![TECSYSTEM FO 935 Скачать руководство пользователя страница 19](http://html1.mh-extra.com/html/tecsystem/fo-935/fo-935_instruction-manual_1072991019.webp)
19
FO 935
STEP
PRESS
EFFECT
PRESS
NOTES
1
Press and hold the PRG button until the display shows
SET PRG
2
Select PRG SET to proceed with programming or PRG 1
to load the default values
PRG 1 default data
3
The ALARM threshold for (CH 1-2-3) is displayed.
Set the desired threshold, the Alarm LED flashes
Default 90°C
4
The TRIP threshold for (CH 1-2-3) appears and the Trip
LED flashes.
5
Set the desired threshold
Default 119°C
6
CH 1-2-3 is displayed
The Fan1 LED flashes
Default YES
7
Select YES/NO
8
The display shows (CH4)
Enabling CH4
9
Select YES or NO
with YES the CH4 is enabled
with NO the CH4 is disabled
10
The ALARM threshold for (CH4) appears and the Alarm
LED flashes.
If CH4=NO jump to step 16,
Default NO
11
Set the desired threshold
Default 120°C
12
The TRIP threshold for (CH4) is displayed.
The TRIP LED flashes
13
Set the desired threshold
Default 140°C
14
The display shows FAN 2 for (CH4)
Default Yes
15
Select YES/NO
16
The display shows ON (CH 1-2-3),
the FAN1 LED flashes
Default 70°C
17
Set the desired threshold FAN1 ON
If FAN1 NO is selected skip to
step 21
18
The display shows OFF (CH 1-2-3),
the FAN1 LED flashes
Default 60°C
19
Set the desired threshold FAN1 OFF
PROGRAMMING
FO 935 BASIC/D