V2.1 | 11-2022 Installation and Commisioning of Tankspion-IoT devices
6
Tankspion-IoT PRO
Connection of the probe line:
•
Low voltage, 4 - 20 mA,
2 wire principle,
connection to terminals
with red at terminal P+ and
black at terminal P-
•
3 wire sensors
(special version):
Ub to terminal P+, signal line
(output) to terminal P- and
ground wire to GND.
•
PT1000 temperature sensor:
Connect the 2-wire cable of
the temperature sensor with
red to the Temp-In terminal
and white to the GND
terminal.
1
2
1
2
3
4
5
6
7
3
4
Alarm Contact Inputs:
•
The Tankspion-IoT PRO has two configurable contact inputs, e.g. for connection of a
burner fault signal contact (potential-free switching contact, interconnect a relay if
necessary).
•
Alarm message on occurrence of a signal at input 'Alarm 1' (DIG-IN + GND).
Message text: Alarm1 (configurable).
If the contact closes (configurable), the remote alarm message occurs after 3 min.
•
Alarm message on occurrence of a signal at input 'Alarm 2' (ALARM IN + GND).
Message text: Alarm2 (configurable).
•
If the contact opens (configurable), the remote alarm message occurs after 3 min.