Connecting The Control
---------------------------------------------------------
Make sure all power to the devices and terminal blocks is off, and remove any
remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their respec-
tive headers on the control and then pushing the terminal blocks into the headers. The
terminal blocks should snap firmly into place.
Install the supplied safety dividers between the unpowered sensor input and the pow-
ered 120 V (ac) or 24 V (ac) wiring chambers.
Apply power to the control. The operation of the control on power up is described in the
Sequence of Operation
section of this brochure.
WARM WEATHER SHUT DOWN (WWSD) ---------------------------------------------------
---------------------------------------------------
The
WWSD
dial is only operational when an outdoor sensor is installed. The WWSD dial
can be set from 35 to 100°F or Off (2 to 38°C or Off). Refer to section A.
Note:
If an outdoor sensor is not installed, the
WWSD
dial must be set to
Off
.
FREQUENCY OF ROTATION ---------------------------------------------------------------------
---------------------------------------------------------------------
The
Frequency of Rotation
dial can be set from 12 to 168 hours or Off. Refer to section A.
30 second Delay / 10 second Delay
-----------------------------------------------------------------------------------
The
30 second Delay / 10 second Delay
DIP switch is used to select what time delay is required to prove flow once a pump
contact is turned on. Refer to section A.
Exercising / Off
---------------------------------------------------------------------------------------------------------
The
Exercising / Off
DIP switch is used to select exercising. If the DIP switch is set to
Exercising
, refer to section A.
Alert per Pump / Alert Levels
-----------------------------------------------------------------------------------------
The
Alert per Pump / Alert Levels
DIP switch is used to select which mode of alert operation is required. Refer to section C.
Settings
13 14
16
15
A A
Alert
Alert
B B
WWSD
35
Off
70° F
100
Frequency of Rotation
12
Off
96 hours
168
48
144
2-Stage
Alert Levels
Pump
1 2
Auto
30 second Delay
Exercising
Alert per Pump
Off
10 second Delay
Off
Stand-by
DIP SWITCH SETTINGS ----------------------------------------------------------------------------------------------------------------------------
----------------------------------------------------------------------------------------------------------------------------
Pump 1 Auto / Off
-----------------------------------------------------------------
The
Pump 1 Auto / Off
DIP switch is used to select pump 1 operation. If the DIP switch
is set to
Pump 1 Auto
, refer to section B.
Pump 2 Auto / Off
----------------------------------------------------------------
The
Pump 2 Auto / Off
DIP switch is used to select pump 2 operation. If the DIP switch
is set to
Pump 2 Auto
, refer to section B.
2-Stage / Stand-by
---------------------------------------------------------------
The 2-Stage / Stand-by DIP switch is used to select which mode of pump control is
required. If 2-Stage is selected, refer to section B2, and if Stand-by is selected, refer to
section B1.