N3 Drive Operations Manual
(Advanced) Parameter Details; A122
Cont.
; 123 - 128
70
Rated Current
(%)
Rated Frequency
(%)
Rated Current
(%)
Rated Frequency
(%)
Rated Current
(%)
Rated Frequency
(%)
103
63
30
100
A Non-Inverter duty motor OL1 protection curve
OL = 103% Start , 150% / 1 Min.
A
Rated Current
(%)
Rated Frequency
(%)
113
63
30
100
B Non-Inverter duty motor OL1 protection curve
OL = 113% Start , 123% / 1 Min.
B
0.13
30
100
C Inverter duty motor OL1 protection curve
OL = 103% Start , 150% / 1 Min.
C
103
113
30
100
D Inverter duty motor OL1 protection curve
OL = 113% Start , 123% / 1 Min.
D
Electronic overload OL1 protection for inverter and non-inverter duty motors (current / frequency)
Fig. 19.25
1.) Over torque is defined as when the output torque exceeds the setting of parameter A125 (Over torque threshold %)
for a time exceeding the setting of parameter A126 (Over torque activation delay Sec.).
Over Torque:
A124 = 0000: When there is over torque, the inverter will continue to run and flashes
“OL3” until the output
torque decreases to less than the A125 set value.
= 0001: When there is over torque, the inverter coasts to stop and flashes
“OL3”. After the fault clears,
the “Reset” key on the keypad or external reset must be activated to restart the drive.
Note: When parameters A105 and / or A106 (Multifunction output terminal) = 05, the relay
Output(s) will be activated on over torque.
2.) Under torque is defined as when the output torque is less than the setting of parameter A127 (Under torque
threshold level %) for a time exceeding the setting of parameter A128 (Under torque activation delay Sec.).
Cont.
A123
Over/Under Torque Detection
Selection
0000: Disable Over/Under Torque Operation.
0001: Enable Over/Under Torque Operation Only
if at Set Frequency.
0002: Enable Over/Under Torque Operation
while the Drive is in Run Mode.
A124 Motor Type Selection
0000: Drive will Continue to Operate After
Over/Under Torque is Activated.
0001: Coast-to-Stop After Over/Under Torque is
Activated.
A125 Over Torque Threshold Level (%) 100 - 200%
A126
Over Torque Activation Delay
Time (Sec.)
0.0 - 25.0 Sec.
A127
Under torque Threshold Level
(%)
0
– 100 %
A128
Under torque activation Delay
Time (Sec.)
0.0 - 25.0 Sec.