NOTES ON THE FCD FUNCTION

 

 

The NT series equipment boasts an innovative control function combined with the dynamic status of the Pt100 sensor 
inside the TPL503. 

 

Activating FCD, the control unit analyses the increase in temperature ∆T (*) recorded in a second (

°C/sec

). 

 

Enabling the function, the user can select the value (∆T) from a minimum of 1°C/sec (2°F) to a maximum of 30°C/ sec. 
(54°F). If the value sensed is higher than the value set by the user, the control unit inhibits the possible activation of the 
ALARM and TRIP alarms and switches the FAULT relay (7-8-9), displaying the message 

"Fcd fault".

 

 

Example: if we set the function to 5°C, FAULT for FCD will switch only if the control unit senses an increase in ∆T of 
over 5°C in a second on the monitored system. 

 

Setting "no" disables the FCD function. 

 

When a channel is in FAULT for FCD, the Alarm and Trip warnings are inhibited; therefore only the quick temperature 
increase is highlighted. 

Press Reset to delete the FCD warnings on all channels and reset the FAULT relay. 

Possible FCD applications

 

 

Identification of a possible induced disturbance on the sensor line

 

If the installation instructions are not complied with (see TPL503 connections on page 15), any disturbance on the Pt100 
sensor line may cause false readings or anomalous alarms.  

Setting the FCD function in a temperature range of between 1°C and 10°C (5°C recommended), the effects caused by 
false readings can be suppressed and the alarm relay activation can be prevented, as shown above. 

Corrective  actions:  check  the  installation  of  the  sensor  extension  cable  is  in  line  with  the  instructions  given  in  the 
paragraph on the TPL503 connections on page 15. 

 

Identification of a sensor fault or faulty connection

 

In case of a faulty connection or sensor fault, a quick positive or negative variation in temperature might occur, leading 
to the system tripping or the alarms of the monitored system to be triggered. 

In this specific case we recommend the FCD function to be set in a temperature range of between 10°C and 20°C. 

 

(*) 

The ΔT value shows the temperature range for each second.

 

 

NOTES ON THE FPS FUNCTION

 

 

Activating the FPS function it is possible to monitor quick increases in pressure. 

 

If the pressure exceeds the set value in a second, the FAULT relay switches and FPS is displayed on the pressure 
channel. 

 

This increase can be set in steps of 10 mbar up to a maximum of 200 mbar. 

 

Sensitivity is controlled by the value set, setting "no" disables the FPS function. Excessively low values might cause 
warnings too often, while excessively high values would do the opposite. 

 

In case of FPS, the relative Alarm and Trip thresholds are always monitored. Press Reset to delete the FPS warnings 

and reset the FAULT relay. 

                ATTENTION:  
  
 

We recommend you check the control unit before starting the device. 
  
The default parameters set by TECSYSTEM might not suit your requirements.    
  
Programming the device is the end user’s responsibility: the set alarm thresholds and the 
enabled functions described in this manual must be checked (by a specialized technician) 
referring  them  to  the  application  and  system  characteristics  on  which  the control  unit  is 
installed. 

 

Содержание NT210 K

Страница 1: ...ISO9001 2008 certified quality system http www tecsystem it R 1 5 31 01 18 Translations of the original instructions TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 NT210 K TPL503...

Страница 2: ...TY REQUIREMENTS 4 2 ACCESSORIES 5 3 TECHNICAL SPECIFICATIONS 6 4 TPL503 SENSOR INSTALLATION PROCEDURE 8 5 FRONT PANEL 10 DISPLAY 11 CHECKING THE WORK PROGRAM LED TEST ALARM RELAY TEST ALARM RELAY SILE...

Страница 3: ...ORK RS485 ELECTRICAL CONNECTIONS DATA FRAME DATA PACKET FUNCTION CODE 21 CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERROR CODES exception code POLLING FREQUENCY MODBUS MAPPING TABLE 22 CRC CALC...

Страница 4: ...exceeding 90 and never touch with wet or humid hands during storms If any liquid penetrates the control unit disconnect it immediately and contact technical service CLEANING Disconnect the power cabl...

Страница 5: ...itch 5 Code 2PL0359 Screws tightening torque 0 5Nm 1 RS485 terminal 3 poles pitch 3 81 Code 2PL0366 Screws tightening torque 0 25Nm 1 TPL503 sensor Tecsybus terminal 4 poles pitch 3 81 Code 2PL0368 Sc...

Страница 6: ...h 131mm terminal block included Hole 92 x 92 mm TEST AND PERFORMANCE Construction in compliance with CE regulations Protection from electrical interference EN 61000 4 4 Dielectric strength 1500 Vac fo...

Страница 7: ...temperature and pressure memory recorded since the last reset Front alarm reset button Sensor fault diagnostics FLT TPL503 TECHNICAL SPECIFICATIONS TPL503 POWER SUPPLY Direct connection to the Power...

Страница 8: ...e from welding or painting residue and perfectly clean The cork rubber gasket TPL base must adhere fully to the support surface note replace the gasket every time it is removed to the TPL base NECESSA...

Страница 9: ...air is released Attention bleeding must be carried out taking into consideration the transformer operating conditions with the transformer switched off and a temperature of about 20 C or ambient the i...

Страница 10: ...7 FAN warning green LED 6 FAULT warning red LED 18 T P L alarm activation AL1 red LED 7 RS communication TPL503 green LED 19 T P L alarm activation AL2 red LED 8 Scanning mode selection button 20 T ma...

Страница 11: ...are tested regularly For this operation press the TEST button briefly all the displays light up for 2 seconds ALARM RELAY TEST This function allows carrying out a test of the relay operation without...

Страница 12: ...t 2 1 3 1MN0007 REV 0 1 Control unit 2 Panel hole dimensions 0 8mm tolerance 3 Identification label Fix the unit securely with the blocks supplied 1 2 3 4 1MN0008 REV 0 1 Control unit 3 Fixing screw 2...

Страница 13: ...nector connection colours 1 RS white 2 PWL brown 3 PWL black 4 RS Blue Note with the power to the unit ON the FAULT relay switches contacts 8 9 open NO and 7 9 closed NC read paragraph ALARMS AND VENT...

Страница 14: ...esholds are exceeded The FAULT relay switches when the unit is powered contacts 7 9 closed NC and 8 9 open NO and holds till one of the following events takes place Data storage fault Ech message TPL5...

Страница 15: ...alteration of the programmed data at start up Ech is displayed with the relative warning of the Fault contact In this case for safety reasons the default parameters are loaded automatically see the pr...

Страница 16: ...ds until the control unit is reset This operation will allow compensating for any reading tolerances due to differences in altitude or transformer filling pressure For the system to be operating corre...

Страница 17: ...old is displayed 6 Set the desired threshold Default 100mbar 7 The pressure TRIP AL2 threshold is displayed 8 Set the desired threshold Default 200mbar 9 The level gas ALARM AL1 threshold is displayed...

Страница 18: ...d Modbus transmission speed Default 9 6 Kb s 31 Set the desired speed From 2 4 Kb s to 38 4 Kb s 32 PAR datum is displayed Parity bit selection Default NO 33 Set the desired speed None No Even EVE Odd...

Страница 19: ...evented as shown above Corrective actions check the installation of the sensor extension cable is in line with the instructions given in the paragraph on the TPL503 connections on page 15 Identificati...

Страница 20: ...emperature reading mode while it is inactive when it is in the following modes display programming and relay test RS485 ELECTRICAL CONNECTIONS As to the signal cable to use in order to guarantee corre...

Страница 21: ...00 17 00 18 00 24 The same must be remembered for the Trip thresholds registers 00 25 00 26 00 32 and for each quantity measured Temperature Pressure Level Note the Alarm level thresholds must be prog...

Страница 22: ...er 1 2 3 see level indication page 16 00 05 00 TPL503 sensor temperature Holding register Temperature Range 40 120 DATA LO 50 10 00 06 00 Not used Holding register 00 07 00 Oil pressure Holding regist...

Страница 23: ...ster 00 14 00 Not used Holding register 00 15 00 Not used Holding register 00 16 00 Not used Holding register 00 17 00 Oil Temperature Set Alarm Holding register C 00 18 00 Oil Pressure HI Set Alarm H...

Страница 24: ...bled 00 29 00 Oil pressure Trip Holding register mbar 10 00 30 00 Not used Holding register 00 31 00 Not used Holding register 00 32 00 Not used Holding register 00 33 00 Hfn Holding register See page...

Страница 25: ...45 00 Oil Temperature alarm history Holding register See note 2 on page 28 00 46 00 Oil Pressure alarm history Holding register 00 47 00 Oil Level alarm history Holding register 00 48 00 Not used Hold...

Страница 26: ...olding register 00 60 00 Not used Holding register 00 61 00 Not used Holding register 00 62 00 Not used Holding register 00 63 00 Not used Holding register 00 64 00 Not used Holding register 00 65 00...

Страница 27: ...00 Not used Holding register 00 80 00 Not used Holding register NOTE 1 STATUS REGISTER The status register contains information on the status of the alarms of the channel it refers to Each bit repres...

Страница 28: ...NOTE 3 GENERAL FLAG REGISTER The general function register contains information on the enabling of general functions FLG_GEN GENERAL FLAGS B7 B6 B5 B4 B3 B2 B1 B0 FREE PRES DEP FREE SYSTEM FLAG ECH E...

Страница 29: ...bytes in the packet excluding the 2 of the CRC G Polynomial 1010 0000 0000 0001 shr shift to the right ALGORHITHM 1 0xFFFF A 2 0 i 3 0 j 4 Di AL AL 5 j 1 j 6 shr A 7 if carry then G A A 8 if NOT j 8...

Страница 30: ...roblem persists European directives 2012 19 EC WEEE and 2011 65 EC RoHS have been approved to reduce electrical and electronic waste and promote the recycling and reuse of the materials and components...

Отзывы: