N3 Drive Operations Manual
(Advanced) Parameter Details; A105
– A108
Cont.
66
The following Fig.’s show some examples of the functions of output relays R1 (A105) and R2 A106)
Run
Command
(b000)
RUN
STOP
Frequency
Reference
(b004)
Inverter Output
Frequency
Relay Output
Signal
If Inverter is
Stopped the
Relay will not
Operate
Target frequency
detection range
(A108)
A105 / A106 = 01 Frequency Reached ( Frequency Reference ± A108)
Target frequency
detection range (A108)
Frequency
Reference
(b004)
Fig. 19.19
Run
Command
(b000)
RUN
STOP
Inverter Output
Frequency
Relay Output
Signal
Set frequency
detection range (A108)
If Inverter is Stopped or has
no Reference Frequency
the Relay will not Operate
Output Freq.
Detection Level
(A107)
Set frequency
detection range
(A108)
A105 / A106 = 02 Set Frequency Reached (Set Frequency ± A108)
Freq. Reference
(b004)
Output Freq.
Detection Level
(A107)
Output Frequency Detection Function FOUT = A107 ± A108
Operation Conditions:
A. I Output Frequency
– Frequency Reference (b004) I < Frequency Threshold Level (A108)
B. I Output Frequency
– Detection Level (A107) I < Frequency Threshold Level (A108)
Fig. 19.20
Cont.