Connecting The Control

 ---------------------------------------------------------

Make sure all power to the devices and terminal blocks is off, and remove any 
remaining jumpers from the terminals. 

Reconnect the terminal blocks to the control by carefully aligning them with their respec-
tive headers on the control and then pushing the terminal blocks into the headers. The 
terminal blocks should snap firmly into place. 

Install the supplied safety dividers between the unpowered sensor input and the pow-
ered 120 V (ac) or 24 V (ac) wiring chambers. 

Apply power to the control. The operation of the control on power up is described in the 

Sequence of Operation

 section of this brochure. 

WARM WEATHER SHUT DOWN (WWSD)  ---------------------------------------------------

 ---------------------------------------------------  

The 

WWSD

 dial is only operational when an outdoor sensor is installed. The WWSD dial

can be set from 35 to 100°F or Off (2 to 38°C or Off). Refer to section A.

Note:

 If an outdoor sensor is not installed, the 

WWSD

 dial must be set to 

Off

FREQUENCY OF ROTATION ---------------------------------------------------------------------

 ---------------------------------------------------------------------  

The 

Frequency of Rotation

 dial can be set from 12 to 168 hours or Off. Refer to section A. 

30 second Delay / 10 second Delay

 

-----------------------------------------------------------------------------------

 

The 

30 second Delay / 10 second Delay

 DIP switch is used to select what time delay is required to prove flow once a pump 

contact is turned on. Refer to section A. 

Exercising / Off

 ---------------------------------------------------------------------------------------------------------

 

The 

Exercising / Off

 DIP switch is used to select exercising. If the DIP switch is set to 

Exercising

, refer to section A. 

Alert per Pump / Alert Levels

 -----------------------------------------------------------------------------------------

 

The 

Alert per Pump / Alert Levels

 DIP switch is used to select which mode of alert operation is required. Refer to section C. 

Settings

13 14

16

15

A     A

Alert

Alert

B     B

WWSD

35

Off

70° F

 

 

100

Frequency of Rotation

12

Off

96 hours

168

48

144

2-Stage

Alert Levels

Pump

1  2

Auto

30 second Delay

Exercising
Alert per Pump

Off

10 second Delay

Off

Stand-by

DIP SWITCH SETTINGS  ----------------------------------------------------------------------------------------------------------------------------

 ----------------------------------------------------------------------------------------------------------------------------

Pump 1 Auto / Off

 -----------------------------------------------------------------

The 

Pump 1 Auto / Off

 DIP switch is used to select pump 1 operation. If the DIP switch 

is set to 

Pump 1 Auto

, refer to section B. 

 

Pump 2 Auto / Off

 ----------------------------------------------------------------

 

The 

Pump 2 Auto / Off

 DIP switch is used to select pump 2 operation. If the DIP switch 

is set to 

Pump 2 Auto

, refer to section B. 

2-Stage / Stand-by

 ---------------------------------------------------------------

The 2-Stage / Stand-by DIP switch is used to select which mode of pump control is 
required. If 2-Stage is selected, refer to section B2, and if Stand-by is selected, refer to 
section B1. 
 

Содержание Pump Sequencer 132

Страница 1: ...ms Ltd Power Pump Relays Alert Relays Demands 120 V 10 60 Hz 6VA 240 V ac 10 A 1 2 hp pilot duty 720 VA 240 V ac 10 A 1 3 hp pilot duty 240 VA 20 to 260 V ac 2 VA Signal wiring must be rated at least...

Страница 2: ...econds then the control turns on all of the red LED s for 2 seconds After this test the control enters its normal operating mode When the control is powered up the Power light remains on continuously...

Страница 3: ...trol turns on the output for 10 seconds This minimizes the possibility of a pump seizing during a long period of inactivity Note The exercising function does not work if power to the control or pumps...

Страница 4: ...ts have two modes of operation The mode of operation for the alert contacts is selected using the Alert per Pump Alert Levels DIP switch When an alert contact is activated refer to the Error Messages...

Страница 5: ...check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections as the wires will interfere with safety dividers which should b...

Страница 6: ...als 17 and 18 The outdoor sensor is used by the 132 to measure the outdoor air temperature Note If an outdoor sensor is not installed the WWSD dial must be set to Off STEP FIVE TESTING THE WIRING Each...

Страница 7: ...is off you should measure less than 5 V ac Test The Outputs Pump 1 and Pump 2 Make sure power to the terminal block is off and install a jumper between Pump 1 terminals 7 and 8 When the pump circuit...

Страница 8: ...to section A 30 second Delay 10 second Delay The 30 second Delay 10 second Delay DIP switch is used to select what time delay is required to prove flow once a pump contact is turned on Refer to sectio...

Страница 9: ...ter 10 seconds the Alert A contact is shut off Step 4 Alert B contact is turned on for 10 seconds After 10 seconds the Alert B contact is shut off ERROR HANDLING If an internal control fault occurs th...

Страница 10: ...or Short Control Internal Error Outdoor Sensor Open WWSD Off Flow Proof Signal Pump 1 Failed Pump 2 Failed Pump 1 and Pump 2 Failed Power WWSD 2 Stage Demand Flow Proof Pump Demand Power WWSD 2 Stage...

Страница 11: ...11 of 12 2010 D 132 04 10 Notes...

Страница 12: ...PTION OF THE PRODUCT ITS NON INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS AND ITS COMPLIANCE WITH OR NON VIOLATION OF ANY APPLICABLE ENVIRONMENTAL HEALTH OR SAFETY LEGISLATION THE TERM OF ANY OT...

Отзывы: