If the thermostat operates a thermal motor (wax actuator) zone valve, set the Heat 
Supply Pump Delay setting to On. This provides a three minute delay to allow the 
zone valve to open before the primary or mix pump is turned on.
In special applications with multiple zoning manifolds, the Heat Supply Pump setting 
can be set to Off. This allows a Zone Group Pump located on the Zone Manager, 
or Wiring Center to operate the pump for the manifold.

DHW Tank Priority

 ---------------------------------------------------

 ---------------------------------------------------

When a tekmarNet

®

 reset control is heating an indirect Domestic Hot Water (DHW) 

tank, the thermostat may shut off the heating zones to allow the DHW tank to recover 
quickly. This is determined by the DHW priority of the tekmarNet

®

 reset control.

Warm Weather Shut Down

 

--------------------------------------------

 

--------------------------------------------

When the outdoor air temperature exceeds the Warm Weather Shut Down (WWSD) 
setting on the tekmarNet

®

 reset control, the heating system is shut off.

Air Group Operation

Section B

In order to prevent heating and cooling at the same time, this thermostat can operate 
together with other thermostats on a tekmarNet

®

 system to form an air group.

In an air group, one thermostat is assigned as the air group master. The air group 
master operates the cooling equipment for the group. This thermostat can be set 
to be a member of the air group.
When operating as an air group, the air temperature readings of all the air group 
member thermostats are communicated to the air group master and a temperature 
average is determined.
When the air group master is in cooling 
operation, the air group member thermostats 
do not operate the heating system for air 
heating.
If the Set Room Heat temperature is adjusted 
while the air group is cooling, the snowflake 
icon is flashed to alert the user that the cooling 
is presently on. Once the cooling shuts off, 
the heating can start operation.

Air Group

Master

Member

Member

tekmarNet Communication

Floor Cooling

Section C

The thermostat has the option to support radiant floor cooling when connected to a 
heat pump control using tekmarNet

®

 communication. The floor cooling setting must 

be set to On and the heating system must be in Warm Weather Shut Down (WWSD). 
When the heat pump system control operates in cooling mode, all thermostats set for 
floor cooling on the tekmarNet

®

 bus all activate the first stage heating contact (H1) 

at the same time to allow chilled water into the system. The thermostat continues 
to operate the cooling until either the room temperature reaches the Set Heat 
temperature plus 3°F (Set Heat+1.5°C) or reaches a minimum temperature of 74°F. 
If only a floor sensor is installed, the floor cooling setpoint is 67°F (19.5°C).

Содержание D528

Страница 1: ...ating Cycle tN2 Communication compatible Room temperature limiting Requires 2 Wires Pulse Width Modulation CSA C US Approved for use in USA and Canada Outdoor Temperature Display Air Group Member Back...

Страница 2: ...ng the Thermostat Wiring 5 Mounting the Thermostat 5 Cleaning the Thermostat 6 Switch Settings 6 User Interface 7 Display 7 Button Operation 7 Symbols Description 7 Settings 8 14 Sequence of Operation...

Страница 3: ...f wire is 1000 feet 300 m Strip wire to 3 8 10 mm for all terminal connections Use standard 18 AWG wire for the tN2 connections Installation Location Removing The Thermostat Base Push tab 1 Remove the...

Страница 4: ...mmunication are provided to the thermostat by connecting the tN2 terminals on the thermostat to the tN2 terminals on a tN2 Wiring Center House Control Zone Manager or Expansion Module tN2 terminals ar...

Страница 5: ...g Center or Zone Manager If the thermostat display remains permanently on there may be a fault with the previously tried zone on the House Control Wiring Center or Zone Manager If the thermostat displ...

Страница 6: ...setback schedule 2 ON SCENE The thermostat responds to changes in the scene system wide manual overrides Requires the installation of a User Switch 479 to use this feature OFF OFF The thermostat does...

Страница 7: ...GROUP The air group is cooling Heating can start once the cooling is finished LOCK Locked to User access level CLOCK Operating on a programmable schedule tekmarNet Communication is present WARNING SYM...

Страница 8: ...ler SET ROOM HEAT AWAY Set the room heating temperature while in the Away scene Continued on next page Press and hold down both the and buttons for 2 seconds to change from one step to the next Releas...

Страница 9: ...ng in the Adjust menu is set to Off 40 to 122 F 4 5 to 50 0 C Default 65 F 18 5 C Installer User SET FLOOR HEAT Set the floor heating temperature while in the event Available when A slab sensor is ins...

Страница 10: ...rge number with Software Version upper right corner and the thermostat address 40 to 95 F 4 5 to 35 0 C Default 85 F 29 5 C Installer MAXIMUM SET ROOM HEAT Set the maximum room heating limit while in...

Страница 11: ...n AND A slab sensor is installed on the auxiliary sensor input AND Sensor setting in the Adjust menu is set to Floor Off 40 to 122 F Off 4 5 to 50 0 C Default Off Installer User SET FLOOR MINIMUM Set...

Страница 12: ...liary sensor input AND Sensor setting in the Adjust menu is set to Floor 1 2 3 4 Default 1 Installer SCHEDULE Thermostat can follow schedule master 1 2 3 or 4 Available when Switch setting 1 is set to...

Страница 13: ...e tekmarNet system Choose Synchronize when zone heated using a boiler Choose Auto when zone is non hydronic heating Available when No reset control on the tekmarNet system ADJUST ADJUST OFF 1 to 16 In...

Страница 14: ...t control mixing Installer tekmarNet ADDRESS The address is shown in the large number field Auto is shown in the upper number field when using automatic addressing Press the or the button to manually...

Страница 15: ...the thermostat is heating The heat can cycle on and off within 1 5 F 1 C of the Set Room Heat temperature Freeze Protection The thermostat operates the heat whenever the room or floor temperature fall...

Страница 16: ...r the group This thermostat can be set to be a member of the air group When operating as an air group the air temperature readings of all the air group member thermostats are communicated to the air g...

Страница 17: ...e Display Room Temperature Setting 1 or or Follows programmable schedule or operates at the occupied temperature 2 Away Away temperature 3 Unoccupied temperature Scenes System Override Section E When...

Страница 18: ...il all settings have been reviewed PORT ERROR Thermostat has been connected to a tN2 Zone already in use by a 2 stage device A 2 stage device requires two tN2 ports to operate This device may be conne...

Страница 19: ...ears automatically once this thermostat is given a new manually set address or if the thermostat is set to automatic addressing ROOM SENSOR SHORT CIRCUIT The built in air temperature sensor has a shor...

Страница 20: ...r sensor fault is corrected FLOOR SENSOR OPEN CIRCUIT The auxiliary floor sensor has an open circuit Check for loose or damaged wires Locate and repair the problem as described in the Data Brochure D0...

Страница 21: ...CIRCUIT The auxiliary room sensor has a short circuit Check for damaged wires Locate and repair the problem as described in the Data Brochure D 076 D077 or D084 Error clears after the auxiliary room...

Страница 22: ...arly so that the room is comfortable at the scheduled time Pressing button does not increase temperature Flashing Max Installer can increase the Maximum Set Room Heat Flashing Floor Max Floor temperat...

Страница 23: ...o 50 C RH max 80 up to 88 F 31 C decreasing linearly to 50 RH at 104 F 40 C Altitude 0 6560 feet 2000 m Installation Category II Pollution Category 2 Power supply Provided by tekmarNet 2 Control 1 3 V...

Страница 24: ...s not cover the cost of the parts or labor to remove or transport the defec tive Product or to reinstall the repaired or replacement Product all such costs and expenses being subject to Purchaser s ag...

Отзывы: