N3 Drive Operations Manual
A (Advanced) Parameter Summary; A148
– A156
44
Parameter
No.
LCD Display
Description
Range/Code
Factory
Setting
Remarks
A148
Fdbk Sel
Feedback Loss
Detection Mode
0000: Disabled
0001: Enabled - Drive Continues to
Operate After Feedback Loss
0002: Enabled - Drive "STOPS"
After Feedback Loss
0000
A149
Fdbk Lvl
Feedback Loss
Detection Level
(%)
0 - 100
0
A150
Fdbk Loss Time
Feedback Loss
Detection delay
Time (Seconds)
0.0 - 25.5
1.0
A151
PID I Limit
Integration Limit
Value (%)
0 - 109
100
1
A152
I Time value Sel
Integration Value
Resets to Zero
when Feedback
Signal equals the
set point
0000: Disabled
0001:1 Second
0030:30 Seconds
0000
A153
I Error Margin
Allowable
integration
Error Margin
(Units)
(1 Unit = 1/8192)
0 - 100
0
A154
AIN AI2 Source
AIN or AI2 Source
signal
0000: AIN = 0 -10V or 0 - 20mA
AI2 = 0 -10V or 0 - 20mA
0001: AIN = 0 -10V or 0 - 20mA
AI2 = 2 -10V or 4 - 20 mA
0002: AIN = 2 -10V or 4 - 20 mA
AI2 = 0 -10V or 0 - 20mA
0003: AIN = 2 -10V or 4 - 20 mA
AI2 = 2 -10V or 4 - 20 mA
0000
7
A155
Sleep Level
Sleep Function
Operation Level
0.00 - 400.00
0.0
A156
Sleep Delay
Time
Sleep Function
Delay Time
0.0 - 25.5
0.0
Cont.
NOTES: