The OFF threshold of the FANS is displayed
Default 60°C
20
Set the desired threshold
21
HFN is displayed
Cyclical test of the fans for 5
minutes every "n" hours
22
Display 000
Default 000= function disabled
23
Set the desired number of hours
Default 000
24
FCD <> "datum" is displayed
Fault due to quick temperature
increase (°C/sec) Default NO
25
Set the desired value (see page 19)
Default no "function excluded"
26
FPS <> "datum" is displayed
Fault due to quick pressure
increase (mbar/sec) Default NO
27
Set the desired value (see page 19)
Default no "function excluded"
28
ADR <> "datum" is displayed
Modbus address Default 001
29
Set the desired address
From 1 to 255
30
BDR <> "datum" is displayed
Modbus transmission speed
Default 9.6 Kb/s
31
Set the desired speed
From 2.4 Kb/s to 38.4 Kb/s
32
PAR <> "datum" is displayed
Parity bit selection
Default NO
33
Set the desired speed
None (No), Even (EVE), Odd
(ODD)
34
END is displayed
End of programming
35
Storing the settings and exiting programming
Err: incorrect programming of
the LED values (note 2)
36
Return to step 1
1) It is possible to go back to the previous step by pressing the MODE button.
2) If, when pressing ENT, "Err" is displayed, it means that one of the following errors have been made:
ALARM ≥ TRIP or FAN-OFF ≥ FAN-ON. Press PRG to go back to step 1 and correct the data.
3) After 1 minute's keyboard inactivity programming is abandoned without saving the data.
4) At the end of programming the FAULT relay is disabled till the control unit is restarted.
5) During programming the control unit does not control/protect the monitored machine.