TECSYSTEM FO 935 Скачать руководство пользователя страница 22

22 

FO 935

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

OUTPUT RS485 MODBUS 

INTRODUCTION TO THE MODBUS INSIDE MODULE 

  

The  MODBUS  INSIDE  expansion  module  is  built  in  the  monitoring  unit  and  allows  data  transfer  on  a  RS485  line  with 
MODBUS RTU protocol, maximum 32 devices. 

 

OPERATING NOTES 

 

  

For the module to work correctly, it is necessary to set the RS485 network set-up parameters: address, baud rate, parity 
bit. 
See programming steps 32 to 37 on page 20. 
The serial communication of the temperature control monitoring unit is active only when the FO 935 D is in temperature 
control mode in one of the intended modes (Scan, Auto, Man and T.Max). 
When  other  functions  such  as  programming,  programming  display  and  relay  test  are  activated,  the  ModBus 
communication is temporarily deactivated. 
 

  

DATA TRANSMISSION ON MODBUS NETWORK 

 

  

The internal MODBUS INSIDE module is used to connect the FO 935 D control unit to an RS485 network with Modbus 
RTU protocol in order to read the data indicated in the modbus table, page. 25, and to be able to write those indicated in 
the notes section for remote programming, the module is always in slave mode. 
The FO 935 D control unit is in communication with the network only when it is in temperature reading mode, while it is 
inactive when in the following modes: display, programming and test relays. 
  

RS485 ELECTRICAL CONNECTIONS 

 

  

As far as the signal cable to be used in order to ensure the correct network operation is concerned, we recommend you 
follow the provisions of the EIA RS485 standard which suggests using a 24AWG twisted pair.

 

The twisted pair that connects units in RS485 might need a 120 ohm end resistor on the last unit of the series. 
Connect the twisted pair paying attention to polarities and lay the network avoiding to make sharp bends or ring windings 
in order not to modify line impedance. If necessary, the GND terminal for grounding is also available. 
Always position the RS485 twisted pair far from power cables. 

 

  

  
  
  
  
  
  
  
  
  
  
DATA FRAME 

 

  

The frame in asynchronous transmission consists of:1 start bit, 8 data bits, 1 parity bit (even or odd, if the parity has been 
set) and 1 stop bit. 
With parity NO (none) it is possible to select N-1 (1 stop bit) or N-2 (2 stop bit). 
The permitted baud rates are:2400, 4800, 9600, 19200 and 38400. 
If not otherwise specified, the word length (DATA) is 16 bits. 

  

DATA PACKET

 

  

A complete request/response sequence is composed as follows: 
  
Master's request: 
  
SLAVE ADDRESS   

- 1 byte 

FUNCTION CODE   

- 1 byte 

DATA 

 

                 - variable, depends on the function code 

CRC 

 

 

 - 2 byte 

  
Slave request: 
  
SLAVE ADDRESS   

- 1 byte 

FUNCTION CODE   

- 1 byte 

DATA 

 

 

- variable, depends on the function code 

CRC 

 

 

 - 2 byte 

  

  
 

1MN0095 REV.0 

(ONLY FO 935 D VERSION) 

Содержание FO 935

Страница 1: ...s with ISO9001 certified quality system http www tecsystem it R 1 1 12 01 22 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 FO 93...

Страница 2: ...NCENTRATOR OPERATION 13 6 FO 935 ASSEMBLY 14 7 ELECTRICAL CONNECTIONS 15 FO 935 BASIC BACK FO 935 D BACK POWER SUPPLY 16 ALARMS AND VENTILATION 17 FAULT AND RESET MESSAGE SEQUENCE SENSOR DIAGNOSTICS C...

Страница 3: ...THE MODBUS INSIDE MODULE OPERATING NOTES DATA TRANSMISSION ON MODBUS NETWORK RS485 ELECTRICAL CONNECTIONS DATA FRAME DATA PACKET FUNCTION CODE 23 CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERR...

Страница 4: ...90 and never touch with wet or damp hands If any liquid penetrates the control unit disconnect it immediately and contact technical assistance CLEANING Disconnect the power cable before cleaning the...

Страница 5: ...ews tightening torque 0 25Nm 1 Terminal 3 pitch poles 3 81 RS485 Code 2PL0366 Screws tightening torque 0 25Nm Only for version D CFO 521 Concentrator CFO 521 Concentrator Start guide and QR code 2 Ter...

Страница 6: ...n removable terminal boards OUTPUTS 2 alarm relays ALARM AND TRIP SPDT 1 relay for faulty probes or operating anomaly FAULT SPST 2 ventilation management relays SPST FAN1 and FAN2 Output relays with 1...

Страница 7: ...3 digits to display temperatures messages and channels 3 LEDs to display the state of the alarms of the selected channel ALARM TRIP FAULT 4 LEDS selection of display mode SCAN AUTO MAN T MAX 2 LEDs t...

Страница 8: ...5 C to 60 C Permitted humidity 90 without condensate Degree of protection IP00 PC UL 94 HB container Electronic part protective treatment Optional DIMENSIONS 145x106 7x55mm Concentrator fixing bracket...

Страница 9: ...S green LED ONLY FO 935 D 5 FAULT signalling red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode se...

Страница 10: ...meters listed in the programming paragraph on pages 19 20 return the control unit to TECSYSTEM for repairs 3 TEC err this message appears when a loss of communication is detected between the thermomet...

Страница 11: ...ture of the concentrator ranges from 25 C to 60 C therefore ensure there is adequate space between the concentrator and the transformer Maximum humidity 90 non condensing The CFO 521 support bracket c...

Страница 12: ...ply the protection bracket using the M4 screws supplied FO FIBRE OPTIC TEMPERATURE SENSOR DIMENSIONS INSTALLATION READING POINT ST CONNECTOR CONNECTION OF THE CONC CFO 521 TO THE FO 935 CONTROL UNIT F...

Страница 13: ...rrect interpretation of the measured values it is advisable to combine the CH2 probe with the central phase V The CFO 521 concentrator has a Pt100 input RTD class A 2 3 wire probe for the possible con...

Страница 14: ...Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Fixing screws 2 Fixing blocks 4 Cross head screwdriver 1X100mm FO 935 ASSEMBLY 1 2 3 4 1MN0008 REV 0 Dril...

Страница 15: ...2 3 1 2 3 4 1 Power supply 85 260Vdc ac 50 60Hz 3 FO IN bus input for connection to the CFO 521 2 Relay ALARM TRIP FAULT FAN1 FAN2 4 RS485 Modbus Inside RTU output 1 Power supply 85 260Vdc ac 50 60Hz...

Страница 16: ...y high intensity overvoltages These problems occur if the main switch is closed and the transformer does not have the load no load test The above is much more evident when the 220 Vac voltage is taken...

Страница 17: ...e 18 NOTE always disconnect the unit before performing any electrical connections eeprom fault concentrator communication bus fault min temperature full scale exceeded max temperature full scale excee...

Страница 18: ...FAN1 and FAN2 and if programmed correctly can control the fans switching ON and OFF to cool the transformer The FAN1 and FAN2 contacts can manage cooling the transformer and the room where it is insta...

Страница 19: ...e display shows CH4 Enabling CH4 9 Select YES or NO with YES the CH4 is enabled with NO the CH4 is disabled 10 The ALARM threshold for CH4 appears and the Alarm LED flashes If CH4 NO jump to step 16 D...

Страница 20: ...played Blinking TRIP LED 29 Select YES or NO Default NO 30 FLS FAULT is displayed Blinking FAULT LED 31 Select YES or NO Default YES For version FO 935 BASIC skip to step 38 32 ADR datum is displayed...

Страница 21: ...ALARM TRIP and FAULT relays programming steps from 26 to 31 page 20 Selecting the YES NO setting introduces the Fail Safe and No Fail Safe functions ALARM AND TRIP By setting NO NO Fail safe the norma...

Страница 22: ...is inactive when in the following modes display programming and test relays RS485 ELECTRICAL CONNECTIONS As far as the signal cable to be used in order to ensure the correct network operation is conc...

Страница 23: ...t affecting the received message Also in the remote programming phase via ModBus it must be considered that the Alarm thresholds must be lower than the Trip thresholds and that the Fan on thresholds m...

Страница 24: ...to ModBus reading the register 7 NO ERROR CH_1 Trip Alarm CH_4 Trip Alarm FAN_1 ON OFF FAN_2 ON OFF Value HFN max see table SYSTEM Setting and Status CONTROL UNIT GENERAL NOTES The various models of t...

Страница 25: ...ASCII R 5 Qty channels 2 ASCII R 6 Options see notes Options see notes R 7 00 Incorrect datum received R see tab 8 00 Info various causes R see tab 9 00 Controls W see tab SYSTEM Setting and Status Ad...

Страница 26: ...sign 2 compl Ch1 temper alarm set point 1 C 190 C AL RW 28 2 compl sign 2 compl Ch1 temper trip set point 1 C 190 C TRP RW 29 2 compl sign 2 compl Ch2 temper 35 C 195 C R 30 2 compl sign 2 compl Ch2...

Страница 27: ...per 35 C 195 C R 38 2 compl sign 2 compl Ch4 max temperat 0 C 195 C R 39 2 compl sign 2 compl Ch4 temper alarm set point 1 C 190 C AL RW 40 2 compl sign 2 compl Ch4 temper trip set point 1 C 190 C TRP...

Страница 28: ...Ch4 Setting See Notes CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R CHANNELS 1 4 Status Address LO 10 Data HI Data LO Notes 1 Notes 2 W write W write W read write 65 Ch1 story Ch1 status See Not...

Страница 29: ...TUS CHn STORY BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 TRIP ALARM FLT FOC FCC RELAY STATUS coil energising status BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 FAULT Relay 1 ON TRIP Relay 1 O...

Страница 30: ...normal domestic waste Returning of used electrical appliances contact TECSYSTEM or the TECSYSTEM agent to receive information on correct disposal of the appliances TECSYSTEM is aware of the impact it...

Страница 31: ...31 FO 935 TECHNICAL INFORMATION ufficiotecnico tecsystem it COMMERCIAL INFORMATION info tecsystem it USEFUL CONTACTS...

Отзывы: