1592006207 XB570L GB r1.1 26.08.2015
XB570L
18
15. TTL SERIAL LINE
The TTL connector allows, by means of the external module TTL/RS485, to connect the unit to a network
line
ModBUS-RTU
compatible as the Dixell monitoring system.
The same TTL connector is used to upload and download the parameter list of the
“HOT KEY”
.
16. USE OF THE PROGRAMMING “HOT KEY “
The Wing units can UPLOAD or DOWNLOAD the parameter list from its own E2 internal memory to the
“Hot
Key”
and vice-versa.
1.
Turn OFF the instrument by means of the ON/OFF key, remove the TTL serial cable if present, insert
the
“Hot Key”
and then turn the Wing ON.
2.
Automatically the parameter list of the
“Hot Key”
is downloaded into the Wing memory, the
“DoL”
message is blinking. After 10 seconds the instrument will restart working with the new parameters.
3.
Turn OFF the instrument, remove the
“Hot Key”,
plug in the TTL serial cable and then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
-
End
for right programming. The instrument starts regularly with the new programming.
-
Err
for failed programming. In this case turn the unit off and then on if you want to restart the
download again or remove the
“Hot key”
to abort the operation.
1.
Turn OFF the instrument by means of the ON/OFF key and remove the TTL serial cable if present; then
turn it ON again.
2.
When the unit is ON, insert the
“Hot Key”
and push the
UP
key; the
“UPL”
message will appear.
3.
Push
SET
key to start the UPLOAD; the
“UPL”
message will start blinking.
4.
Turn OFF the instrument, remove the
“Hot Key”
, plug in the TTL serial cable and then turn it ON
again.
At the end of the data transfer phase the instrument displays the following messages:
-
End
for right programming. The instrument starts regularly with the new programming.
-
Err
for failed programming. In this case turn the unit off and then on if you want to restart the
download again or remove the
“Hot key”
to abort the operation.
17. ALARM SIGNALS
Mess.
Cause
Outputs
EE
Data or memory failure
Alarm output ON. Other outputs unchanged
rPF
Thermostat Probe failure
Alarm output ON. Compressor output according to parameters Con and CoF
EPF
Evaporator Probe failure
Alarm output ON. Defrost termination is timed. No temperature control on fans.
i1P i2P i3P
Insert probe 1, 2, 3, failure
Alarm output ON. Other outputs unchanged. The cycle is made by time
rtC
Real Time Clock data lost
Alarm output ON. Other outputs unchanged.
rtF
Real Time Clock failure
Alarm output ON. Other outputs unchanged. The date and the duration of the
cycle are not available.
HA
Maximum temperature alarm
Alarm output ON. Other outputs unchanged.
LA
Minimum temperature alarm
Alarm output ON. Other outputs unchanged.
FF
Fast freezing interrupted by
short power failure
Alarm output ON. The freezing cycle restart from the same point at which was
interrupted.
PFA
Fast freezing interrupted by long
power failure
Alarm output ON. The freezing cycle restart from the current phase.
OCF
Max duration of the cycle is
expired
Alarm output ON. Other outputs unchanged. In any case the cycle ends when the
final temperature is reached
EA
External alarm
Alarm output ON. Other outputs unchanged.
CA
Serious external alarm
Alarm output ON. Other outputs OFF.
dA
Door open alarm
Alarm output ON. Other outputs unchanged.
16.1 DOWNLOAD (FROM THE “HOT KEY” TO THE INSTRUMENT)
16.2 UPLOAD (FROM THE INSTRUMENT TO THE “HOT KEY”)
Содержание BLC10
Страница 1: ...BLAST CHILLER FREEZER User Manual PT SL 49 61 EN FR IT ES 3 13 25 37...
Страница 2: ...2...
Страница 9: ...9 QUICK GUIDE For the daily use...
Страница 13: ...REFROIDISSEURS CONG LATEURS RAPIDES Manuel d utilisation PT SL 49 61 FR IT ES 13 25 37...
Страница 14: ...14...
Страница 21: ...21 GUIDE RAPIDE Guide rapide quotidien...
Страница 25: ...ABBATTITORI CONGELATORI Manuale d uso PT SL 49 61 IT ES 25 37...
Страница 26: ...26...
Страница 33: ...33 33 GUIDA RAPIDA Guida pratica quotidiana...
Страница 37: ...ABATIDORES CONGELADORES Manual del usuario PT SL 49 61 ES 37...
Страница 38: ...38...
Страница 45: ...45 GU A R PIDA Gu a r pida diaria...
Страница 49: ...PT SL 49 61 ABATEDORES DE TEMPERATURA CONGELADORES Manual do utilizador...
Страница 50: ...50...
Страница 57: ...57 GUIA R PIDO Guia r pido di rio...
Страница 61: ...SL 61 HLADILNIK ZAMRZOVALNIKA ZA HITRO HLAJENJE ZAMRZOVANJE Navodila za uporabo...
Страница 62: ...62...
Страница 69: ...69 HITRI VODNIK Za dnevno uporabo...
Страница 73: ...1592006207 XB570L GB r1 1 26 08 2015 XB570L 2 20 XB590L XB570L...
Страница 94: ...1593006207 XB570L FR r1 0 26 08 2015 XB570L 2 24 XB590L XB570L...
Страница 118: ...1591006207 XB570L IT r1 1 26 08 2015 XB570L 2 24 XB590L XB570L...
Страница 141: ...1591006207 XB570L IT r1 1 26 08 2015 XB570L 25 24...
Страница 142: ...1594006207 XB570L SP r1 0 26 08 2015 XB570L 2 20 XB590L XB570L...
Страница 162: ...XB590L XB570L...
Страница 177: ...1592006207 XB570L GB r1 1 26 08 2015 XB570L 16 20 3 12 2 MONTAGEM...
Страница 184: ...1592006207 XB570L GB r1 1 26 08 2015 XB570L 2 20 XB590L XB570L...