want to change by using the SETUP button. Once you have set the date and time, you can leave
the menu by pressing the SETUP button, after which the new settings will be stored in the central
battery system in a matter of few seconds.
To move back to the higher-level menu from the test log, press the SETUP button for 1.5 s.
NOTE: A battery test cannot be started unless the battery set is sufficiently charged.
Figure
10. Settings and starting a test
External USB connection
A USB port on the LCD allows data entered in a separate PC programme to be transferred to the LCD.
Using the PC programme, luminaires can be given names, along with descriptive information. Connect
the LCD to the PC using a USB cable. Once you have connected the cable to the LCD, the following
display is shown:
Figure
11. USB cable connected
Browse luminaire tests
Browse battery tests
Browse error log
Setup
Date Time Error
>23.03.11 10:30 2
23.03.11 10:32 5
22.03.11 00:15 2
Browse luminaire tests
Browse battery tests
Browse error log
Setup
Start battery test
Start luminaire test
Set date and time
Stop battery test
Start luminaire test
Set date and time
PC connected
Data transfer speed 1200
Содержание TAPSA CONTROL TKT65
Страница 37: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 37 TKT65 P cabinet construction...
Страница 38: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 38 TKT65C PP IP54 construction...
Страница 43: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 43...
Страница 44: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 44...
Страница 45: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 45...
Страница 46: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 46...
Страница 47: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 47...
Страница 48: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 48...
Страница 49: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 49...
Страница 50: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 50...
Страница 51: ...VOT 34 Rev 1 81 EN 11 12 2019 TKT65C Installation and maintenance 51...