How To Use The Data Brochure

Settings ............................................................Pg 8

Testing the Control .........................................Pg 9

Error Messages ...............................................Pg 10

Technical Data .................................................Pg 12

Limited Warranty ............................................Pg 12

Sequence of Operation ..................................Pg 2

 

Section A: General Operation

 ..............Pg 2

 
 

Section B: Pump Operation

 ..................Pg  3

 
 

Section C: Alert Operation

 ...................Pg 4

 
Installation .......................................................Pg  5

This brochure is organized into three main sections. They are: 1) 

Sequence of Operation

, 2) 

Installation

, 3) 

Troubleshooting

. The 

Sequence of Operation

 section has three sub-sections. We recommend reading Section A: 

General Operation

 of the 

Sequence of 

Operation

, as this contains important information on the overall operation of the control. Then read the sub-sections that apply to your 

installation. 

Table of Contents

Section A

General Operation

Page 2 - 3

Section B

Pump  Operation

Page 3 - 4

Section C

Alert Operation 

Page 4

Sequence of Operation

Section A: General Operation

POWERING UP THE CONTROL  -----------------------------------------------------------------------------------------------------------------

 -----------------------------------------------------------------------------------------------------------------

When the Pump Sequencer 132 is powered up, a software version code is displayed for 2 seconds, then the control turns on all 
of the red LED’s for 2 seconds. After this test, the control enters its normal operating mode. When the control is powered up, the 

Power

 light remains on continuously. 

OPERATION  --------------------------------------------------------------------------------------------------------------------------------------------

 --------------------------------------------------------------------------------------------------------------------------------------------

The Pump Sequencer 132 has two modes of operation. The 132 is capable of operating two pumps in either a stand-by or 2-stage 
configuration. 

Stand-by

 ----------------------------------------------------------------------------------------------------------------

 

In the stand-by mode of operation the 132 automatically switches over from the lead pump to the stand-by pump if the lead pump 
fails to provide flow in the system. 
 

2-Stage 

 -----------------------------------------------------------------------------------------------------------------

 

In the 2-stage mode of operation the 132 turns on the second stage pump if there is a requirement for additional flow in the 
system. At the same time the control still provides stand-by pump operation. 

PUMP DEMAND  --------------------------------------------------------------------------------------

 --------------------------------------------------------------------------------------

A pump demand is required in order for the 132 to provide flow. A pump demand is gener-
ated by applying a voltage between 24 and 240 V (ac) across the 

Pump Demand

 terminals 

(1 and 2). Once voltage is applied, the 

Pump Demand

 light is turned on and the pump(s) 

operate as required. A pump demand can be permanently powered, or generated from an 
external source such as a manual switch or another control system. 
 

1

2

Pump

Demand

24 to 240 V (ac)

Содержание Pump Sequencer 132

Страница 1: ...ms Ltd Power Pump Relays Alert Relays Demands 120 V 10 60 Hz 6VA 240 V ac 10 A 1 2 hp pilot duty 720 VA 240 V ac 10 A 1 3 hp pilot duty 240 VA 20 to 260 V ac 2 VA Signal wiring must be rated at least...

Страница 2: ...econds then the control turns on all of the red LED s for 2 seconds After this test the control enters its normal operating mode When the control is powered up the Power light remains on continuously...

Страница 3: ...trol turns on the output for 10 seconds This minimizes the possibility of a pump seizing during a long period of inactivity Note The exercising function does not work if power to the control or pumps...

Страница 4: ...ts have two modes of operation The mode of operation for the alert contacts is selected using the Alert per Pump Alert Levels DIP switch When an alert contact is activated refer to the Error Messages...

Страница 5: ...check the wiring diagram and select those sections of the chamber with common voltages Do not allow the wiring to cross between sections as the wires will interfere with safety dividers which should b...

Страница 6: ...als 17 and 18 The outdoor sensor is used by the 132 to measure the outdoor air temperature Note If an outdoor sensor is not installed the WWSD dial must be set to Off STEP FIVE TESTING THE WIRING Each...

Страница 7: ...is off you should measure less than 5 V ac Test The Outputs Pump 1 and Pump 2 Make sure power to the terminal block is off and install a jumper between Pump 1 terminals 7 and 8 When the pump circuit...

Страница 8: ...to section A 30 second Delay 10 second Delay The 30 second Delay 10 second Delay DIP switch is used to select what time delay is required to prove flow once a pump contact is turned on Refer to sectio...

Страница 9: ...ter 10 seconds the Alert A contact is shut off Step 4 Alert B contact is turned on for 10 seconds After 10 seconds the Alert B contact is shut off ERROR HANDLING If an internal control fault occurs th...

Страница 10: ...or Short Control Internal Error Outdoor Sensor Open WWSD Off Flow Proof Signal Pump 1 Failed Pump 2 Failed Pump 1 and Pump 2 Failed Power WWSD 2 Stage Demand Flow Proof Pump Demand Power WWSD 2 Stage...

Страница 11: ...11 of 12 2010 D 132 04 10 Notes...

Страница 12: ...PTION OF THE PRODUCT ITS NON INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS AND ITS COMPLIANCE WITH OR NON VIOLATION OF ANY APPLICABLE ENVIRONMENTAL HEALTH OR SAFETY LEGISLATION THE TERM OF ANY OT...

Отзывы: