4-35
5) 03-11=
【
4
】
.
RY1 will be on while Output Freq.
>
Frequency Detection Level
(03-13).
6) 03-11=
【
5
】
.
RY1 will be on while Output Freq.
<
Frequency Detection Level
(03-13).
03-15
Output Current Agree Setting
Range
【
0.1~15.0
】
A
03-16
Current Agree Delay Time
Range
【
0.1~10.0
】
Sec
¾
03-11=
【
13
】
.
RY1 will be on as soon as the output current value > current agree setting
(03-15).
¾
03-15: Setting range (0.1~15.0 Amps) as required according to the rated motor current.
¾
03-16: Setting range (0.1~10.0) unit: seconds.