TECSYSTEM FO 935 Скачать руководство пользователя страница 10

10 

FO 935

 

 

 

 

DISPLAY 
  
The first display is dedicated to temperatures. 

  

The second display to the monitored channel. 
  

When  the  device  is  switched  on  or  after  a  reset,  the  model  of  the  control  unit,  the  type  of  sensors,  VER  "00"  (firmware 
version) and the temperature range of the device and the identification abbreviation are always shown on the display. 

 

Pressing the MODE key, the display modes can be set: 

 

SCAN

: the control unit shows in scanning (every 2 seconds) all the enabled (°C) and disabled (NO) channels. 

 

AUTO

: the control unit displays the hottest channel automatically. 

 

MAN

: manual reading of the channel temperature using the up/down keys



 

 

T.MAX

:  the  display  shows  the  maximum  temperature  of  the  channel  selected  with  the  cursor  keys. 

In 

the 

event 

of 

fault, 

the 

Tmax 

value 

is 

replaced 

with 

the 

type 

of 

fault 

stored 

(fcc-foc). 

Turning 

on 

the 

Trip 

Alarm-Fault 

LED 

warns 

of 

any 

events 

that 

have 

occurred. 

The recordings are always successive to the moment in which the T.Max is reset (by pressing RESET). 

 

OPERATING PROGRAM CONTROL 

  

To control the protection levels programmed, press the PRG key twice to access the 

VIS 

programme. Repeatedly pressing 

the PRG key, you can scroll through all the previously loaded values in  sequence. After 1 minute's keyboard inactivity, the 
programming display procedure is automatically abandoned. 

  

To stop the display, press the ENT key. 

 
 
NOTES ON SCAN AND MAN FUNCTIONS

 

 
During the SCAN and MAN modes, the operation of the FO 935 can be displayed.

 

  

1) RUN cPU

This message appears upon ignition of the device. 

2) Ech Err

This message appears when damage in the EEPROM memory is detected. 
Pressing Reset will cancel the message and restore the original default parameters, listed in the  programming paragraph 
on pages 19-20 return the control unit to TECSYSTEM for repairs. 

3) TEC err: 

this message appears when a loss of communication is detected between the thermometric control unit and the 

CFO 521 concentrator. The temperatures shown on the display all appear at 0°C.

 

4) FO Err: 

this message appears when it is detected that one or more FO sensors are not working correctly 

FCC, FOC 

and

 

FLT, 

signals, see sensor diagnostics on page 17. 

 
In case of 

Err 

the FAULT relay will be de-energised. 

  

The above messages will be displayed following the 1-2-3-4 priority stated. 

  

  

 
LED TEST 

  

We suggest carrying out the control unit LED test regularly. 
For this operation, press the TEST key briefly; all the displays turn on for 2 seconds.

 

If one of the LEDS does not work, please return the control unit to TECSYSTEM for repair. 

  

 
ALARM RELAY TEST 

  

This  function  allows  you  to  carry  out  a  test  of  the  relays  operation  without  having  to  use  further  devices.  To start  the  test 
procedure,  press  and  hold  the  TEST  button  for  approximately  5  seconds:  the  TST  indication  appears  for  2  seconds 
confirming entry into the Relays Test mode. 

                                       

The lit LED indicates the relays to be tested, use the cursors 



to select the desired relay.

 

Press the SET and RESET keys to energise and de-energise the relay to be tested; the display will show ON-OFF. 
After 1 minute's keyboard inactivity, the RELAY TEST procedure will be automatically abandoned. 
To stop the RELAY TEST procedure, press the TEST key. 

 
ATTENTION: entering the relay test mode will temporarily disable the fail-safe function, relays with enable function   
switch (ALARM-TRIP-FAULT). 

  

ALARM RELAY SILENCING 

  

To silence the ALARM signal, press the RESET key: the relay will de-energise and the ALARM LED, which is on steady, will 
start to flash. Silencing is automatically disabled when the temperature goes below the ALARM threshold. 

 

Содержание FO 935

Страница 1: ...s with ISO9001 certified quality system http www tecsystem it R 1 1 12 01 22 Translations of the original instructions ENGLISH TECSYSTEM S r l 20094 Corsico MI Tel 39 024581861 Fax 39 0248600783 FO 93...

Страница 2: ...NCENTRATOR OPERATION 13 6 FO 935 ASSEMBLY 14 7 ELECTRICAL CONNECTIONS 15 FO 935 BASIC BACK FO 935 D BACK POWER SUPPLY 16 ALARMS AND VENTILATION 17 FAULT AND RESET MESSAGE SEQUENCE SENSOR DIAGNOSTICS C...

Страница 3: ...THE MODBUS INSIDE MODULE OPERATING NOTES DATA TRANSMISSION ON MODBUS NETWORK RS485 ELECTRICAL CONNECTIONS DATA FRAME DATA PACKET FUNCTION CODE 23 CODE 3 10 CODE 16 10 NOTES FOR REMOTE PROGRAMMING ERR...

Страница 4: ...90 and never touch with wet or damp hands If any liquid penetrates the control unit disconnect it immediately and contact technical assistance CLEANING Disconnect the power cable before cleaning the...

Страница 5: ...ews tightening torque 0 25Nm 1 Terminal 3 pitch poles 3 81 RS485 Code 2PL0366 Screws tightening torque 0 25Nm Only for version D CFO 521 Concentrator CFO 521 Concentrator Start guide and QR code 2 Ter...

Страница 6: ...n removable terminal boards OUTPUTS 2 alarm relays ALARM AND TRIP SPDT 1 relay for faulty probes or operating anomaly FAULT SPST 2 ventilation management relays SPST FAN1 and FAN2 Output relays with 1...

Страница 7: ...3 digits to display temperatures messages and channels 3 LEDs to display the state of the alarms of the selected channel ALARM TRIP FAULT 4 LEDS selection of display mode SCAN AUTO MAN T MAX 2 LEDs t...

Страница 8: ...5 C to 60 C Permitted humidity 90 without condensate Degree of protection IP00 PC UL 94 HB container Electronic part protective treatment Optional DIMENSIONS 145x106 7x55mm Concentrator fixing bracket...

Страница 9: ...S green LED ONLY FO 935 D 5 FAULT signalling red LED 16 3 digit channel display 6 FAN 1 yellow LED 17 T max mode selection red LED 7 FAN 2 yellow LED 18 Man mode selection yellow LED 8 Display mode se...

Страница 10: ...meters listed in the programming paragraph on pages 19 20 return the control unit to TECSYSTEM for repairs 3 TEC err this message appears when a loss of communication is detected between the thermomet...

Страница 11: ...ture of the concentrator ranges from 25 C to 60 C therefore ensure there is adequate space between the concentrator and the transformer Maximum humidity 90 non condensing The CFO 521 support bracket c...

Страница 12: ...ply the protection bracket using the M4 screws supplied FO FIBRE OPTIC TEMPERATURE SENSOR DIMENSIONS INSTALLATION READING POINT ST CONNECTOR CONNECTION OF THE CONC CFO 521 TO THE FO 935 CONTROL UNIT F...

Страница 13: ...rrect interpretation of the measured values it is advisable to combine the CH2 probe with the central phase V The CFO 521 concentrator has a Pt100 input RTD class A 2 3 wire probe for the possible con...

Страница 14: ...Control unit 2 Panel hole dimensions 0 8 mm tolerance 3 Identification label 1 Control unit 3 Fixing screws 2 Fixing blocks 4 Cross head screwdriver 1X100mm FO 935 ASSEMBLY 1 2 3 4 1MN0008 REV 0 Dril...

Страница 15: ...2 3 1 2 3 4 1 Power supply 85 260Vdc ac 50 60Hz 3 FO IN bus input for connection to the CFO 521 2 Relay ALARM TRIP FAULT FAN1 FAN2 4 RS485 Modbus Inside RTU output 1 Power supply 85 260Vdc ac 50 60Hz...

Страница 16: ...y high intensity overvoltages These problems occur if the main switch is closed and the transformer does not have the load no load test The above is much more evident when the 220 Vac voltage is taken...

Страница 17: ...e 18 NOTE always disconnect the unit before performing any electrical connections eeprom fault concentrator communication bus fault min temperature full scale exceeded max temperature full scale excee...

Страница 18: ...FAN1 and FAN2 and if programmed correctly can control the fans switching ON and OFF to cool the transformer The FAN1 and FAN2 contacts can manage cooling the transformer and the room where it is insta...

Страница 19: ...e display shows CH4 Enabling CH4 9 Select YES or NO with YES the CH4 is enabled with NO the CH4 is disabled 10 The ALARM threshold for CH4 appears and the Alarm LED flashes If CH4 NO jump to step 16 D...

Страница 20: ...played Blinking TRIP LED 29 Select YES or NO Default NO 30 FLS FAULT is displayed Blinking FAULT LED 31 Select YES or NO Default YES For version FO 935 BASIC skip to step 38 32 ADR datum is displayed...

Страница 21: ...ALARM TRIP and FAULT relays programming steps from 26 to 31 page 20 Selecting the YES NO setting introduces the Fail Safe and No Fail Safe functions ALARM AND TRIP By setting NO NO Fail safe the norma...

Страница 22: ...is inactive when in the following modes display programming and test relays RS485 ELECTRICAL CONNECTIONS As far as the signal cable to be used in order to ensure the correct network operation is conc...

Страница 23: ...t affecting the received message Also in the remote programming phase via ModBus it must be considered that the Alarm thresholds must be lower than the Trip thresholds and that the Fan on thresholds m...

Страница 24: ...to ModBus reading the register 7 NO ERROR CH_1 Trip Alarm CH_4 Trip Alarm FAN_1 ON OFF FAN_2 ON OFF Value HFN max see table SYSTEM Setting and Status CONTROL UNIT GENERAL NOTES The various models of t...

Страница 25: ...ASCII R 5 Qty channels 2 ASCII R 6 Options see notes Options see notes R 7 00 Incorrect datum received R see tab 8 00 Info various causes R see tab 9 00 Controls W see tab SYSTEM Setting and Status Ad...

Страница 26: ...sign 2 compl Ch1 temper alarm set point 1 C 190 C AL RW 28 2 compl sign 2 compl Ch1 temper trip set point 1 C 190 C TRP RW 29 2 compl sign 2 compl Ch2 temper 35 C 195 C R 30 2 compl sign 2 compl Ch2...

Страница 27: ...per 35 C 195 C R 38 2 compl sign 2 compl Ch4 max temperat 0 C 195 C R 39 2 compl sign 2 compl Ch4 temper alarm set point 1 C 190 C AL RW 40 2 compl sign 2 compl Ch4 temper trip set point 1 C 190 C TRP...

Страница 28: ...Ch4 Setting See Notes CHx RW 61 00 00 R 62 00 00 R 63 00 00 R 64 00 00 R CHANNELS 1 4 Status Address LO 10 Data HI Data LO Notes 1 Notes 2 W write W write W read write 65 Ch1 story Ch1 status See Not...

Страница 29: ...TUS CHn STORY BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 TRIP ALARM FLT FOC FCC RELAY STATUS coil energising status BIT 7 BIT 6 BIT 5 BIT 4 BIT 3 BIT 2 BIT 1 BIT 0 FAULT Relay 1 ON TRIP Relay 1 O...

Страница 30: ...normal domestic waste Returning of used electrical appliances contact TECSYSTEM or the TECSYSTEM agent to receive information on correct disposal of the appliances TECSYSTEM is aware of the impact it...

Страница 31: ...31 FO 935 TECHNICAL INFORMATION ufficiotecnico tecsystem it COMMERCIAL INFORMATION info tecsystem it USEFUL CONTACTS...

Отзывы: